6ES7214-1AF40-0XB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The CPU 1214FC merges safety control and standard control into one device. The standard program uses the full S7-1200 instruction set, while the safety program runs in a separate F-runtime group called by the F organization block (default 100 ms cyclic interrupt, priority 9) without interfering with standard logic. Safety code can only be written in F-LAD/F-FBD using TÜV-certified safety blocks; compilation generates a safety signature (CRC) that changes with any modification and requires a fresh download. On the safety side, PROFIsafe links the CPU to SM 1226 fail-safe modules and distributed F-devices, transporting process data, status bytes, and checksums securely. The CPU integrates one PROFINET interface (RJ45, 100 Mbit/s, PROFINET IO controller/device, PROFIsafe, OPC UA server, web server) and retains high-speed counting, pulse outputs, PID, and positioning axes for routine motion and control tasks beyond safety functions.
● Standard and safety in one CPU: parallel execution of standard and safety programs, eliminating separate safety relays
● SIL 3 / PL e safety rating: compliant with IEC 61508 (SIL 3) and ISO 13849-1 (PL e)
● Native PROFIsafe: safe communication with SM 1226 F-DI/F-DQ modules and distributed F-devices
● 200 KB work memory: shared by standard and safety programs; 4 MB load memory plus memory card option
● Full technology functions: 6 high-speed counters (up to 100 kHz), 4 × 100 kHz pulse outputs, 8 positioning axes, PID
● Communication and diagnostics: PROFINET, OPC UA server, MODBUS, web server, 2 configurable traces
Item | Specification |
Order No. / Model | 6ES7214-1AF40-0XB0 / CPU 1214FC DC/DC/DC (S7-1200F) |
Firmware / Engineering | V4.7 / STEP 7 (TIA Portal) V20 or higher; STEP 7 Safety license required for safety programs |
Safety Rating | Up to SIL 3 (IEC 61508) and PL e (ISO 13849-1) in safety mode; PROFIsafe supported |
Onboard Digital Inputs | 14 × 24V DC, sink/source capable; 6 usable for high-speed counting |
Input Levels / Delay | "1": 15V DC at 2.5 mA; "0": 5V DC at 1 mA; delay 0.1 µs to 20 ms, parameterizable |
Onboard Digital Outputs | 10 × 24V DC transistor (sourcing), 4 of them 100 kHz pulse train outputs |
Output Capacity / Delay | 0.5 A per point (resistive), 5 W lamp load; max. 1 µs / 5 µs switching delay |
Onboard Analog Inputs | 2 × 0–10V, 10 bit including sign, input resistance ≥100 kΩ, 625 µs conversion per channel |
Counting / Pulse | 6 counters up to 100 kHz (3 × 100 kHz + 3 × 30 kHz single-phase); 4 PTO outputs up to 100 kHz |
Memory | Work memory 200 KB; load memory 4 MB (extendable via SIMATIC memory card); retentive 14 KB |
Instruction Times | Bit 0.08 µs; word 1.7 µs; floating point 2.3 µs |
Expansion | 1 signal board (SB) + 8 signal modules (SM, incl. SM 1226 F-modules) + 3 communication modules (CM) |
Interfaces | 1 × PROFINET (RJ45, 100 Mbit/s, isolated); IO controller for up to 16 devices; OPC UA server (Basic license), MODBUS, web server |
Supply / Current | 24V DC (20.4 to 28.8V, reverse-polarity protected); 500 mA CPU only, 1500 mA max. with all expansion |
Power Loss | Typ. 12 W |
Clock Backup | Hardware real-time clock, maintenance-free backup approx. 480 h (typ.), ≤60 s/month at 25°C |
Dimensions / Weight | 110 × 100 × 75 mm / approx. 415 g; IP20 |
Ambient Temperature | 0 to 55°C (horizontal) / 0 to 45°C (vertical); storage -40 to 70°C |
Approvals | CE, UL, cULus, FM, RCM, KC, marine; TÜV type examination for functional safety |
Q1: How does the 1214FC differ from a standard 1214C? Can it be swapped in directly? The 1214FC is the fail-safe CPU (order no. 1AF40) and can execute safety programs at up to SIL 3 / PL e in addition to standard control; a standard 1214C (e.g. 1AG40) has no F-runtime group and cannot perform safety functions. Mounting and wiring are essentially identical, but the project must be re-configured and recompiled for an F-CPU — downloading a standard project to an FC is rejected by the safety signature check.
Q2: Can onboard I/O alone handle safety functions? What else is needed? The onboard 14 DI / 10 DQ can be used as F-I/O in the safety program (the usable channel count depends on firmware and configuration). For more safety points or higher drive capability, add SM 1226 fail-safe modules (e.g. F-DI 16×24V DC, F-DQ 4×24V DC/2A). A STEP 7 Safety license (Basic or Advanced) is also required, along with safety-compliant wiring, validation, and acceptance documentation.
Q3: Are the safety and standard programs separated? Do they interfere? They run in parallel in the same CPU but are isolated: the safety program lives in a separate F-runtime group invoked by the F organization block (default 100 ms cyclic interrupt) and may only use F-LAD/F-FBD with certified safety blocks, while the standard program uses the full instruction set. Every change to the safety program alters the safety signature and triggers a STOP→RUN sequence, so plan modifications during scheduled downtime.
Q4: Will this model remain available long term? Siemens lists the product with a phase-out effective 1 November 2026 (successor: S7-1200 G2 series). Spare-part and maintenance purchases remain possible, but new projects should evaluate the corresponding G2 fail-safe CPU to avoid future lead-time constraints.