6ES7516-3AN01-0AB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
6ES7516-3AN01-0AB0 is the CPU 1516-3 PN/DP of the SIMATIC S7-1500 family, hardware functional status FS03, firmware upgradable to V2.9. It targets applications with large program scope, complex network structures and high demands on processing speed and determinism: 1 MB of program work memory and 5 MB of data work memory, 10 ns bit-instruction execution, and PROFINET IRT synchronization supporting isochronous mode (minimum OB 6x cycle of 375 μs distributed, 1 ms central) for high-speed coordinated control.
Communication is the defining strength of this CPU. Interface 1 is a PROFINET IO IRT port with an integrated 2-port switch (RJ45) for line topologies and deterministic real-time communication, operating as IO controller, Shared Device or I-Device. Interface 2 is a PROFINET RT port with its own IP address, ideal for network separation — keeping engineering or IT traffic apart from the real-time control network. Interface 3 is a PROFIBUS DP master port that takes over installed DP slaves and legacy drives. All three run simultaneously without any additional CP module.
The front panel carries a 6.1 cm display and six keys, allowing IP address, firmware version and diagnostics to be read on site without a programming device. Security Integrated provides know-how protection, block copy protection (blocks can be bound to the serial number of the SIMATIC Memory Card) and Global Security-based access protection. The SIMATIC Memory Card (max. 32 GB) is the mandatory load memory; programs, recipes and archives are all managed on the card, so a spare CPU is restored simply by inserting the configured card. Combined with PLCopen-standard motion control (up to 30 axes) and the PID Compact closed-loop controller, it serves as the main controller for mid-to-large lines, packaging and assembly machines, and process control units.
Bit 10 ns, floating-point 64 ns; isochronous mode in distributed/central operation (min. 375 μs / 1 ms) and cyclic-interrupt OBs down to 250 μs for high-speed synchronization and precise cycle control.
PROFINET IRT (2-port switch) + PROFINET RT with separate IP + PROFIBUS DP master, all live simultaneously: real-time, management and legacy DP networks each get their own port — no extra communication modules.
Program and data memory are allocated separately; DBs up to 5 MB, 8000 blocks in total. Load memory comes from the SIMATIC Memory Card (max. 32 GB) with room for recipes and archives.
PLCopen-standard motion control blocks for up to 30 speed/positioning axes, external encoders and cams; drives integrate directly via PROFINET or PROFIBUS — no dedicated technology CPU needed.
The 6.1 cm display and six keys expose IP, firmware and diagnostics locally; know-how protection, copy protection and Global Security guard the program against unauthorized reading, modification and reproduction.
Drives and HMI are configured and diagnosed in the same engineering environment; trace functions cover all CPU tags, and configuration control via data record is supported.
Parameter | Specification |
|---|---|
General | |
Order number | 6ES7516-3AN01-0AB0 |
Product family / CPU type | SIMATIC S7-1500, CPU 1516-3 PN/DP |
Hardware status / firmware | FS03 / firmware V2.9 (highest for this hardware) |
Engineering software | TIA Portal V17 (FW V2.9); or V13 SP1 Update 4 (FW V1.8) or higher |
Display / operator controls | 6.1 cm display; 6 keys + 1 mode selector switch |
Memory | |
Work memory | 1 MB for program, 5 MB for data (integrated, not expandable) |
Load memory | Plug-in SIMATIC Memory Card (mandatory), max. 32 GB |
Retentive memory | Max. 512 KB (incl. timers, counters, bit memories) |
Backup | Maintenance-free |
Performance | |
Execution time | Bit 10 ns | word 12 ns | fixed-point 16 ns | floating-point 64 ns |
Blocks / block size | 8000 blocks in total (OB / FB / FC / DB) plus UDTs; DB up to 5 MB, FB / FC / OB up to 1 MB each |
Nesting depth | 24 levels per priority class |
S7 counters / timers | 2048 each (retentivity configurable); IEC counters / timers limited only by memory |
Bit memories / I/O address area | 16 KB bit memories; 32 KB input / 32 KB output address area (fully in the process image) |
Isochronous mode | Distributed min. OB 6x cycle 375 μs; central 1 ms |
Cyclic interrupt OBs | 20, minimum OB 3x cycle 250 μs |
Communication | |
1st interface | PROFINET IO IRT with 2-port switch (RJ45); IO controller / Shared Device / I-Device |
2nd interface | PROFINET RT (separate IP address), for network separation |
3rd interface | PROFIBUS DP master |
Protocols | PROFINET IO (RT / IRT), TCP/IP, UDP, SNMP, web server; PtP and other protocols via CM modules |
Motion control | Up to 30 axes (speed / positioning, PLCopen standard blocks) |
Electrical | |
Supply voltage | 24 V DC rated (permissible 19.2 – 28.8 V), reverse polarity protection |
Current consumption | 0.85 A rated, inrush max. 2.4 A (I²t 0.02 A²·s) |
Backplane bus | Infeed 12 W, self-consumption (balanced) 6.7 W |
Power loss | Typ. 7 W |
Power failure buffering | 5 ms, repetition rate ≥ 1/s |
Mechanical & environmental | |
Net weight | Approx. 0.9 kg |
Ambient temperature | Horizontal mounting 0 – 60 °C; vertical mounting 0 – 40 °C |
Origin / EAN | Germany | 4047623404958 |
1Is a SIMATIC Memory Card mandatory?
Yes — the CPU will not run without a memory card. The load memory is provided entirely by the plug-in SIMATIC Memory Card (max. 32 GB), which holds the user program, hardware configuration, recipes and archives. When replacing a CPU, simply insert the configured card into the new unit to restore operation.
2How are the three interfaces used?
Interface 1 (PROFINET IO IRT with 2-port switch) is the real-time control port for IO devices, drives and line topologies. Interface 2 (PROFINET RT) has a separate IP address and is typically used for network separation — isolating the engineering/IT segment from the real-time network — or to serve a second group of IO devices. Interface 3 (PROFIBUS DP) connects installed DP slaves and legacy drives. All three work simultaneously, with no additional CP modules required.
3What is the difference between AN00, AN01 and AP03?
AN00 is the original hardware version. AN01 (this article) is the upgraded hardware (FS03) whose firmware is maintained up to V2.9, giving it the longest firmware support among the two. AP03 (6ES7516-3AP03-0AB0) is the Siemens-designated successor with forward-compatible functionality — new projects should go straight to AP03. When replacing an AN01, confirm the TIA Portal version (FW V2.9 requires V17) and verify the hardware configuration.
4How capable is the motion control?
The CPU integrates PLCopen-standard motion control for up to 30 axes (speed and positioning axes), including external encoders, cams and cam tracks; drives are integrated and diagnosed directly in TIA Portal via PROFINET or PROFIBUS. For advanced functions such as absolute synchronous axes and cam synchronization, choose the S7-1500T technology CPU family.
5Can S7-300/400 programs be migrated?
Yes, via the TIA Portal migration path: S7-300/400 projects are imported and converted to S7-1500 projects, but certain system functions, addressing methods and absolutely-addressed DBs need adjustment (DBs with absolute addressing are limited to 64 KB on this CPU). Assess program scope and system blocks before migrating; 1 MB of program memory is ample for most mid-sized migration projects.
6What should be considered for power supply and consumption?
The CPU is powered via the backplane bus from a system power supply (PS); it has no direct 24 V terminal connection. Rated current is 0.85 A with a typical power loss of 7 W. Size the system power supply for the 12 W backplane infeed and ensure uninterrupted power for the 5 ms buffering window (repetition rate ≥ 1/s).
7Are there mounting orientation or temperature limits?
Horizontal mounting allows an ambient temperature of 0 – 60 °C, while vertical mounting is derated to 0 – 40 °C. Provide ventilation channels inside the cabinet and arrange multi-module racks according to the S7-1500 rail thermal requirements.
8What is the lifecycle status?
This article's phase-out was announced on 2 June 2020 and cancelled the same day (delivery release 7 August 2015); it now circulates as a spare part. The Siemens-designated successor is 6ES7516-3AP03-0AB0 (newer hardware revision with a longer firmware roadmap). When sourcing spares, verify the production batch and firmware version, and plan the transition to AP03 or the latest hardware.