6ES7231-5PD32-0XB0

The SIMATIC S7-1200 SM 1231 RTD analog input module (order no. 6ES7231-5PD32-0XB0) converts resistance signals directly into temperature values inside the controller. Four channels accept the common platinum, nickel and copper resistance thermometers — Pt10 / Pt50 / Pt100 / Pt200 / Pt500 / Pt1000, Ni100 / Ni120 / Ni200 / Ni500 / Ni1000, Cu10 / Cu50 / Cu100 and LG-Ni1000 — as well as plain resistance in the 0–150 Ω, 0–300 Ω and 0–600 Ω ranges.

Unlike a generic analog input module, no transmitter and no conversion block are needed: connect the sensor with 2, 3 or 4 wires and the module delivers the temperature in °C or °F. Resolution is 15 bit plus sign (16-bit ADC) with an integrating measurement principle, so readings stay stable in the electrically noisy environment typical of ovens, dryers, extruders and HVAC plant.

Diagnostics cover wire break and supply voltage, reported to the CPU as diagnostic alarms, with a status LED per channel and a maintenance LED on the front. The module occupies a single 45 mm slot to the right of the CPU and is powered from the backplane bus.
  • 6ES7231-5PD32-0XB0

  • Siemens

Availability:
Quantity:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
sharethis sharing button

Temperature measurement without transmitters. The usual way to read a Pt100 is to buy a transmitter per channel, wire it to a 4–20 mA input and scale the value in the program. This module removes all three steps. Each channel measures resistance directly, and the sensor curve is selected on the module — so the value arriving in the CPU is already a temperature in °C or °F. For a machine with four temperature zones — a reflow oven, a dryer tunnel, an injection unit, a chiller header — the saving is four transmitters, four power feeds and four scaling blocks per module.

2-, 3- and 4-wire connection. The wiring method determines what the reading actually means. Two-wire connection is the simplest but adds the resistance of both leads to the sensor value — roughly 0.4 Ω per 10 m of 0.5 mm² copper, which is about 1 °C of error on a Pt100. Three-wire connection compensates the lead resistance and is the normal choice in machinery; four-wire connection eliminates it entirely and is used for narrow spans and laboratory-grade accuracy. All three are supported on every channel, and the method is selected in the device configuration.

Resolution, rejection and diagnostics. 15 bit plus sign gives a temperature step far finer than the accuracy of the sensor itself, so the module is never the limiting element. Series-mode rejection of 85 dB at 50 / 60 / 400 Hz and common-mode rejection of at least 120 dB keep mains hum and drive interference out of the reading — the 400 Hz setting exists specifically for machines with 400 Hz supplies and for fast-cycling thermal processes. Basic error is ±0.1 % of the configured range at 25 °C, ±0.2 % over the full temperature range to 55 °C, with a steady-state repeat accuracy of ±0.05 %. Wire-break detection identifies a disconnected or burnt sensor, which is the most common failure in a temperature loop and the one that otherwise shows up as a plausible but wrong reading.

① Direct RTD input, no transmitter
Pt10 … Pt1000, Ni100 … Ni1000, Cu10 / Cu50 / Cu100 and LG-Ni1000 measured directly; value delivered in °C or °F.

② 15 sensor types on one module
One article covers platinum, nickel and copper sensors plus 150 / 300 / 600 Ω resistance ranges — fewer variants to stock.

③ 2-, 3- and 4-wire
Two-wire for simple loops, three-wire to cancel lead resistance, four-wire for narrow spans and highest accuracy.

④ 15 bit + sign resolution
16-bit ADC with integrating measurement; finer than sensor tolerance, so accuracy is set by the RTD, not the module.

⑤ 85 dB rejection, 120 dB CMRR
Rejection at 50 / 60 / 400 Hz and ≥120 dB common-mode rejection for ovens, drives and 400 Hz plant.

⑥ Wire-break diagnostics
Wire break and supply monitoring with diagnostic alarms, per-channel status LEDs and a maintenance LED.

General

Product type designation

SM 1231, AI 4×16 bit RTD

System / platform

SIMATIC S7-1200 (expansion to the right of the CPU)

Number of analog inputs

4; resistance thermometer and resistance

Dimensions (W × H × D)

45 × 100 × 75 mm (one slot width)

Weight

approx. 220 g

Mounting / degree of protection

35 mm DIN rail, snapped to the right of the CPU / IP20

Power supply

Rated supply voltage

24 V DC

Current consumption at 24 V (typ.)

40 mA

Current from backplane bus 5 V (typ.)

80 mA

Power loss (typ.)

1.5 W

Analog inputs — sensors and ranges

Input type

RTD / resistance only (no voltage, no current, no thermocouple)

Platinum sensors

Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000

Nickel sensors

Ni100, Ni120, Ni200, Ni500, Ni1000, LG-Ni1000

Copper sensors

Cu10, Cu50, Cu100

Resistance ranges

0–150 Ω, 0–300 Ω, 0–600 Ω

Connection method

2-, 3- or 4-wire per channel

Temperature unit

°C or °F, selectable

Permissible input voltage (destruction limit)

±35 V

Resolution, accuracy and EMC

Resolution incl. sign (max.)

15 bit + sign (16-bit ADC)

Measurement principle

Integrating

Integration time

Not separately parameterizable; set by the selected rejection frequency

Series-mode rejection (f1 = 50 / 60 / 400 Hz)

85 dB

Common-mode rejection (f = n × f1 ± 1 %)

≥ 120 dB

Basic error at 25 °C

±0.1 % of input range

Temperature error

±0.2 % over total measuring range up to 55 °C

Repeat accuracy in steady state at 25 °C

±0.05 %

Diagnostics and status

Diagnostics function / diagnostic alarm

Yes, readable out / yes

Monitored

Wire break, supply voltage

LED indication

Status LED per channel, maintenance LED

Environment and approvals

Ambient temperature (horizontal / vertical)

−20 to +60 °C / −20 to +50 °C

Storage and transport temperature

−40 to +70 °C

Relative humidity

≤ 95 % at 25 °C, no condensation

Approvals

CE, UL, cULus, CSA, FM, RCM, KC, EAC, ATEX / IECEx, marine (DNV / LR / RMRS / CCS / KR)

Q1. Pt100 or Pt1000 — which should I specify?

Both are supported. Pt1000 has ten times the resistance of Pt100, so the lead resistance matters ten times less: on a two-wire run of 10 m, the error drops from roughly 1 °C with Pt100 to about 0.1 °C with Pt1000. Pt1000 is therefore the better choice for long cable runs, small machines with thin wiring, and three-wire connections that are not perfectly balanced. Pt100 remains common in process plant and is preferred where fast response is needed, because its sensing element can be made smaller. With four-wire connection the difference largely disappears.

Q2. Which wiring method should I use — 2, 3 or 4 wire?

Two-wire: simplest and cheapest, but the lead resistance adds directly to the measured value (about 0.4 Ω per 10 m of 0.5 mm² copper, roughly 1 °C on a Pt100) — acceptable only for short runs and loose accuracy. Three-wire: the standard for machinery; it compensates lead resistance provided the three leads are identical. Four-wire: the lead resistance is eliminated entirely; use it for narrow spans, high accuracy or long cables. All three are set per channel in the device configuration.

Q3. Can it also read 4–20 mA transmitters or 0–10 V signals?

No. Voltage, current and thermocouple inputs are all listed as "No" for this module — it measures resistance only. For 4–20 mA or ±10 V use the 6ES7231-4HF32-0XB0 (8× universal analog input); for thermocouples use 6ES7231-5QF32-0XB0 (8× TC). Ordering the wrong one of these three is the most common mistake in S7-1200 temperature applications.

Q4. What temperature range can it measure?

The range is set by the sensor, not by the module: a Pt100 to IEC 60751 covers −200 to +850 °C, a Pt1000 −200 to +600 °C, Ni1000 −60 to +250 °C, and Cu sensors roughly −50 to +150 °C. Configure the range to the span you actually use, not to the sensor's full range — accuracy is specified relative to the configured input range, so a narrow span gives a proportionally smaller absolute error.

Q5. What does ±0.1 % accuracy mean in degrees?

It is ±0.1 % of the configured input range. On the full Pt100 span of −200 to +850 °C (1050 K) that is about ±1 °C; if you configure −20 to +120 °C (140 K), the same specification corresponds to about ±0.14 °C. Add the sensor tolerance — a class B Pt100 is roughly ±0.3 °C at 0 °C — and the sensor, not the module, dominates the total error. The ±0.05 % repeat accuracy is what matters for control stability, because it describes the scatter of repeated readings at a constant temperature.

Q6. Can the four channels use different sensor types?

No. The sensor type is a module-level setting, selected with the DIP switches on the module and mirrored in the device configuration, so all four channels use the same RTD type and the same wiring method. If a machine needs Pt100 on two zones and Ni1000 on the other two, use two modules or standardise on one sensor type across the machine.

Q7. Do I need a front connector or shielding accessories?

The terminal block is supplied with the module — S7-1200 SM modules are wired directly at the front, unlike S7-300 / S7-400 where a front connector must be ordered separately. For the sensor cable, use shielded twisted-pair and ground the shield at one end; where the cable passes close to drives, route it separately from power cables. Long two-wire runs should be converted to three- or four-wire rather than compensated in the program.

Q8. Is it still available, and is there a successor?

Yes, it can still be ordered. Siemens lists it as an active product (PM300), with product phase-out announced for 1 November 2026 as part of the S7-1200 first generation. New units remain orderable until 31 October 2027, after which the module is available as a spare part for a further nine years (planned to around 2036). For new projects Siemens recommends the S7-1200 G2 platform; for existing machines, secure stock before the new-unit window closes and keep a complete backup of the TIA Portal project and firmware version.