6ES7231-4HF32-0XB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
Eight differential channels, one module for the whole machine. Differential inputs are more than a wiring convention: they measure the signal between two terminals referred to ground, which suppresses the common-mode noise that drives, servos and contactors couple into field wiring. Fitting eight channels into a 45 mm module halves the width compared with two 4-channel modules and removes one backplane connection. Because the range is configured per channel, 4–20 mA transmitters and ±10 V sensors can be mixed on the same module — no need to order different variants by signal type.
13-bit ADC and a 625 μs cycle. Resolution is 12 bit plus sign, corresponding to digital values of ±27648 over the nominal range (bipolar) or 0–27648 (unipolar). A complete cycle over all eight channels takes 625 μs maximum, roughly 78 μs per channel — ample for closed-loop control of pressure, flow and temperature. Basic error is ±0.1 % at 25 °C, with a temperature error of ±0.1 % up to 55 °C and a total error of no more than ±0.2 % over the measuring range. That is sufficient for the vast majority of general machinery and process equipment; only metering-grade or weighing applications need a higher class of module.
Diagnostics and engineering convenience. The module supports wire-break diagnostics (transmitter break detection in current mode), overrange and underrange alarms, and supply-voltage monitoring. Diagnostics are reported to the CPU as alarms and can be surfaced directly on an HMI; each channel has a status LED on the front, plus a maintenance LED. Smoothing is selectable in four steps and interference suppression can be set to 50 or 60 Hz to match the local mains, cutting series-mode interference by around 40 dB. The terminal block is supplied with the module, wiring is done at the front, and the block can be unplugged as a whole during module replacement — no terminal-by-terminal rewiring.
① Eight differential inputs
8 analog channels in a single 45 mm slot; differential measurement rejects common-mode noise near drives and servos.
② Voltage and current combined
±10 V / ±5 V / ±2.5 V and 0–20 mA / 4–20 mA on one module, configured per channel — no variant change.
③ 13-bit ADC, ±0.1 %
12 bit plus sign, nominal digital value ±27648; ±0.1 % basic error at 25 °C, ≤ ±0.2 % total error over temperature.
④ 625 μs for all channels
A full cycle over 8 channels takes 625 μs max, about 78 μs per channel — enough for process loops and fast sampling.
⑤ Wire-break and supply diagnostics
Wire break, overrange/underrange and supply monitoring, alarms to the CPU, per-channel status LEDs plus maintenance LED.
⑥ Parameterizable smoothing
None / weak / medium / strong filtering and 50/60 Hz rejection of about 40 dB — no external filter needed on site.
General | |
Product type designation | SM 1231, AI 8×13 bit |
System / platform | SIMATIC S7-1200 (expansion to the right of the CPU) |
Number of analog inputs | 8; current or voltage, differential inputs |
Dimensions (W × H × D) | 45 × 100 × 75 mm (one slot width) |
Weight | approx. 180 g (net weight 0.187 kg) |
Mounting / degree of protection | 35 mm DIN rail, snapped to the right of the CPU / IP20 |
Power supply | |
Rated supply voltage | 24 V DC |
Current consumption at 24 V (typ.) | 60 mA |
Current from backplane bus 5 V (typ.) | 90 mA |
Power loss (typ.) | 1.5 W |
Analog inputs | |
Input ranges, voltage | ±10 V, ±5 V, ±2.5 V |
Input ranges, current | 0–20 mA, 4–20 mA |
Thermocouple / RTD / resistance | Not supported (use TC or RTD module) |
Input resistance, voltage | ≥ 9 MΩ |
Input resistance, current | 280 Ω |
Destruction limit (voltage / current) | 35 V / 40 mA |
Common mode voltage, max. | 12 V |
Cycle time, all channels (max.) | 625 μs |
Resolution incl. sign (max.) | 12 bit + sign (13-bit ADC) |
Digital value at nominal range | ±27648 bipolar; 0–27648 unipolar |
Isolation | Field side to backplane bus; no isolation between channels |
Accuracy and EMC | |
Basic error at 25 °C (voltage / current) | ±0.1 % of input range |
Temperature error | ±0.1 % up to 55 °C; ±0.2 % over total measuring range |
Series-mode rejection (f1 = 50/60 Hz) | 40 dB (DC to 60 V interference) |
Common-mode rejection (f = n × f1 ± 1 %) | Designed for 12 V common-mode voltage |
Smoothing of measured values | None / weak / medium / strong, parameterizable |
Integration time | Parameterizable |
Diagnostics and status | |
Diagnostics function / diagnostic alarm | Yes / yes |
Monitored | Supply voltage, wire break (current mode), overrange / underrange |
LED indication | Status LED per channel, maintenance LED |
Environment and approvals | |
Ambient temperature (horizontal / vertical) | −20 to +60 °C / −20 to +50 °C |
Storage and transport temperature | −40 to +70 °C |
Relative humidity | ≤ 95 % at 25 °C, no condensation |
Approvals | CE, UL, cULus, CSA, FM, RCM, KC, EAC, ATEX / IECEx, marine (BV / DNV / RINA / CCS / KR and others) |
Q1. Can this module read thermocouples or Pt100 sensors directly?
No. It accepts voltage and current signals only — the datasheet lists thermocouple, resistance thermometer and resistance as "No". For temperature use 6ES7231-5QF32-0XB0 (8× thermocouple) or 6ES7231-5PF32-0XB0 (8× RTD, supporting Pt100 / Pt1000 / Ni1000 / Cu10 in 2-, 3- or 4-wire connection). This is the most common ordering mistake in S7-1200 analog selection.
Q2. How do I connect a two-wire 4–20 mA transmitter? Does the module power it?
It can be connected, but the module does not provide a dedicated transmitter supply. A two-wire transmitter needs 24 V: take it from the system 24 V supply or the CPU sensor supply, then loop the current through the module's current input terminals (I+ / M). All channels share a reference potential, so keep loop drop and common-mode voltage (12 V max.) within limits. Four-wire transmitters connect their current output directly, with supply and signal separated.
Q3. Is 625 μs a simultaneous sample of all eight channels?
No. 625 μs is the maximum time for one complete cycle over all eight channels, roughly 78 μs per channel, and the channels are converted sequentially rather than sampled simultaneously. For phase-synchronous multi-channel measurement — three-phase power analysis, vibration phase — use a module with synchronous sampling or a dedicated measuring device; this module is not intended for that.
Q4. Are 13-bit resolution and ±0.1 % accuracy the same thing?
No. Resolution is the smallest change the module can distinguish: 13 bit over a ±27648 full scale is about 1/27648 ≈ 0.0036 %. Accuracy is how far the reading can be from the true value: the basic error here is ±0.1 % of range at 25 °C, i.e. roughly ±10 mV on the ±10 V range. In short, it resolves fine steps, but each reading may still be off by about 0.1 %. For metering or batching by weight, judge suitability by the accuracy figure, not the resolution.
Q5. Are the eight channels isolated from each other?
No. Isolation exists only between the field side and the backplane bus; the channels share a reference ground, so the common-mode voltage of every channel must stay within 12 V. Where signal sources sit at different ground potentials, where cables run long distances, or where strong drive interference is present, add a signal isolator ahead of the module — otherwise expect drift or crosstalk between channels.
Q6. Do I need to order a front connector separately?
No. S7-1200 SM modules are supplied with their terminal block and are wired directly at the front of the module — unlike S7-300 / S7-400, which require a separately ordered front connector. If a terminal block needs replacing after long service, S7-1200 SM terminal block spare kits are available (pack of 4).
Q7. Is it interchangeable with the older 6ES7231-4HF30-0XB0?
Yes. The 4HF30 is the earlier hardware version; the 4HF32 (this article) is the current production version with compatible function and terminal assignment. It can replace the older unit in the same TIA Portal project without changing channel addresses or configuration. Order the 4HF32 for new projects; when using it as a spare, check the nameplate and hardware version and confirm the configured ranges match the original project.
Q8. Is it still available, and is there a successor?
Yes, it can still be ordered. Siemens lists it as PM300: Active Product, but has announced product phase-out (PM400) effective 1 November 2026. New units remain available until 31 October 2027, after which the product moves to the PM410 spare-part phase with roughly nine to ten years of spare-parts commitment. For new projects, evaluate the S7-1200 G2 platform; for existing machines, build stock early and keep a complete backup of the TIA Portal project and firmware version. Confirm the exact successor article number and changeover date with Siemens or your authorized distributor.