6ED1052-2CC08-0BA0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
Via its integrated Ethernet interface, the module communicates with LOGO! 8 base devices, LOGO! TDE text displays, SIMATIC controllers, Basic Panels and PCs, while the built-in web server allows remote access and monitoring directly from a browser; programs are stored and transferred on standard micro CF cards. The system supports modular expansion addressing up to 24 digital inputs, 20 digital outputs, 8 analog inputs and 8 analog outputs. The 71.5 mm wide housing (4 module units) clips onto a 35 mm DIN rail, operates from -20 to +55 °C (no condensation), and holds CE, CSA, UL, FM and marine approvals — developed to IEC 61131 and compliant with VDE 0631, with EMC emissions of limit class B for use in residential areas.
Fully Integrated 24 V DC24 V DC supply/inputs/outputs (transistor 0.3 A, outputs with electronic short-circuit protection)
4 Multiplexed Analog Inputs4 of the 8 DIs can be switched to 0-10 V analog inputs — one device, multiple roles
400 Function BlocksAmple program capacity for complex interlocking, sequencing and control logic
Integrated Ethernet + Web ServerNetworks with LOGO!/SIMATIC/PCs; remote monitoring via browser
Modular ExpansionExpandable to 24 DI / 20 DO / 8 AI / 8 AO, plus LOGO! TDE text display support
Global ApprovalsCE / CSA / UL / FM / marine approvals; IEC 61131 and VDE 0631 compliant
Model | 6ED1052-2CC08-0BA0 (LOGO! 24CEo logic module, LOGO! 8.3, without display) |
|---|---|
Supply voltage | 24 V DC |
Digital inputs | 8 DI (24 V DC), of which 4 can be used in analog mode (0-10 V) |
Digital outputs | 4 DO (24 V DC transistor), max. 0.3 A per signal "1"; outputs with electrical short-circuit protection (1 A) |
Program capacity | 400 interlinkable function blocks; integrated real-time clock and 400 time switching clocks (power reserve 480 h) |
Communication | Integrated Ethernet interface (LOGO! 8, LOGO! TDE, SIMATIC controllers/panels, PC); integrated web server |
Expansion capability | Connects digital/analog expansion modules; max. 24 DI / 20 DO / 8 AI / 8 AO addressable |
Program storage | Standard micro CF card |
Display / programming | No display or keyboard; drag-and-drop programming with LOGO! Soft Comfort / LOGO! Web Editor |
Mounting | 35 mm standard DIN rail, 4 module units wide |
Dimensions | 71.5 mm (W) × 90 mm (H) × 58 mm (D) |
Protection rating | IP20 (EN 60529) |
Ambient conditions | Operation -20 ~ +55 °C (no condensation); storage/transport -40 ~ +70 °C; altitude -1000 ~ +2000 m |
EMC | Emission of radio interference per EN 55011, limit class B (for use in residential areas) |
Approvals | CE, CSA, UL, FM, marine approvals; developed per IEC 61131, compliant with VDE 0631 |
Q1: What is the 6ED1052-2CC08-0BA0, and what does "CEo" mean?
It is the Siemens LOGO! 8.3 intelligent logic module base device, model LOGO! 24CEo. "CE" indicates that supply, inputs and outputs are all 24 V DC with transistor outputs; "o" (ohne) means without display and keyboard — programs are downloaded via Ethernet from a PC, making it more cost-effective than display versions.
Q2: What if the I/O count is not enough?
The base device itself offers 8 DIs (4 multiplexable as 0-10 V analog inputs) and 4 DOs. It connects LOGO! 8 digital/analog expansion modules (e.g., DM16 24R) via the system bus, addressing up to 24 digital inputs, 20 digital outputs, 8 analog inputs and 8 analog outputs, plus a LOGO! TDE text display.
Q3: What loads can the outputs drive?
The 4 outputs are 24 V DC transistor type rated max. 0.3 A per signal "1", with built-in 1 A electrical short-circuit protection. High-current loads (contactors, lighting, motors) are switched via the outputs driving a LOGO! Contact switching module or external relays.
Q4: Without a display, how are programs created and the device monitored?
Via the integrated Ethernet interface, programs are created in LOGO! Soft Comfort (drag-and-drop graphical programming) or LOGO! Web Editor on a PC and downloaded to the module. The built-in web server allows remote status and alarm monitoring from a browser. For local operation, a LOGO! TDE text display can be connected; programs can be copied on standard micro CF cards.
Q5: What communication and integration options are supported?
The Ethernet interface connects LOGO! 8 base devices, LOGO! TDE, SIMATIC controllers, Basic Panels and PCs, allowing integration into larger automation architectures; the integrated web server enables remote monitoring — well suited for connected building and equipment management.
Q6: What timing functions are available? Will data be lost after a power failure?
An integrated real-time clock supports up to 400 time switching clocks with daily/weekly/yearly schedules. The clock has a 480-hour power reserve, so no re-synchronization is needed after short power outages.
Q7: What are typical applications?
Typical applications include pump and fan control, lighting and blinds management, HVAC, gate and garage door control, and small machine interlocking. With EMC emission limit class B, it can be used directly in residential areas — an economical replacement for traditional relay control cabinets.
Q8: Which approvals does the product hold?
It is CE, CSA, UL and FM approved and holds marine approvals; developed per the IEC 61131 programmable controller standard and compliant with VDE 0631, with IP20 protection — meeting market access requirements in most regions worldwide.