The SIMATIC S7-1200 CPU 1214C (DC/DC/DC, order no. 6ES7214-1AG40-0XB0) is the most widely used mid-range compact controller in the S7-1200 family. A single unit integrates 14 digital inputs at 24 V DC, 10 transistor outputs at 24 V DC and 2 analog inputs at 0–10 V, plus one onboard PROFINET interface — enough to build a complete small control station without an additional power supply module or communication card.

The DC/DC/DC variant uses a 24 V DC supply with 24 V DC inputs and transistor outputs, making it a natural match for DC solenoid valves, indicator lamps and stepper or servo drives: fast response, no contact wear. The current version runs firmware V4.7 with 150 KB work memory and 4 MB load memory, engineered in TIA Portal (STEP 7 V20 or higher).
  • 6ES7214-1AG40-0XB0

  • Siemens

Availability:
Quantity:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
sharethis sharing button

Integrated compact design, a control core out of the box. The CPU 1214C packs power supply, CPU, onboard I/O and PROFINET interface into a 110 × 100 × 75 mm housing that snaps onto a standard 35 mm DIN rail, occupying minimal cabinet space. Fourteen digital inputs and ten digital outputs cover the control needs of most standalone machines, avoiding the cost and wiring of expansion modules for a handful of extra points; the two 0–10 V analog inputs accept pressure or temperature transmitters and potentiometers directly, with no analog module required. The 5 V backplane supply delivers up to 1600 mA, leaving ample headroom for expansion.

Technology functions for motion and high-speed signals. Six of the 14 digital inputs can be used as high-speed counters (HSC) — up to 100 kHz single-phase and 80 kHz differential — for direct connection of encoders and flow-meter pulses. Four of the ten outputs support PTO/PWM at up to 100 kHz, driving stepper or servo drives for positioning, with up to 8 positioning axes via PLCopen motion control instructions. An integrated PID controller, a real-time clock (480 h battery-free backup) and 4 alarm inputs cover process control and fault interlocking without extra hardware.

Native PROFINET and digital-ready. The onboard RJ45 port provides 100 Mbit/s industrial Ethernet and supports both PROFINET IO controller and IO device roles, connecting up to 16 IO devices; the same port also handles programming, HMI access and the web server. Firmware V4.7 adds an OPC UA server, giving production data a standard route to MES/SCADA systems or the cloud. Communication modules such as CM 1241 and CM 1243-5 add RS-232/485 and PROFIBUS DP where legacy fieldbuses are required.

① Onboard I/O, ready to run
14 DI + 10 DO (transistor, 0.5 A) + 2 AI (0–10 V, 10-bit) — no expansion needed for small machines.

② High-speed counting and pulse output
6 HSC channels up to 100 kHz and 4 PTO/PWM outputs at 100 kHz, supporting up to 8 positioning axes.

③ 150 KB work memory
Firmware V4.7 provides 150 KB work memory and 4 MB load memory — ample capacity for complex logic.

④ Integrated PROFINET
1 × RJ45 at 100 Mbit/s, IO controller and device roles, up to 16 IO devices, also serving programming and HMI.

⑤ OPC UA server and web server
Firmware V4.7 supports OPC UA and user-defined web pages for cloud connectivity and remote diagnostics.

⑥ Flexible expansion, maintenance-free
Up to 8 SM + 1 SB + 3 CM; battery-free retention with a 480 h real-time clock backup.

General

Product type

CPU 1214C DC/DC/DC

Firmware version

V4.7

Engineering software

STEP 7 / TIA Portal V20 or higher

Dimensions (W × H × D)

110 × 100 × 75 mm

Weight

approx. 415 g

Mounting / protection

35 mm DIN rail or panel mount / IP20

Power supply

Rated supply voltage

24 V DC (20.4 – 28.8 V), reverse-polarity protected

Current consumption

500 mA (CPU only); 1500 mA max. with all expansion modules

Inrush current

12 A max. at 28.8 V, I²t = 0.5 A²·s

Backplane supply (5 V DC)

1600 mA max. for SM / CM

24 V encoder supply

L+ minus 4 V DC (min.)

Power loss

12 W typical

Memory and performance

Work memory

150 KB integrated (not expandable)

Load memory

4 MB integrated; expandable with SIMATIC Memory Card

Retentive data area

14 KB max. (incl. timers, counters, flags)

Bit / word / floating-point

0.08 µs | 1.7 µs | 2.3 µs

Process image

1 KB inputs / 1 KB outputs (adjustable)

Data backup

Maintenance-free, battery-free (EEPROM)

Onboard I/O

Digital inputs

14 × 24 V DC, sink/source selectable; 6 usable as HSC

Input thresholds / delay

"0" ≤5 V (1 mA); "1" ≥15 V (2.5 mA); delay 0.1–20 ms configurable

Digital outputs

10 × 24 V DC transistor (sourcing), 0.5 A per point, short-circuit protected; 4 high-speed

Analog inputs

2 × 0–10 V DC, 10-bit resolution, approx. 625 µs conversion per channel

High-speed counters

6 channels: 3 × 100 kHz + 3 × 30 kHz single-phase; 3 × 80 kHz + 3 × 30 kHz differential

Pulse outputs (PTO/PWM)

4 channels, up to 100 kHz

Positioning axes

Up to 8 (PLCopen motion control)

Cable length (DI / DO)

Inputs 500 m shielded / 300 m unshielded; outputs 500 m shielded / 150 m unshielded

Communication

PROFINET interface

1 × RJ45, 100 Mbit/s, autonegotiation/autocrossing (single port, no integrated switch)

Role and capacity

IO controller / IO device; up to 16 IO devices

Protocols

TCP/IP, ISO-on-TCP, UDP, MODBUS TCP, SNMP, OPC UA (V4.7)

Connection resources

34 reserved / 68 max. total (PG, HMI, S7, open user, web)

Web server

Yes, with user-defined pages

Expansion

Signal modules (SM)

Up to 8

Signal board / comm. board

1 in total (SB, CB, BB)

Communication modules (CM)

Up to 3 (e.g. CM 1241 RS-232/485, CM 1243-5 PROFIBUS DP master)

Clock and environment

Real-time clock

Yes; 480 h typical backup; deviation ≤±60 s/month at 25 °C

Operating temperature

−20 to +60 °C (horizontal); −20 to +50 °C (vertical)

Storage temperature / humidity

−40 to +70 °C / ≤95%, non-condensing

Approvals

CE, UL, cULus, FM Class I Div. 2, KC, RCM, marine approvals

Q1: Is the work memory 100 KB or 150 KB?

It depends on the firmware version. This order number 6ES7214-1AG40-0XB0 currently ships with firmware V4.7 and 150 KB work memory; units with earlier firmware (early V4.0–V4.x) had 100 KB. Many online sources still quote the older 100 KB figure — always confirm against the firmware version read online in TIA Portal when preparing a quotation or design.

Q2: Is a SIMATIC Memory Card mandatory?

No. The CPU has 4 MB of integrated load memory, so programs can be downloaded and run directly. The SIMATIC Memory Card is used mainly for cloning complete programs across batch machines, firmware updates, recipes and data logging. It is recommended if CPUs must be replaced on site without a PC, or if data archiving is required.

Q3: How does DC/DC/DC differ from other variants — can it drive AC loads?

The CPU 1214C comes in three variants: DC/DC/DC (this model — 24 V supply with transistor outputs), DC/DC/RLY (transistor pre-stage with relay outputs) and AC/DC/RLY (AC supply with relay outputs). The outputs here are sourcing transistors and can only switch 24 V DC loads; they cannot be connected directly to 220 V AC solenoid valves or contactor coils. For AC loads, add interposing relays or choose an RLY variant.

Q4: Is the PROFINET port a two-port switch?

No. The CPU 1214C has a single RJ45 port with no integrated switch (two-port models are the CPU 1215C, CPU 1516, etc.). Use an industrial switch for line topology or when several local devices must connect; with the single port, up to 16 PROFINET IO devices can be operated.

Q5: What can the high-speed counting and pulse outputs handle?

Of the 6 HSC channels, 3 reach 100 kHz single-phase — suitable for encoder speed measurement, flow metering and high-speed sorting. The 4 PTO outputs run up to 100 kHz and, with PLCopen instructions, support up to 8 positioning axes for stepper motors or servos with a pulse interface. For bus-based servos (e.g. SINAMICS V90 PN), control them as technology objects over PROFINET instead.

Q6: How much I/O expansion is possible?

Up to 8 signal modules (SM) + 1 signal board (SB) + 3 communication modules (CM) locally. When configuring, verify that total 5 V backplane current stays within 1600 mA and check the configuration in TIA Portal; if more points are needed, add ET 200SP distributed I/O over PROFINET.

Q7: What should be considered when switching inductive loads with transistor outputs?

Always fit a freewheeling diode (or an RC snubber across the load) for inductive DC loads such as solenoid valves and relay coils; otherwise the reverse EMF at switch-off can destroy the output transistor. Observe the 0.5 A per-point rating and the group current limits — for higher currents use an interposing relay or solid-state relay.

Q8: How do I choose between the 1214C and 1215C?

The 1215C adds 2 analog outputs (0–10 V / 0–20 mA), two more digital inputs and outputs, two PROFINET ports with an integrated switch, and more work memory. Choose the 1215C if you need analog output control of drives or proportional valves, or a line network topology; for predominantly digital standalone machines, the 1214C offers better value.