6ES7321-1BP00-0AA0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The 64-point SM 321 uses a double-row 40-pin front connector design, bringing out all 64 inputs through two terminal blocks and connecting cables for tidy cabinet wiring and easy maintenance. Input characteristics meet IEC 61131 type 1: a "1" signal is +13 to +30V and a "0" signal is -30 to +5V, with a typical input current of 4.2 mA per point and a typical signal delay of 4.2 ms (1.2 to 4.8 ms), effectively filtering contact bounce and short interference. Inputs are isolated from one another in groups of 16, and each group is isolated from the backplane bus by optocouplers with a 500V DC test voltage, suppressing common-mode noise in the field. Every input has a green status LED for point-by-point verification during commissioning. A 40-pin terminal block (6ES7392-1.N00-0AA0) and connecting cable (6ES7392-4...0-0AA0) are required separately.
● 64-point high density: 64 inputs in a single 40 mm wide module, saving rack slots
● Isolation in groups of 16: optocoupler isolation between groups and to the backplane, 500V DC tested
● Sink/source compatible: PNP and NPN sensors connect directly for flexible wiring
● 4.2 ms input filtering: suppresses contact bounce and field noise for stable signals
● Per-point status LEDs: a green LED on every channel for straightforward commissioning and inspection
● Long-distance acquisition: shielded cable up to 1,000 m, unshielded 600 m
Item | Specification |
Order No. / Model | 6ES7321-1BP00-0AA0 / SM 321 DI 64×24V DC |
Input Points | 64, 24V DC, sink/source |
Input Characteristic | According to IEC 61131, type 1 |
Signal Voltage | "1": +13 to +30V; "0": -30 to +5V |
Input Current | Typ. 4.2 mA at "1" |
Input Delay | Typ. 4.2 ms (1.2 to 4.8 ms for 0→1 and 1→0), not parameterizable |
Simultaneously Controllable Inputs | ≤40°C: 64; ≤60°C: 32; vertical mounting ≤40°C: 32 |
Galvanic Isolation | Between channels in groups of 16; channels to backplane via optocoupler; 500V DC tested |
Load Voltage L+ | 24V DC, reverse polarity protected |
Backplane Bus Current | Max. 100 mA (5V DC) |
Power Loss | Typ. 7W |
Cable Length | 1,000 m shielded; 600 m unshielded |
Status Indication | Green LED per channel; no SF group fault LED |
Diagnostics / Interrupts | No diagnostic alarm or hardware interrupt |
2-Wire Sensors | Not supported (3-wire or 4-wire sensors with external supply required) |
Front Connector | 40-pin; terminal block 6ES7392-1.N00-0AA0 and cable 6ES7392-4...0-0AA0 required |
Dimensions (W×H×D) | 40 × 125 × 112 mm |
Weight | Approx. 230 g |
Q1: Are terminal blocks included? No. A 40-pin front connector terminal block (6ES7392-1.N00-0AA0) and matching connecting cable (6ES7392-4...0-0AA0) must be ordered separately; without them the module cannot be wired.
Q2: Can all 64 points be energized at the same time? It depends on ambient temperature: up to 64 points below 40°C, but no more than 32 points between 40 and 60°C; vertical mounting is limited to 32 points even below 40°C. Allow margin in hot cabinets.
Q3: Can two-wire sensors be connected directly? No. This module does not support 2-wire sensors (dry contacts or sensors requiring an external supply). Use 3-wire or 4-wire sensors, or provide a separate sensor supply.
Q4: Why is there no wire-break or short-circuit diagnostics? This is a basic input module without diagnostic alarms or hardware interrupts; it provides per-point status indication only. For wire-break detection, choose an SM 321 model with diagnostics.