1769-IF16C
AB
| Availability: | |
|---|---|
| Quantity: | |
The module offers 16 single-ended current inputs using Sigma-Delta conversion with 16-bit resolution (15 bits plus sign for bipolar ranges) and approximately ±0.5% full-scale accuracy at 25°C. Selectable input filters (16Hz / 50Hz / 60Hz and more) suppress field noise, while over-range and under-range detection plus channel diagnostics simplify troubleshooting. No field calibration is required. The module occupies a single slot and can be used as local I/O or as distributed I/O over EtherNet/IP.
● 16 single-ended current inputs: 0~20mA / 4~20mA ranges, compatible with 2-wire and 4-wire transmitters
● High resolution: 16-bit unipolar / 15-bit plus sign bipolar, Sigma-Delta conversion
● Selectable filtering: 16Hz / 50Hz / 60Hz / 315Hz / 1365Hz for line-frequency and noise rejection
● Channel diagnostics: over/under-range bit reporting, process alarms, per-point status LEDs
● No calibration: automatic calibration reduces maintenance effort
● Compact and high density: one slot replaces multiple modules, saving panel space
Item | Specification |
Catalog Number | 1769-IF16C |
Input Channels | 16 single-ended analog current inputs |
Input Range | 0~20mA / 4~20mA (full scale 0~21mA / 3.2~21mA) |
Resolution / Converter | 16-bit unipolar, 15-bit plus sign bipolar / Sigma-Delta |
Accuracy | ±0.5% full scale @25°C; drift ±0.0045%/°C |
Input Impedance | approx. 249Ω |
Filter Frequency | 16Hz / 50Hz / 60Hz / 315Hz / 1365Hz (selectable) |
Backplane Current / Power | 190mA @5.1V DC; 70mA @24V DC / 4.0W max |
Isolation | 500V AC or 710V DC for 1 minute (input group to bus) |
Operating / Storage Temp. | 0~60°C / -40~85°C |
Mounting Position / Type | Within 8 modules of the power supply; DIN rail or panel mount |
Dimensions / Weight | approx. 118×35×87mm / approx. 300g |
Wiring | Removable terminal block (RTB, ordered separately) |
Certifications | UL, CE, UKCA and other industry certifications |
Q1: Which controllers is the 1769-IF16C compatible with? It works with the 1769 Compact I/O platform of CompactLogix and MicroLogix 1500 controllers.
Q2: Can 2-wire 4~20mA transmitters be connected? Yes. The module accepts standard 4~20mA signals from both 2-wire and 4-wire transmitters; 2-wire devices require an external 24V DC loop supply.
Q3: Does the module require field calibration? No. It performs automatic calibration; simply select the appropriate filter frequency for your noise environment.
Q4: How can I improve stability for small signals? Use shielded twisted-pair cable with single-point grounding, select the 16Hz or 50/60Hz filter, and keep the module within 8 modules of the power supply.