6ES7223-1BH32-0XB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The SM 1223 merges input and output expansion into a single step. The inputs comply with IEC 61131 Type 1 and accept both sourcing (PNP) and sinking (NPN) sensors directly; the input delay is parameterizable from 0.2 to 12.8 ms in groups of four, balancing response speed and noise immunity. The outputs are solid-state sourcing transistors with switching delays of only 50 µs / 200 µs and no contact wear, suited to high-frequency switching of 24V DC loads such as solenoid valves, indicators, and small relays. Every channel carries a status LED for straightforward field troubleshooting, and the removable terminal blocks support permanent wiring — a module can be replaced without unwiring point by point. The module connects to the CPU through the integrated backplane bus connector and is recognized automatically in TIA Portal, with no jumpers or address settings required.
● 8 in + 8 out in one module: expands digital inputs and outputs simultaneously in a 45 mm body
● Sink/source universal inputs: direct connection of PNP and NPN sensors, IEC 61131 Type 1
● Fast transistor outputs: 0.5 A per point, 50 µs / 200 µs switching, no contact wear
● Configurable input delay: 0.2 to 12.8 ms, parameterizable in groups of four
● Plug-and-play: direct backplane connection, automatically recognized in TIA Portal
● Tool-free module replacement: removable terminal blocks plus per-channel status LEDs
Item | Specification |
Order No. / Model | 6ES7223-1BH32-0XB0 / SM 1223, DI 8×24V DC, DQ 8×24V DC |
Product Type | S7-1200 digital input/output signal module (SM) |
Digital Inputs | 8 points, 24V DC, sink/source universal, IEC 61131 Type 1, 2 isolation groups |
Input Levels | "1": 15V DC at 2.5 mA (typ. 4 mA); "0": 5V DC at 1 mA |
Input Delay | 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 12.8 ms, parameterizable (groups of 4) |
Digital Outputs | 8 points, sourcing solid-state transistor, 24V DC, 1 isolation group |
Output Capacity | Resistive load max. 0.5 A per point, lamp load 5 W; 4 A total per group |
Output Signal / Delay | "1" min. 20V DC (L+ −0.5V); "0" max. 0.1V; on/off delay approx. 50 µs / 200 µs |
Short-Circuit Protection | None built-in; external fusing required. Inductive clamp voltage limited to L+ −48V |
Cable Length | Inputs: 500 m shielded / 300 m unshielded; outputs: 150 m unshielded |
Isolation | 500V AC (type test) between field side and logic side |
Supply / Backplane Current | Load voltage L+ 24V DC (20.4 to 28.8V); backplane 5V DC max. 145 mA |
Power Loss | Typ. 2.5 W |
Terminals | Removable terminal blocks, permanent wiring supported for quick module swap |
Dimensions / Weight | 45 × 100 × 75 mm / approx. 210 g |
Protection / Temperature | IP20; -20 to 60°C (horizontal), up to 50°C vertical; storage -40 to 70°C |
Configuration | STEP 7 (TIA Portal), automatically recognized on insertion; no jumpers or address setting |
Certifications | UL, cULus, FM, CE, RCM, KC, marine approvals |
Q1: How do I choose between 1BH32 (transistor) and 1FH32 (relay)? Both are 8DI/8DO; they differ in output type. The 1BH32 has transistor outputs of 0.5 A per point for 24V DC loads only, but switches fast with no contact wear — suited to frequently actuated loads such as solenoid valves. The 1FH32 has relay outputs of 2 A per point for AC or DC loads, but with low switching frequency and mechanical contact life. Choose 1BH32 for frequent switching of 24V DC loads; choose the relay version for 230V AC or higher-current loads.
Q2: The outputs have no short-circuit protection — what should be considered? The official datasheet states there is no built-in short-circuit protection, so configure a separate fuse or miniature circuit breaker for the output circuits. When driving inductive loads such as solenoids and contactors, the module clamps turn-off overvoltage to L+ −48V internally, but a freewheeling diode on the load side is still recommended to extend the life of the output transistors.
Q3: PNP or NPN sensors? Is a separate power supply needed? The inputs are sink/source universal, so both PNP and NPN sensors connect directly without conversion. A "1" signal is 15V DC at 2.5 mA or more, supplied from the field-side 24V DC shared with the CPU. Input delay is set in TIA Portal in groups of four; select 0.2 ms where fast response is required.
Q4: Is this module still purchasable, or discontinued? Siemens has marked this product for phase-out from 1 November 2026, as the classic S7-1200 is gradually replaced by the S7-1200 G2 series. Spare parts for existing installations remain procurable; for new projects, we recommend also evaluating the corresponding G2 module to avoid future lead-time constraints.