6ES7421-1EL00-0AA0

The SM 421 (6ES7421-1EL00-0AA0) is a 32-channel digital input module for the S7-400 platform, rated at 120 V with universal AC/DC input (AC 47–63 Hz or DC) and potential isolation. It is designed for 120 V binary signals — valve feedback, limit switches, pushbuttons and relay contacts — as found in imported machinery, overseas projects and older installations with 120 V control circuits.

The module isolates channels in groups of 8, so interference in one group cannot affect its neighbours. It mounts in a single 25 mm slot and offers a 5–25 ms input delay with built-in filtering.
  • 6ES7421-1EL00-0AA0

  • Siemens

Availability:
Quantity:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
sharethis sharing button

dedicated interface for 120 V circuits. In most domestic projects 24 V DC dominates, but 120 V AC control circuits remain common in imported equipment and overseas plants. Interposing relays on a 24 V module add cost, wiring and failure points while consuming cabinet space; the SM 421 1EL00 accepts 120 V AC/DC directly, covering 32 points with simple wiring and reliable response.

Group isolation keeps faults local. The 32 channels are split into four groups of 8 with isolation between groups, plus isolation between channels and the backplane bus (1500 V AC test voltage). Field surges and earth-potential differences stay confined to one group and cannot reach the backplane, making the module suitable for electrically noisy environments. Shielded cable runs up to 1000 m, unshielded up to 600 m.

Economical standard version. Input current is only 2 mA typical, backplane draw is 200 mA max. at 5 V, and power loss is 6.5 W typical. The module has no channel-level diagnostics, only a green LED per channel; configuration is done in STEP 7 and default characteristics work without extra settings. The front connector is ordered separately, and because it is removable the module can be swapped as a whole.

① 120 V AC/DC universal
AC 79–132 V and DC 80–132 V both read as "1" — one module for either circuit type.

② Isolation in groups of 8
32 channels in four isolated groups; a fault in one group does not affect the others.

③ 32 points in one slot
25 mm wide, one rack slot for 32 inputs, saving rack space.

④ Low input current
Only 2 mA typical at "1", a light load on the field circuit.

⑤ Long cable runs
Up to 1000 m shielded and 600 m unshielded.

⑥ Clear status indication
A green LED per channel for tool-free on-site troubleshooting.

General

Product type

SIMATIC S7-400 SM 421 digital input module

Dimensions (W × H × D)

25 × 290 × 210 mm, one slot

Weight / origin

approx. 0.77 kg / Germany

Inputs

Number of inputs

32 DI (all simultaneously controllable)

Rated input voltage

120 V UC (AC/DC, AC 47–63 Hz)

Signal "1"

AC 79–132 V; DC 80–132 V

Signal "0"

0–20 V UC

Input current

"1" 2 mA typical (2–5 mA); "0" 1 mA max.

Input delay (0→1)

5 – 25 ms

2-wire sensors

Supported, quiescent current 1 mA max.

Isolation and power

Channel-to-channel isolation

Yes, in groups of 8 (four groups)

Channel-to-backplane

Isolated, 1500 V AC test voltage

Backplane current (5 V DC)

200 mA max.

Power loss

6.5 W typical (16 W max.)

Connection, environment, software

Front connector

Not included — order separately (40-pin)

Cable length (shielded / unshielded)

1000 m / 600 m

Ambient temperature / protection

0 – 60 °C / IP20

Diagnostics / display

No channel diagnostics; green LED per channel

Engineering software

STEP 7

Lifecycle

PM300 active; phase-out announced by Siemens (effective 2025-10-01)

Q1: Can it accept both 120 V AC and 120 V DC?

Yes. The inputs are UC (universal AC/DC) rated: AC 79–132 V and DC 80–132 V both count as "1", with an AC frequency range of 47–63 Hz. Different channels on the same module can be fed from AC and DC signals respectively.

Q2: How do I choose between this and the common 1BL01 (24 V DC) version?

Choose by field circuit voltage: for 24 V DC use 6ES7421-1BL01-0AA0 (7 mA input current, 1.2–4.8 ms delay); for 120 V use this 1EL00. Both provide 32 points in a 25 mm slot, but the voltage ratings are not interchangeable — connecting 120 V to a 24 V module will destroy it.

Q3: Is the front connector included?

No. A 40-pin front connector must be ordered separately. It is removable, so the module can be replaced as a whole without rewiring.

Q4: Does the 5–25 ms input delay cause problems?

It is fully adequate for conventional binary signals such as valve feedback, limit switches, pushbuttons and relay contacts; the delay itself provides interference filtering that suppresses bounce and false triggering on AC circuits. It is not suitable for high-speed counting or precise timing — use an interrupt-capable module or an FM function module for those tasks.

Q5: Is this module still available?

Yes. It currently carries status PM300 (active) and is supplied normally, but Siemens has announced a phase-out effective 2025-10-01. We recommend stocking this module as a critical spare for existing 120 V systems; for new projects, evaluate a 24 V circuit with S7-1500 / ET 200SP instead.