1769-PB2
AB
| Availability: | |
|---|---|
| Quantity: | |
A controller and its expansion I/O share one 1769 backplane: logic runs from 5.1V, field-side circuits from the 24V auxiliary rail. When points are added and bus loading nears the limit of the controller's built-in supply, one 1769-PB2 re-establishes an independent power budget for that bank — no controller change, no program edits.
It mounts anywhere in an I/O bank and accepts up to eight modules per side (sixteen total). The 19.2–31.2V DC input rides through brownouts; both outputs are current-limited and short-circuit protected. Pure hardware — no configuration or firmware — compatible with all 1769 I/O and L1x/L2x/L3x controllers.
1
Economical mid-range capacity5.1V/2.0A and 24V/0.8A for typical I/O banks.
2
Wide 19.2–31.2V DC inputTolerates brownouts; 10 ms–10 s ride-through.
3
Drives up to 16 I/O modulesEight per side, close to the load, space-saving.
4
Protection & status LEDsOvercurrent, short, overvoltage, thermal; power and fault LEDs.
5
No configuration, no fanPure hardware, ready to run; 0–60 °C natural cooling.
6
Compact DIN-rail package118 × 70 × 87 mm, 454 g; rail or panel mounting.
Catalog no. | 1769-PB2 | Product family | CompactLogix / Compact I/O |
Function | DC expansion power supply | Nominal input | 24V DC (19.2–31.2V DC) |
Output 1 | 5.1V DC / 2.0 A | Output 2 | 24V DC / 0.8 A |
Input power | 50 VA @ 24V DC | Inrush current | ≤ 30 A @ 31.2V DC |
Dissipation | 7.5 W @ 60 °C | Isolation | 75V continuous, reinforced |
Protection | Overcurrent, short circuit, overvoltage and overtemperature; internal fuse Wickmann 19193-6.3A / Littelfuse 021706.3MXP | ||
Mounting | 35 mm DIN rail / panel | Wire size | 14 AWG (2.5 mm²), 90 °C copper |
Dimensions | 118 × 70 × 87 mm | Weight | 454 g (1.00 lb) |
Operating temp. | 0–60 °C (−40–85 °C storage) | Humidity | 5–95%, non-condensing |
Vibration / shock | 5g @ 10–500 Hz / 30g | Altitude | 2000 m max |
Certifications | c-UL-us, CE, ATEX, IECEx, CCC, UKCA; open-type enclosure, in-cabinet mounting | ||
QPB2 or PB4 — which one?
Choose the 1769-PB2 when the bank stays within 2.0A @ 5.1V and 0.8A @ 24V; pick the 1769-PB4 for denser banks or heavier loads.
QCan it power sensors or solenoids?
No. The 24V output serves module circuitry only; field devices need a separate 24V supply.
QDoes it accept 220V AC input?
No — 24V DC only. For AC supplies use the 1769-PA2 (120/240V AC).
QIs configuration or firmware needed?
None. It is a pure hardware module with no parameters or firmware.
QNo output after power-up?
Check the 19.2–31.2V DC input, terminal polarity, load shorts and the fuse, then cycle power.