6ES7421-1BL01-0AA0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
32 points in one slot — maximum rack efficiency. Slot capacity in an S7-400 rack, especially the central rack, is a scarce resource. The SM 421 1BL01 packs 32 input channels into a width of just 25 mm (290 mm high × 210 mm deep). The same point count with 16-channel 1BH01 modules would occupy two slots; the slot saved can be used for a CP communications processor or an FM function module. All 32 channels can be active simultaneously across the full 0–60 °C range, with no temperature-related derating.
Reliable signal acquisition, maintenance-free by design. The input side is optically isolated from the backplane bus (insulation test voltage 500 V DC), keeping field surges and earth-loop currents away from the backplane. The 1.2–4.8 ms input delay filters contact bounce while maintaining adequate response speed, so no external filter circuitry is required. Signal thresholds follow IEC 61131-2 Type 1 ("1" = 13–30 V DC, "0" = −30 to +5 V DC) and 2-wire proximity switches are supported with a maximum quiescent current of 1.5 mA. Every channel has its own green status LED for fast on-site troubleshooting, and shielded cables can run up to 1000 m for plant-wide signal collection.
Plug-in system architecture. The module communicates with the CPU over the S7-400 backplane bus and draws a maximum of only 20 mA at 5 V, placing virtually no load on the rack power supply. Configuration is done in STEP 7; with default characteristics the module works without manual parameter setting. As a standard (non-diagnostic) module it concentrates on one job — reliably feeding large numbers of ordinary binary signals into the controller — which makes it one of the most cost-effective I/O choices on the S7-400 platform. The front connector is ordered separately to match the rack; because it is removable, modules can be swapped as a whole without rewiring.
① 32 points in a single slot
32 channels in 25 mm — the highest channel density in the S7-400 DI range, saving scarce rack slots.
② IEC 61131-2 Type 1 inputs
"1" = 13–30 V DC, "0" = −30 to +5 V DC, compatible with all common 24 V DC sensors and contacts.
③ Optical isolation
Channel-to-backplane isolation (500 V DC test voltage) protects the bus from field surges and earth-loop currents.
④ Bounce-suppressing input filter
1.2–4.8 ms input delay suppresses mechanical contact bounce while keeping response fast.
⑤ Long cable runs
Up to 1000 m shielded and 600 m unshielded, suited to large plant areas and remote signal sources.
⑥ Minimal system load
Only 20 mA max. at 5 V from the backplane, 6 W typical power loss, and a green LED per channel.
General | |
Product type | SIMATIC S7-400 SM 421 digital input module |
Platform | SIMATIC S7-400 (UR racks) |
Dimensions (W × H × D) | 25 × 290 × 210 mm |
Weight | approx. 0.77 kg |
Slots occupied | 1 |
Country of origin / EAN | Germany / 4019169021463 |
Digital inputs | |
Number of inputs | 32 DI, 24 V DC, isolated |
Simultaneously controllable inputs | 32 (0–60 °C, all mounting positions) |
Input characteristic | IEC 61131-2 Type 1 |
Signal "1" voltage range | 13 – 30 V DC |
Signal "0" voltage range | −30 – +5 V DC |
Input current, "1" (typical) | 7 mA |
Input current, "0" (max. quiescent) | 1.3 mA |
2-wire sensors | Supported (max. quiescent current 1.5 mA, e.g. 2-wire BERO) |
Input delay (0→1 / 1→0) | 1.2 – 4.8 ms (standard inputs) |
Isolation | |
Between channels and backplane bus | Yes (optical isolation) |
Between channels | No (one group of 32, common ground within the group) |
Insulation test voltage | 500 V DC (type test) |
Power supply and losses | |
Current from backplane bus (5 V DC) | 20 mA max. |
Power loss | 6 W typical |
Diagnostics and display | |
Diagnostics | None (standard version; no diagnostic or hardware interrupt) |
Status display | 1 green LED per channel (input status) |
Connection | |
Front connector | Not included — order separately (20-pin, e.g. 6ES7492-1AL00-0AA0) |
Cable length (shielded / unshielded) | 1000 m max. / 600 m max. |
Ambient conditions | |
Ambient temperature, operation | 0 – 60 °C |
Ambient temperature, storage/transport | −40 – +85 °C |
Degree of protection | IP20 |
Engineering and lifecycle | |
Engineering software | STEP 7 |
Product lifecycle | PM300: Active; current version 1BL01 (earlier version 1BL00) |
Q1: Is a front connector included in the scope of supply?
No. The SM 421 front connector must be ordered separately (20-pin, e.g. 6ES7492-1AL00-0AA0, screw-type). It is removable, so a module can be replaced as a whole without undoing the wiring.
Q2: Are the channels isolated from one another?
No. All 32 channels form one isolation group with a common ground; only the channel-to-backplane bus path is optically isolated (500 V DC test voltage). Field signals should therefore share a common 24 V reference. If signals at different ground potentials must be isolated from each other, choose a module with grouped isolation.
Q3: Does it support diagnostics or hardware interrupts?
No. The 1BL01 is a standard, cost-optimised module: it provides only the per-channel green status LED, with no diagnostic interrupt, no hardware interrupt and no substitute-value configuration. For wire-break/short-circuit diagnostics or millisecond event capture, select a high-feature SM 421 with diagnostics (e.g. 16-channel 6ES7421-7BL01-0AA0 / 7BH01 versions).
Q4: Which signals and sensors can be connected?
24 V DC binary signals: pushbuttons, selector switches, limit switches, relay and contactor auxiliary contacts, and 2-wire proximity switches (BERO, max. 1.5 mA quiescent current). The module senses DC signals only — for AC inputs choose the corresponding AC version. It fits S7-400 racks only and cannot be used directly on S7-300 or S7-1500 platforms.
Q5: How does it differ from the earlier 1BL00 version?
The 1BL01 is the current version of the 1BL00. Functions and ratings are essentially identical; the MLFB (order number) differs. Always order by the complete article number, and verify system-configuration compatibility when using either version as a spare part.
Q6: Can all 32 channels be used at the same time without overloading the module?
Yes. The official data permits all 32 inputs to be active simultaneously at any mounting position across the full 0–60 °C range, with no temperature or position derating. Typical power loss is 6 W and backplane current draw is only 20 mA max., so the impact on rack power and the bus is negligible.
Q7: With a 1.2–4.8 ms input delay, is it suitable for high-speed counting or emergency stop?
The standard delay is fine for ordinary binary acquisition and for reliably reading emergency-stop pushbuttons and limit-switch protection (the delay already includes contact-bounce filtering). However, the module provides no hardware interrupt, so it is not suited to high-speed event capture or precise timing. Use an interrupt-capable module or a high-speed counter function module (FM) for those tasks.
Q8: Is it still available, and what happens when S7-400 is phased out?
The module currently carries lifecycle status PM300: Active and is supplied normally. As good practice, stock this module as a critical spare for existing S7-400 systems. For new projects or large retrofits, evaluate the S7-1500 platform with ET 200MP / ET 200SP I/O, which offers higher density and better diagnostics, and for which Siemens provides a migration path under TIA Portal.