6ES7517-3AP00-0AB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
Two PROFINET interfaces, one DP master. X1 carries two RJ45 ports behind an integrated switch with PROFINET IRT, isochronous mode, MRP/MRPD and DFP, and accepts up to 512 IO devices — 64 of them with IRT — at a 250 µs send clock. X2 is a single port without a switch, PROFINET RT only, with its own IP address and subnet and room for 128 IO devices: the HMI, the line SCADA link or the plant backbone sits there, separated from the machine network without an external router. X3 is a PROFIBUS DP master — RS485, 12 Mbit/s, 125 DP devices, 48 connections, equidistant and isochronous mode — so legacy DP equipment needs no gateway and no second controller. All three run concurrently, and the CPU keeps 320 connection resources (288 on the integrated interfaces) plus 64 S7 routing paths, so an engineering station can reach downstream devices across the whole topology.
Memory, speed and program structure. 2 MB of program memory and 8 MB of data memory hold up to 12 000 elements (OB, FB, FC, DB, UDT), with 1 MB per OB, FB or FC and 8 MB per data block (64 KB when absolutely addressed). OB resources are the widest of the standard range: 100 free-cycle OBs, 20 time-of-day, 20 delay and 20 cyclic interrupts down to 100 µs, 50 process interrupts, three DPV1 interrupts, three isochronous OBs and 100 startup OBs. At 2 ns per bit instruction, 3 ns per word and for fixed-point arithmetic, and 12 ns for floating-point, the controller closes fast loops in software that would otherwise need a dedicated motion or technology module — and still keeps cycle jitter under control thanks to isochronous OBs from 250 µs. The retentive area is 768 KB, of which 700 KB is usable; with the PS 60 W 24/48/60 V DC HF power supply it extends to 8 MB. The diagnostic buffer holds 3 200 entries (1 000 retentive) and up to eight traces can record signals inside the CPU.
Motion, IT integration and the power budget. Motion control resources total 10 240 — roughly seventy positioning axes at a 4 ms motion control cycle, or 128 at 8 ms, before gearing, camming, external encoders and probes are taken into account. OPC UA is a step above the mid-range CPUs: server with 64 sessions and up to 200 000 accessible variables, sampling from 10 ms, client with 40 connections — under the runtime licence "Large", not "Medium". HTTPS web server, Web API with 200 sessions, Modbus TCP, NTP and PROFIenergy complete the IT side. One planning detail deserves attention: the CPU draws about 30 W from the backplane bus while feeding only 12 W back into it, so the rack needs a system power supply module (for example PS 60 W) to cover the balance and the I/O modules — unlike a 1516, which can often run without one.
① 2 ns bit performance
2 ns bit, 3 ns word, 3 ns fixed-point, 12 ns floating-point — fast enough for software-based closed-loop and motion tasks.
② 2 MB / 8 MB work memory
12 000 elements, 1 MB blocks, 8 MB data blocks, 768 KB retentive (700 KB usable), extendable to 8 MB.
③ 512 + 128 IO devices
X1: IRT with 2-port switch, 512 devices (64 IRT). X2: separate RT interface with its own IP, 128 devices. X3: DP master, 125 slaves.
④ 10 240 motion control resources
About 70 positioning axes at 4 ms or 128 at 8 ms, plus synchronous axes, external encoders, cams, cam tracks and probes.
⑤ 320 connections, 64 routing paths
288 connections on the integrated interfaces; engineering access across PROFINET and PROFIBUS without extra hardware.
⑥ OPC UA "Large", 8 traces
64 sessions, 200 000 variables, 10 ms sampling, 40 client connections; 3 200-entry diagnostics and eight traces in the CPU.
General | |
Product type | CPU 1517-3 PN/DP (standard CPU, not fail-safe) |
Hardware version | FS11 (earlier batches FS08 / FS10) |
Firmware version | V3.1 (updateable); earlier batches V2.8 / V2.9 |
Engineering software | TIA Portal V19 (FW V3.1); V13 Update 3 or higher for FW V1.6 |
Dimensions (W × H × D) | 175 × 147 × 129 mm |
Weight | approx. 1.93 kg |
Mounting / degree of protection | S7-1500 profile rail / IP20 |
Memory | |
Work memory, program | 2 MB |
Work memory, data | 8 MB |
Load memory | SIMATIC Memory Card, max. 32 GB (required, 1 slot) |
Retentive data area | 768 KB max., of which 700 KB usable; extendable to 8 MB with PS 60 W 24/48/60 V DC HF |
Bit memory (M) | 16 KB max.; 8 clock memory bits |
Data block size | 8 MB (64 KB when absolutely addressed) |
OB / FB / FC size | 1 MB each |
Performance | |
Bit / word operations | 2 ns / 3 ns |
Fixed-point / floating-point | 3 ns / 12 ns |
Elements (OB, FB, FC, DB, UDT) | 12 000 total |
OBs available | 100 cyclic, 20 time-of-day, 20 delay, 20 cyclic (min. 100 µs), 50 process, 3 DPV1, 3 isochronous, 100 startup |
Nesting depth | 24 per priority class |
S7 counters / S7 timers | 2 048 / 2 048, retentivity adjustable |
IEC counters / timers | Unlimited, limited only by work memory |
Communication | |
Interface X1 | PROFINET IRT, 2× RJ45 with integrated switch, 100 Mbit/s |
Interface X2 | PROFINET RT, 1× RJ45, no switch, no IRT |
Interface X3 | PROFIBUS DP master, RS485, up to 12 Mbit/s, 125 DP devices, 48 connections |
IO devices | X1: 512 (64 with IRT); X2: 128 |
IRT update time | 250 µs – 4 ms at a 250 µs send clock; isochronous OB min. 250 µs distributed / 1 ms central |
Redundancy | MRP / MRP interconnection / MRPD, typical switchover 200 ms, max. 50 nodes per ring |
Connections / routing | 320 max. (288 on the integrated interfaces, 10 reserved for ES / HMI / web); 64 S7 routing paths |
OPC UA | Server: 64 sessions, 200 000 variables, sampling from 10 ms. Client: 40 connections. Runtime licence "Large" required |
Web server / protocols | HTTP and HTTPS, Web API 200 sessions; Modbus TCP; NTP; PROFIenergy; DFP |
Motion control | |
Resources | 10 240 (speed axis 40, positioning axis 80, synchronous axis 160, encoder 80, output cam 20, cam track 160, probe 40) |
Positioning axes (typical) | About 70 at a 4 ms motion control cycle; 128 at 8 ms |
Closed-loop blocks | PID_Compact, PID_3Step, PID-Temp with integrated optimization |
Power, display and environment | |
Rated supply | 24 V DC (19.2 – 28.8 V), reverse polarity protected; 5 ms power-fail buffering |
Current consumption | 1.55 A rated, 1.9 A max. |
Power loss / backplane | 24 W typ.; feeds 12 W to the backplane bus, draws 30 W from it — a system power supply is required |
Display | 6.1 cm, 6 keys and 1 mode selector; switches off above 50 °C horizontal / 40 °C vertical |
Ambient temperature | 0 to +60 °C horizontal / 0 to +40 °C vertical |
Storage and transport | −40 to +70 °C; installation altitude up to 5 000 m (restrictions above 2 000 m) |
Q1. What is the lifecycle status?
This article is cancelled. Siemens records delivery release on 4 April 2014, the phase-out announcement (PM400) on 1 October 2025, and product cancellation (PM410) on 1 October 2026. It is supplied as a spare part only, subject to stock. The official successor is 6ES7517-3AQ10-0AB0 — CPU 1517-3 PN. For a new line, specify the successor; for the installed base, stock spares or plan the migration now, because availability of the classic article will only get worse.
Q2. What changes when migrating to the successor 6ES7517-3AQ10-0AB0?
The successor is a different platform, not a drop-in: 4 MB program and 50 MB data instead of 2 MB / 8 MB, 0.6 ns bit performance instead of 2 ns, firmware V4.1 with TIA Portal V21. The decisive difference is the interfaces — the new CPU has no PROFIBUS DP port: X1 and X2 are both PROFINET IRT with two-port switches, X3 is a standard Ethernet port. Any DP slave (ET 200M, DP drives, field instruments) then needs a CM DP module such as 6ES7545-5DA00-0AB0. Plan the network rework, the new device names and a full re-download, not just a CPU swap.
Q3. Why does the rack need an additional power supply?
Because of the power balance. The CPU feeds 12 W into the backplane bus but draws about 30 W from it, so the difference, plus the consumption of the I/O modules, has to come from a system power supply module — a PS 60 W 24/48/60 V DC HF, for example. This is the most common surprise when a 1516 is replaced by a 1517 in an existing rack: the 1516 often runs without a PS, the 1517 does not. Check the backplane budget in the TIA Selection Tool before ordering.
Q4. Is the SIMATIC Memory Card included?
No, and it is mandatory. The CPU has no integral load memory: program, hardware configuration, recipes and retentive data all live on the card, up to 32 GB. Order it with the CPU and keep a programmed spare on site — with a cancelled article, a spare card is often easier to obtain than a spare CPU.
Q5. How many axes can it run?
10 240 motion control resources in total, with a positioning axis costing 80, a synchronous axis 160, a speed axis 40, an external encoder 80, an output cam 20, a cam track 160 and a probe 40. Siemens quotes about 70 positioning axes at a 4 ms motion control cycle, or 128 at 8 ms — figures that assume positioning only. Gearing and camming consume resources two to four times faster, and every axis also takes cycle time from the user program, so validate the real configuration in the TIA Selection Tool.
Q6. Can it run safety functions?
No — this is a standard CPU without PROFIsafe. Safety applications require the F-version 1517F-3 PN/DP (6ES7517-3FP00/3FP01-0AB0) with F-DI / F-DO modules; note that this F-version is affected by the same phase-out schedule. Standard and safety programs can share an F-CPU, but never a standard one.
Q7. What OPC UA licence is needed?
The "Large" runtime licence — one level above the "Medium" licence of the 1515-2 PN and 1516-3 PN/DP, and two above the "Small" of the 1513-1 PN. That buys 64 server sessions, up to 200 000 accessible variables, a 10 ms minimum sampling interval and 40 client connections. Without the licence the OPC UA server cannot be activated; the web server, S7 communication and Modbus TCP continue to work.
Q8. 175 mm width, 1.93 kg — what does that mean for the cabinet?
It takes 175 mm of rail, five times the width of a 35 mm single-interface CPU, and the 24 W power loss has to be removed from the enclosure — plan the thermal budget, not just the rail space. In vertical mounting the ambient limit drops from 60 °C to 40 °C and the display switches off at that point. Also allow space for the memory card to be exchanged with the door closed, and for the front connector of the supply.