1769-PB4
AB
| Availability: | |
|---|---|
| Quantity: | |
A CompactLogix controller and its expansion I/O share one 1769 backplane: logic runs from 5.1V, while field-side and communication circuits use the 24V auxiliary rail. As points are added, bus loading approaches the limit of the built-in supply — the 1769-PB4 re-establishes an independent power budget, converting an external 24V DC source into stable 5.1V and 24V outputs.
It mounts anywhere in an I/O bank and accepts up to eight modules per side (sixteen in total), ideal where no extra rail fits. A 19.2–31.2V DC input rides through brownouts; both outputs are current-limited and short-circuit protected, and a fault latches the output off so it cannot spread to adjacent modules. Pure hardware — no configuration or firmware — with removable terminals and a 35 mm DIN latch for tool-free replacement. Works with all 1769 I/O and 1769-L1x/L2x/L3x controllers.
1
High-capacity dual outputsIndependent 5.1V/4.0A and 24V/2.0A, low ripple.
2
Wide 19.2–31.2V DC inputRides through brownouts and line fluctuations.
3
Drives up to 16 I/O modulesEight per side, close to the load, space-saving.
4
Protection & fault isolationOvercurrent, short, overvoltage, thermal latch.
5
Configuration-free start-upNo programming, firmware or parameters.
6
Fanless industrial designNatural cooling, 0–60 °C full load, 5g vibration.
Catalog no. | 1769-PB4 | Product family | CompactLogix / Compact I/O |
Function | DC expansion power supply | Nominal input | 24V DC (19.2–31.2V DC) |
Output 1 | 5.1V DC / 4.0 A | Output 2 | 24V DC / 2.0 A |
Input power | 100 VA @ 24V DC | Inrush current | ≤ 30 A @ 31.2V DC |
Dissipation | 14.5 W @ 60 °C, full load | Isolation | 75V cont., 1697V DC / 1 s |
Protection | Overcurrent, short circuit, overvoltage and overtemperature latch; reset by cycling power | ||
Fuse | Replaceable — Wickmann 19193-6.3A / Littelfuse 021706.3MXP | ||
Mounting | 35 mm DIN rail / panel | Wire size | 22–14 AWG, 90 °C copper |
Dimensions | 118 × 70 × 87 mm | Weight | 630 g (1.39 lb) |
Operating temp. | 0–60 °C (−40–85 °C storage) | Humidity | 5–95%, non-condensing |
Vibration / shock | 5g @ 10–500 Hz / 20g, 30g | Altitude | 2000 m max |
Certifications | c-UL-us, CE, ATEX, IECEx, CCC, UKCA, ABS; open-type enclosure, in-cabinet mounting | ||
QWhen is a 1769-PB4 required?
When I/O demand exceeds the controller's integral supply, or the module count exceeds the bus distance rating.
QCan it power sensors or solenoids?
No. The 24V output serves module circuitry only; field devices need a separate supply.
QDoes it accept 220V AC input?
No. For AC supplies use the 1769-PA4 (120/240V AC, same output).
QCan it share a rail with PA4 / PA2 units?
Yes, but each supply feeds its own I/O bank and budgets are calculated per bank.
QNo output or an abnormal LED?
Check input voltage, polarity, load shorts and the fuse, then cycle power to reset.
QIs configuration or firmware needed?
No — it is ready out of the box and doubles the capacity of the 1769-PB2.