6ES7214-1BG40-0XB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
AC supply, a simpler cabinet. The main value of AC/DC/RLY lies in the power architecture: 220 V mains feeds the CPU directly, removing the 24 V DC power supply module and eliminating a common single point of failure. The CPU provides a 24 V sensor supply output (20.4–28.8 V) for its own digital inputs and a few proximity switches; where many 24 V loads exist, an external supply is still recommended to keep headroom. Rated current draw is only 100 mA at 120 V AC (50 mA at 240 V AC), with 14 W typical power loss.
Relay outputs for both AC and DC loads. Each of the ten relay outputs is rated 2 A with a maximum switching voltage of 250 V AC / 30 V DC, so AC solenoids, contactors, interposing relays and lamps connect directly without additional relays — something a transistor version cannot do. Mechanical life is around 10 million operations, electrical life around 100,000 at rated load, which suits applications with moderate switching frequency. Note that the relay outputs have no short-circuit protection: external fuses or circuit breakers are mandatory, and an RC snubber or varistor is recommended for inductive loads to extend contact life.
Control capability identical to the standard version. Apart from supply and output type, the 1BG40 matches the 1AG40 (DC/DC/DC): 0.08 µs bit instructions, 150 KB work memory (firmware V4.6 and later), 4 MB load memory, 6 high-speed counters up to 100 kHz, an integrated PROFINET interface for up to 16 IO devices, OPC UA and web server, real-time clock and PID control. Up to 8 signal modules, 1 signal board and 3 communication modules can be added. The one functional trade-off: relay outputs cannot generate high-frequency pulses, so this variant is unsuitable for pulse-based positioning — choose the transistor version for motion control.
① Wide-range AC supply
85–264 V AC, 47–63 Hz: 220 V mains connects directly, no 24 V power supply module required.
② Ten relay outputs
2 A per point, max. 250 V AC / 30 V DC — drives AC solenoids and contactor coils directly.
③ 150 KB work memory
Firmware V4.6 and later provides 150 KB work memory and 4 MB load memory; SIMATIC Memory Card supported.
④ Six high-speed counters
3 × 100 kHz + 3 × 30 kHz single-phase for encoders and flow-meter pulses.
⑤ Integrated PROFINET
1 × RJ45 at 100 Mbit/s for up to 16 IO devices; OPC UA server and web server included.
⑥ Flexible expansion
Up to 8 SM + 1 SB + 3 CM, with 1600 mA available on the 5 V backplane.
General | |
Product type | CPU 1214C AC/DC/RLY |
Firmware version | V4.7 (current) |
Engineering software | STEP 7 / TIA Portal V20 or higher |
Dimensions (W × H × D) | 110 × 100 × 75 mm |
Weight / protection | approx. 415 g / IP20 |
Mounting | 35 mm DIN rail or panel mount |
Power supply | |
Rated supply voltage | AC 120 V / AC 230 V |
Permissible range | 85 – 264 V AC |
Line frequency | 47 – 63 Hz |
Current (rated / max.) | 100 mA / 300 mA at 120 V AC; 50 mA / 150 mA at 240 V AC |
Inrush current | 20 A max. at 264 V, I²t = 0.8 A²·s |
Backplane supply (5 V DC) | 1600 mA max. |
24 V sensor supply | 20.4 – 28.8 V DC |
Power loss | 14 W typical |
Memory and performance | |
Work memory | 150 KB integrated (not expandable) |
Load memory | 4 MB integrated; SIMATIC Memory Card supported |
Retentive data area | 14 KB max. (incl. timers, counters, flags) |
Bit / word / floating-point | 0.08 µs | 1.7 µs | 2.3 µs |
Process image | 1 KB inputs / 1 KB outputs (adjustable) |
Data backup | Maintenance-free, battery-free (EEPROM) |
Onboard I/O | |
Digital inputs | 14 × 24 V DC, sink/source selectable; 6 usable as HSC |
Input thresholds / delay | "0" ≤5 V (1 mA); "1" ≥15 V (2.5 mA); delay 0.2–12.8 ms configurable |
Digital outputs | 10 × relay, 2 A per point; max. switching 250 V AC / 30 V DC |
Contact life | Mechanical approx. 10 million; electrical approx. 100,000 at rated load |
Output protection | No short-circuit protection (external fuse/breaker required) |
Analog inputs | 2 × 0–10 V DC, 10-bit resolution |
High-speed counters | 6 channels: 3 × 100 kHz + 3 × 30 kHz single-phase; 3 × 80 kHz + 3 × 30 kHz differential |
Pulse outputs | Relay version does not support high-frequency PTO/PWM (choose transistor version for motion) |
Cable length (DI) | 500 m shielded / 300 m unshielded (≤50 m recommended for technology inputs) |
Communication | |
PROFINET interface | 1 × RJ45, 100 Mbit/s (single port, no integrated switch) |
Role and capacity | IO controller / IO device; up to 16 IO devices |
Protocols | TCP/IP, ISO-on-TCP, UDP, MODBUS TCP, SNMP, OPC UA |
Expansion and environment | |
Expansion | 8 SM + 1 SB + 3 CM |
Real-time clock | Yes; 480 h typical backup; ≤±60 s/month at 25 °C |
Operating temperature | −20 to +60 °C (horizontal); −20 to +50 °C (vertical) |
Approvals | CE, UL, cULus, FM Class I Div. 2, KC, RCM |
Q1: What is the essential difference from the 1AG40 (DC/DC/DC)?
The three 1214C variants differ in supply and output type: 1AG40 = 24 V DC supply with transistor outputs; 1HG40 = 24 V DC supply with relay outputs; 1BG40 (this model) = 85–264 V AC supply with relay outputs. CPU performance, memory, communication and expansion are identical. Choose the 1BG40 when only 220 V AC power is available on site, or when AC loads must be switched directly.
Q2: Can the relay outputs be used for pulse-based positioning?
No. Relay contacts cannot switch at high frequency, so this variant does not provide 100 kHz PTO/PWM pulse outputs and cannot drive stepper or servo positioning. For pulse positioning or high-speed pulse output, use the transistor version 1AG40 (4 × 100 kHz PTO, up to 8 positioning axes) or control a bus-based servo such as SINAMICS V90 PN over PROFINET.
Q3: Is the work memory 75 KB, 100 KB or 150 KB?
It depends on the firmware version: early units had 75 KB, later ones 100 KB, and firmware V4.6 and above provides 150 KB (current V4.7). All three figures appear online because the screenshots come from datasheets of different years. Read the actual firmware version online in TIA Portal before sizing the memory budget.
Q4: With AC supply, do the digital inputs still need 24 V?
Yes. Although the CPU is powered from 220 V AC, its 14 digital inputs remain 24 V DC. The module provides a 24 V sensor supply output (20.4–28.8 V) for its own inputs and a few sensors. Where many 24 V loads exist (solenoids, lamps, sensors drawing significant total current), add an external 24 V supply so the CPU's internal supply is not overloaded.
Q5: How much load can the relay contacts handle?
2 A per point with a maximum switching voltage of 250 V AC / 30 V DC — enough for AC solenoids, contactor coils, indicator lamps and small heaters. However, the outputs have no short-circuit protection, so external fuses or circuit breakers are mandatory; fit an RC snubber or varistor across inductive loads to suppress switch-off transients and extend contact life. For frequent switching (several times per second) use transistor outputs or external solid-state relays.
Q6: Can it be connected directly to 380 V?
No. The supply range is 85–264 V AC single-phase, matching 220/230 V mains. 380 V is a three-phase line voltage — use a transformer or take a single phase; never connect it directly.
Q7: Are the high-speed counters still usable?
Yes. High-speed counting sits on the input side and is independent of the output type: 3 of the 6 HSC channels reach 100 kHz single-phase, 3 reach 30 kHz, and in differential mode 3 reach 80 kHz. They serve encoder speed measurement, flow metering and counting/sorting — you simply cannot use those counts to drive high-speed pulse outputs for closed-loop positioning.
Q8: Is this model still suitable for new projects?
It suits small and medium standalone machines dominated by AC loads with no pulse-positioning requirement — especially retrofits and export machines that can use local 220/230 V power. If the machine involves servo positioning, high dynamic response or many analog channels, choose the transistor version 1AG40 or move up to the CPU 1215C / S7-1500 platform.