6ES7231-4HA30-0XB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The SB 1231 integrates analog acquisition directly into the CPU. Once plugged in, it is ready to use while the CPU's footprint and DIN-rail space remain unchanged — a clear advantage where cabinet space is tight. The differential input structure effectively rejects common-mode interference. Measurement is based on the integrating principle, with a maximum conversion time of 156.25 µs for all channels, and the filter can be set to 10 Hz, 50 Hz, 60 Hz or 400 Hz to balance response speed against mains interference rejection. The gold-plated removable terminals support permanent wiring, so a replacement board can be fitted without disturbing existing wiring, shortening downtime. The board is powered from the CPU backplane at 5V DC and requires no external 24V supply. Note that it offers no RTD or thermocouple measurement, and there is no electrical isolation between the field side and the logic side; use a signal isolator for long cable runs or heavily disturbed loops.
● One differential analog input: ±10V, ±5V, ±2.5V voltage or 0 to 20 mA current in a single board
● No module slot required: plugs into the CPU front holder, leaving dimensions unchanged
● Gold-plated removable terminals: permanent wiring supported, no rewiring when replacing the board
● Fast conversion: 11 bits plus sign, max. 156.25 µs for all channels
● Four selectable filters: 10/50/60/400 Hz, 85 dB noise rejection for different mains environments
● Backplane powered: supplied by the CPU (typ. 55 mA), no external 24V DC needed
Item | Specification |
Order No. / Model | 6ES7231-4HA30-0XB0 / SB 1231, AI 1×12 bit |
Product Type | S7-1200 analog input signal board (SB) |
Inputs and Type | 1 input, differential, voltage or current |
Input Ranges | Voltage ±10V / ±5V / ±2.5V; current 0 to 20 mA |
Resolution / Full Scale | 11 bits + sign; data word -27648 to 27648 |
Accuracy | ±0.3% FS at 25°C; ±0.6% FS from -20 to 60°C |
Principle / Conversion Time | Integrating; max. 156.25 µs for all channels (400 Hz rejection) |
Noise / Common-Mode Rejection | 85 dB depending on filter setting (10/50/60/400 Hz); common-mode rejection 40 dB (DC to 60 Hz) |
Input Impedance / Overload | Voltage ≥9 MΩ, current 250 Ω; ±35 V / 40 mA without damage |
Isolation | None between field side and logic side; none between channels |
Power Supply / Loss | 5V DC from CPU backplane, typ. 55 mA; no external 24V DC; approx. 0.4 W |
Diagnostics | Overflow / underflow alarm; no wire-break detection |
Cable Length | Shielded twisted pair, max. 100 m |
Dimensions / Weight | 38 × 62 × 21 mm / approx. 35 g |
Mounting and Quantity | CPU front signal board holder; one board per CPU; no SM expansion slot used |
Protection / Operating Temperature | IP20; 0 to 55°C (horizontal mounting) / 0 to 45°C (vertical mounting) |
Firmware Requirement | CPU firmware V2.0 or later |
Q1: Is this a 4-channel RTD input module? No. The 6ES7231-4HA30-0XB0 is an SB 1231 signal board with a single input for ±10V voltage or 0 to 20 mA current, and it offers no RTD or thermocouple measurement. For direct temperature measurement choose the SM 1231 RTD 4×16 bit (6ES7231-5PD32-0XB0) or SM 1231 TC 4×16 bit (6ES7231-5QD32-0XB0). The "1231" in the designation is easily confused with the SM 1231 series — the most common source of misordering for this part.
Q2: Can a 4 to 20 mA transmitter be connected? Yes. The rated current range is 0 to 20 mA, so a 4 to 20 mA signal falls within it (4 mA corresponds to approximately 5530 in the data word); convert it to engineering units in the program with NORM_X / SCALE_X. The 0 to 4 mA segment cannot be used for wire-break diagnostics, however — if broken-wire alarms are required, select an SM 1231 current input module with wire-break detection.
Q3: How does current wiring differ from voltage wiring? For current input, terminals R and 0+ must be jumpered so that the internal 250 Ω shunt resistor is inserted into the loop. For voltage input, never jumper terminal R. Two-wire transmitters need an external 24V DC source to complete the loop (the board does not supply transmitter power); four-wire transmitters connect to 0+ / 0-. Gold-plated terminals must be used (supplied with the board, also available as a spare part) — poor contact directly affects measurement accuracy.
Q4: How many signal boards per CPU, and is an external 24V supply needed? Each S7-1200 CPU accepts only one signal board, mounted in the holder on the front of the CPU. It occupies no SM expansion slot on the right and does not change the CPU's mounting dimensions. The board is powered from the CPU backplane at 5V DC (typ. 55 mA) and needs no external 24V DC. CPU firmware V2.0 or later is required.