6ES7355-0VH10-0AE0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The FM 355 C offloads closed-loop computation from the CPU to module hardware: each of the four channels acquires its process value, executes the PID algorithm, and drives its output without consuming OB1 scan time, so a busy program cannot slow the control cycle. Analog inputs accept thermocouples, Pt100 and other resistance thermometers, and 0~10V, 0~20mA, or 4~20mA standard signals, with one additional input dedicated to thermocouple cold-junction compensation. Outputs are four continuous analog channels configurable as 0~10V or 0~20mA / 4~20mA, driving control valves, variable-frequency drives, and analog actuators directly. Four operating modes are supported — automatic, manual, safety, and backup. When the CPU stops or backplane communication is lost, the module switches to backup mode and maintains the loop at the last setpoint, preventing a valve from slamming shut or fully open and ruining the batch. Configuration uses the multilingual package supplied with the module together with the FM 355 function blocks in STEP 7, which read and write setpoints, process values, PID parameters, and alarm states.
● Four independent loops: separate sampling and computation per channel, PID and fuzzy temperature control with autotuning
● No CPU cycle load: algorithms run in the module, unaffected by OB1 scanning or program load
● Broad input coverage: thermocouples, Pt100 resistance thermometers, voltage, and current signals connect directly
● Backup-mode operation: keeps the loop closed at the last setpoint when the CPU stops, protecting process and equipment
● Continuous analog outputs: four channels at 0~10V / 0~20mA / 4~20mA for valves and drives
● Complete engineering package: multilingual configuration package, manual, and dedicated FM 355 function blocks included
Item | Specification |
Order No. / Model | 6ES7355-0VH10-0AE0 / FM 355 C |
Product Type | S7-300 closed-loop control function module (continuous action) |
Control Channels | 4 independent, PID / fuzzy temperature control with autotuning |
Analog Inputs | 4: thermocouple / Pt100 and other resistance thermometers / voltage / current |
Additional Input | 1, for thermocouple cold-junction compensation |
Digital Inputs | 8, 24V DC, according to IEC 61131 type 2 |
Analog Outputs | 4, configurable 0~10V / 0~20mA / 4~20mA (continuous) |
Operating Modes | Automatic / manual / safety / backup (loop maintained when CPU stops) |
Load Voltage L+ | 24V DC (20.4 to 28.8V), reverse polarity protected |
Backplane Bus Current | Max. 75 mA (5V DC) |
Power Loss | Typ. 6.5W, max. 7.8W |
Front Connectors | 2 × 20-pin (separate sensor and actuator sides) |
Cable Length | Shielded cable up to 1,000 m |
Compatible Hosts | S7-300 central rack; ET 200M (with S7-300/400 DP master) |
Configuration | Supplied multilingual configuration package plus STEP 7 FM 355 function blocks (FB) |
Mounting | S7-300 standard rack / DIN rail |
Q1: How do I choose between FM 355 C (0VH10) and FM 355 S (1VH10)? Look at the actuator type. The C version provides four continuous analog outputs (0~10V / 0~20mA / 4~20mA) for control valves, drives, and analog actuators; the S version provides eight step/pulse outputs for electric actuators, heating elements, and solid-state relays (SSR).
Q2: What advantage does it have over "SM analog modules plus PID in the CPU"? The FM 355 runs PID in module hardware, so it consumes no CPU scan time and keeps a stable control cycle. When the CPU stops or communication fails, it continues in backup mode, whereas CPU-based PID loses its output with the CPU.
Q3: Which sensors can be connected? The four analog inputs accept thermocouples, Pt100 and other resistance thermometers, and 0~10V, 0~20mA, or 4~20mA standard signals. For thermocouples, the additional fifth input provides cold-junction compensation to improve accuracy.
Q4: Can it directly replace the FM 355-2 C (2CH00)? No. The two are different generations with firmware and configuration packages that are not fully interchangeable; replacement requires reconfiguration and recompiling the program. This model is also in the discontinued/spare-part phase, so new projects should evaluate S7-1500 temperature control solutions.