6ES7288-1CR60-0AA0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The CPU CR60 combines controller, power supply, and I/O in one housing that mounts directly on a standard DIN rail, eliminating an extra rack. Its Ethernet port (10/100 Mbit/s, transformer-isolated) handles program download and device networking, while the RS485 port (up to 187.5 kbps) connects drives, meters, and other field devices; an optional CM01 signal board adds further communication ports. Program memory is 12 KB with 8 KB of user data, and basic instruction execution takes about 150 ns. Four high-speed counters and up to eight PID loops cover positioning, counting, and closed-loop control, and a microSDHC slot supports program and firmware updates.
● 60 onboard I/O points: 36 × 24V DC inputs plus 24 × 2A relay outputs, reducing add-on modules
● Dual communication ports: standard Ethernet and RS485, with S7 communication and PROFINET IO
● Wide-range power supply: 85~264V AC (47~63Hz) for different grid conditions
● Fast processing: approx. 150 ns per bit instruction, 4 × 100 kHz high-speed counters
● Built-in PID: up to 8 closed-loop channels with continuous or binary outputs
● Easy maintenance: microSDHC card for program and firmware updates, DIN-rail mounting
Item | Specification |
Order No. / Model | 6ES7288-1CR60-0AA0 / CPU CR60 AC/DC/Relay |
Digital Inputs | 36 points, 24V DC ("1": +15~+30V; "0": <5V) |
Digital Outputs | 24 relay outputs, 2A resistive (lamp load DC 30W / AC 200W) |
Power Supply | 85~264V AC, 47~63Hz; 24V DC sensor supply max. 300mA |
Program / User Data Memory | 12 KB / 8 KB |
Instruction Execution Time | Bit 150 ns; word 1.2 µs; floating point 3.6 µs |
Communication Ports | 1× Ethernet (10/100 Mbit/s, 1500V AC isolated); 1× RS485 (≤187.5 kbps) |
High-Speed Counting | 4 channels at 100 kHz single-phase (or 2 at 50 kHz A/B phase) |
PID Loops | Up to 8 |
Real-Time Clock | Hardware clock, no battery backup, approx. 7-day retention |
Memory Card | microSDHC (optional) for program and firmware updates |
Power Loss | 20W max |
Mounting | Standard DIN rail |
Programming Software | STEP 7-Micro/WIN SMART |
Q1: What is the difference between the CR60 and the SR60? Both offer the same I/O count (36DI/24DO); the CR60 has relay outputs with an AC supply, while the SR60 has transistor outputs with a 24V DC supply. Choose by load type and available power.
Q2: How can I add I/O if the onboard points are insufficient? Use S7-200 SMART expansion modules for additional digital or analog channels, or signal boards for extra communication ports and a few I/O points, without consuming extra cabinet space.
Q3: Which engineering software is supported? Programming uses STEP 7-Micro/WIN SMART; program download and online monitoring run over the Ethernet port.
Q4: Can the relay outputs drive contactor coils directly? Yes, within the 2A resistive contact rating. Surge suppression is recommended for inductive loads to extend contact life.