6ES7215-1AG40-0XB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
One module, one machine. The CPU 1215C packs supply, CPU, onboard I/O and network interfaces into a 130 × 100 × 75 mm housing that clips onto a standard 35 mm DIN rail — minimal footprint, minimal wiring. Fourteen digital inputs and ten digital outputs cover the discrete signals of most standalone machines; two analog inputs take pressure, temperature or level transmitters and two analog outputs feed a drive or a control valve directly. What used to need two expansion modules now comes with the CPU, cutting hardware cost and potential failure points. A 1600 mA backplane supply leaves headroom for up to eight signal modules.
Two-port PROFINET, more freedom in wiring. Both RJ45 ports share one isolated PROFINET interface and one IP subnet through an integrated switch: several devices can be chained in a line topology without an external switch, or one port can serve the PLC/HMI level while the other serves field I/O. As an IO controller the CPU handles up to 16 PROFINET IO devices and can also act as an IO device, embedding the machine as an intelligent slave in a larger system. Firmware V4.7 provides an OPC UA server and a web server, so production data reaches MES, SCADA or cloud platforms without an extra gateway.
Technology functions built in. Six of the 14 inputs work as high-speed counters — three at 100 kHz and three at 30 kHz single-phase, or three at 80 kHz and three at 30 kHz differential — capturing encoder, flow-meter and length signals directly. Four of the ten outputs support PTO/PWM up to 100 kHz for stepper or pulse-type servo positioning, with up to 8 positioning axes via PLCopen motion control instructions. PID autotuning, a real-time clock (480 h battery-free backup), four alarm inputs plus trace and diagnostic buffers cover process control and fault analysis without additional hardware.
① Digital and analog in one unit
14 DI + 10 DO (transistor, 0.5 A) + 2 AI (0–10 V) + 2 AO (0–20 mA) — closed-loop control without an analog expansion module.
② Two-port PROFINET switch
2 × RJ45 with integrated switch for line and daisy-chain topologies, saving an external switch and cabinet wiring.
③ 200 KB work memory
200 KB work memory, 4 MB load memory and 14 KB retentive area at firmware V4.7 — room for complex logic and recipes.
④ High-speed counting and positioning
6 HSC channels up to 100 kHz, 4 PTO/PWM outputs at 100 kHz, up to 8 positioning axes for stepper or pulse servo drives.
⑤ OPC UA and web server
Firmware V4.7 includes an OPC UA server and user-defined web pages — cloud connectivity and remote diagnostics without a gateway.
⑥ Maintenance-free and expandable
Battery-free retention with 480 h clock backup; up to 8 SM + 1 SB + 3 CM with 1600 mA backplane supply.
General | |
Product type | CPU 1215C DC/DC/DC |
Firmware version | V4.7 |
Engineering software | STEP 7 / TIA Portal V20 or higher |
Dimensions (W × H × D) | 130 × 100 × 75 mm |
Net weight | approx. 500 g |
Mounting / degree of protection | 35 mm DIN rail or panel / IP20 |
Country of origin | Germany |
Power supply | |
Rated supply voltage | 24 V DC (20.4 – 28.8 V), reverse-polarity protected |
Current consumption | 500 mA (CPU only); max. 1500 mA with all expansion modules |
Inrush current | max. 12 A at 28.8 V, I²t = 0.5 A²·s |
Backplane supply (5 V DC) | max. 1600 mA for SM / CM |
24 V encoder supply | L+ minus 4 V DC (min.) |
Power loss | 12 W typ. |
Memory and performance | |
Work memory | 200 KB integrated, not expandable |
Load memory | 4 MB integrated; expandable with SIMATIC Memory Card |
Retentive data area | max. 14 KB (timers, counters, flags) |
Bit / word / floating-point | 0.08 µs | 1.7 µs | 2.3 µs |
Process image | 1 KB inputs / 1 KB outputs, adjustable |
Data backup | Maintenance-free, battery-free |
Onboard digital I/O | |
Digital inputs | 14 × 24 V DC, sink/source selectable; 6 usable as HSC |
Input threshold / delay | "0" ≤5 V (1 mA); "1" ≥15 V (2.5 mA); delay 0.2 – 12.8 ms configurable in groups of four |
Digital outputs | 10 × 24 V DC transistor (sourcing), 0.5 A per point; 4 usable as high-speed outputs |
Output load | 0.5 A resistive; lamp load max. 5 W; inductive shutdown limited to L+ (−48 V) |
Output delay | "0"→"1" ≤1 µs, "1"→"0" ≤5 µs (resistive load) |
Cable length (DI / DO) | Inputs 500 m shielded / 300 m unshielded; outputs 500 m shielded / 150 m unshielded |
Onboard analog I/O | |
Analog inputs | 2 × 0 – 10 V DC, 10-bit resolution, input resistance ≥100 kΩ, conversion time 625 µs per channel |
Analog outputs | 2 × 0 – 20 mA DC, 10-bit resolution |
Analog cable length | max. 100 m, twisted and shielded |
Technology functions | |
High-speed counters | 6 total: 3 × 100 kHz + 3 × 30 kHz single-phase; 3 × 80 kHz + 3 × 30 kHz differential |
Pulse outputs (PTO/PWM) | 4, up to 100 kHz |
Positioning axes | up to 8 (PLCopen motion control) |
Closed loop / alarms | PID autotuning (up to 16 loops); 4 alarm inputs; trace and diagnostic buffer |
Communication | |
PROFINET interface | 1 interface / 2 × RJ45 ports, integrated switch, 100 Mbit/s |
Roles and capacity | IO controller / IO device; up to 16 IO devices (8 of them activatable/deactivatable at runtime) |
Protocols | PROFINET IO, TCP/IP, ISO-on-TCP, UDP, MODBUS TCP, SNMP, OPC UA (V4.7) |
Web server | Yes, user-defined pages supported |
Expansion | |
Signal modules (SM) | up to 8 |
Signal / communication board | up to 1 (SB, CB, BB combined) |
Communication modules (CM) | up to 3 (e.g. CM 1241 RS-232/485, CM 1243-5 PROFIBUS DP master) |
Clock and environment | |
Real-time clock | Yes; 480 h typical backup; deviation ≤±60 s/month at 25 °C |
Ambient temperature | −20 to +60 °C horizontal; −20 to +50 °C vertical |
Derating at high temperature | Above 55 °C (horizontal) / 45 °C (vertical), simultaneously active channels drop to 14 / 10; at 60 °C / 50 °C to 7 / 5 |
Storage temperature / humidity | −40 to +70 °C / ≤95% non-condensing |
Approvals | CE, UL, cULus, FM Class I Div. 2, KC, RCM, marine approvals |
Q1: Is the work memory 125 KB or 200 KB?
It depends on the firmware. This order number 6ES7215-1AG40-0XB0 currently ships with firmware V4.7 and 200 KB of work memory; earlier firmware releases (V4.4 / V4.5 and before) of the same article number had 125 KB. Many online listings still quote the old figure — always check the firmware actually installed (readable online in TIA Portal) before quoting or sizing a program.
Q2: How does the 1215C differ from the 1214C?
Discrete I/O is identical (14 DI / 10 DO / 2 AI). The differences are: (1) analog outputs — the 1215C adds 2 × 0–20 mA, the 1214C has none; (2) ports — 2 × RJ45 with integrated switch versus a single port; (3) memory — 200 KB versus 150 KB; (4) width — 130 mm versus 110 mm. Choose the 1215C when you need an analog output for a drive or proportional valve, or want a line topology without an external switch; for pure discrete standalone machines the 1214C is more economical.
Q3: Are the two ports two separate networks? Can they be used for network separation?
No. Both RJ45 ports belong to one isolated PROFINET interface on the same IP subnet — they are an integrated switch, intended for line and daisy-chain wiring, not for isolating two networks. If the office network and the machine network must be physically separated, use a CPU with genuinely independent interfaces (for example the S7-1500 CPU 1516-3 PN/DP, whose second PROFINET interface has its own IP address), or add an external router or firewall.
Q4: Can the analog outputs drive a VFD or a proportional valve directly?
Yes, with three caveats. The outputs are current type, 0–20 mA, 10-bit. For a 4–20 mA signal, scale it in TIA Portal against the engineering range (4 mA at the lower limit) rather than adding external offset hardware. If a 0–10 V signal is required, a shunt resistor in the loop converts current to voltage — but check the permissible load impedance, and keep analog cable runs within 100 m, twisted and shielded. Where accuracy beyond 10 bits (about 0.1%) is needed, use an SM 1232 analog module instead.
Q5: Is a SIMATIC Memory Card mandatory?
No. The CPU has 4 MB of integrated load memory and programs download and run without a card. The card is used for fast cloning of identical machines, firmware updates, recipes and data logging; fit one if you need to swap a CPU on site without a laptop or archive data.
Q6: Can it do motion control, and how many axes?
Yes. Four outputs provide PTO/PWM up to 100 kHz, supporting up to 8 positioning axes through PLCopen motion control instructions — suitable for stepper motors or pulse-type servo drives in point-to-point and speed control. With a PROFINET servo drive (e.g. SINAMICS V90 PN) the axes are configured as technology objects and the count depends on the TIA Portal configuration and drive capability. For interpolation, cam synchronization or kinematics, move up to the S7-1500T platform.
Q7: Can the transistor outputs switch 230 V AC loads?
No. The outputs are 24 V DC sourcing transistors and drive 24 V DC loads only; connecting a 230 V AC solenoid valve or contactor coil will destroy the output stage. Use an interposing relay for AC loads, or select the AC/DC/RLY variant (6ES7215-1BG40-0XB0). For inductive DC loads a freewheeling diode is mandatory — the switch-off transient will otherwise puncture the output transistor.
Q8: Is this model still available, and what is its lifecycle status?
Siemens lists it as PM300: Active Product, but has announced that product phase-out starts on 1 November 2026. For new projects with a long service life, evaluate migration to the new S7-1200 G2 platform now; for spares on existing machines, stock up early and keep a complete backup of the TIA Portal project, firmware version and configuration. Confirm the exact successor article number and changeover date with Siemens or your authorized distributor for your specific project.