6ES7532-5HD00-0AB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The module's 4 output channels form one group, electrically isolated from the backplane bus and the load voltage L+. Conversion time is 0.5 ms per channel, with a minimum cycle time of 3.2 ms for all channels. Voltage outputs are short-circuit protected (max. 24 mA short-circuit current); current outputs provide max. 22 V no-load voltage.
Wire break (current mode), short circuit (voltage mode), overflow/underflow and supply voltage failures are all diagnosed and raise diagnostic alarms; each channel has green/red status LEDs for at-a-glance fault indication. Substitute values can be configured so that, on CPU STOP or channel fault, the module outputs a predefined safe value to keep the process under control. Reparameterization and calibration in RUN (CiR) are supported for maintenance without downtime.
At only 35 mm wide, the module ships with feeding elements, shield contact components and shielding terminals; the front connector (screw-type or push-in) must be ordered separately.
● 4 universal U/I outputs: 0–10 V, 1–5 V, ±10 V voltage and 0/4–20 mA, ±20 mA current — one module covers all common actuator signal types
● 16-bit resolution, 0.3% accuracy: operational error limit ±0.3% of output range (basic error ±0.2% at 25 °C); output ripple only ±0.02%
● Fast response: 0.5 ms conversion time per channel, 1.5 ms settling time with resistive loads
● Comprehensive diagnostics: wire break, short circuit, overflow/underflow and supply voltage monitoring with per-channel LED indication
● Substitute values: predefined safe outputs on CPU STOP or channel fault for improved process safety
● Safe disconnection of load groups up to SIL2 (EN IEC 62061) / Cat. 2, PL c (EN ISO 13849-1)
● 35 mm narrow housing, tool-free mounting: integrated shield connection on the uniform S7-1500 rail, saving cabinet space
Item | Value |
Order number | 6ES7532-5HD00-0AB0 |
Product type designation | AQ 4xU/I ST |
Applicable systems | SIMATIC S7-1500 / ET 200MP |
Number of analog outputs | 4 (one group of 4 channels) |
Output ranges (voltage) | 0–10 V, 1–5 V, −10–+10 V |
Output ranges (current) | 0–20 mA, −20–+20 mA, 4–20 mA |
Resolution (with sign, incl. overrange) | max. 16 bit |
Conversion time per channel | 0.5 ms |
Cycle time (all channels) | min. 3.2 ms |
Accuracy (operational error limit) | ±0.3% (voltage/current, of output range) |
Load impedance | voltage ≥1 kΩ (≥0.5 kΩ at 1–5 V); current ≤750 Ω |
Load voltage (L+) | 24 V DC, permissible range 20.4–28.8 V |
Current consumption | max. 190 mA (at 24 V DC supply) |
Backplane bus power / power loss | 0.6 W / typ. 4 W |
Diagnostic functions | wire break (current), short circuit (voltage), overflow/underflow, supply voltage monitoring |
Safe disconnection of load groups | SIL2 (EN IEC 62061) / Cat. 2, PL c (EN ISO 13849-1) |
Shielded cable length | max. 200 m (voltage) / 800 m (current) |
Dimensions (W×H×D) | 35 × 147 × 129 mm |
Weight | approx. 310 g |
Engineering / firmware | TIA Portal from V12; firmware V2.2.0, FW update possible |
Q1: Can voltage and current signals be output simultaneously?
A: Yes. All 4 channels are universal U/I outputs; each channel can be independently configured as voltage or current, with ranges set per channel in TIA Portal.
Q2: Is a front connector included?
A: No. The scope of supply includes feeding elements, shield contact components and shielding terminals. A 40-pin front connector must be ordered separately: screw-type 6ES7592-1AM00-0XB0 or push-in 6ES7592-1BM00-0XB0.
Q3: How does the module help with on-site troubleshooting?
A: It diagnoses wire break (current outputs), short circuit (voltage outputs), overflow/underflow and supply voltage failures, indicated per channel by red LEDs. Diagnostic messages are transferred to the CPU via the backplane bus and trigger diagnostic alarms for fast fault localization.
Q4: What happens to the outputs when the CPU stops?
A: A substitute value (e.g. a predefined safe value) can be configured per channel. On CPU STOP or channel fault, the module outputs the substitute value, preventing actuators from staying in an undefined state.
Q5: How does this module differ from the HF (High Feature) version?
A: This is the Standard (ST) version with 16-bit resolution and 0.3% accuracy, well suited for conventional process control. HF versions offer around 8× faster conversion, isochronous operation and extended diagnostics for high-dynamics, high-precision applications. Contact us for selection advice if you need higher speed or accuracy.