6ES7522-1BH01-0AB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The module provides 16 digital output channels arranged in 2 electrically isolated groups of 8, with up to 4 A per group, 8 A per module, and 0.5 A per channel. Single-channel diagnostics detect wire break, short circuit, missing load voltage, and group faults down to the individual channel, reported in real time and indicated by per-channel status LEDs.
Each output supports a configurable substitute value so a predefined safe level is output even when the CPU is down. An integrated switching cycle counter monitors wear on connected actuators such as solenoid valves, enabling predictive rather than reactive maintenance. Isochronous mode with a minimum TCO of 70 µs meets deterministic motion control requirements, and safety-oriented shutdown of load groups up to SIL2 (EN IEC 62061) and Category 3 / PL d (EN ISO 13849-1) is supported with an S7-1500 CPU. At only 35 mm wide, the module mounts on the S7-1500 rail or ET 200MP station; front connectors (screw or push-in type) are ordered separately.
● 16 fast transistor outputs: sourcing (PNP), 0.5 A per channel, output delay from 100 µs, switching frequency up to 100 Hz with resistive load
● Single-channel diagnostics: wire break, short circuit, missing load voltage, and group faults detected and reported per channel — fault location down to the point
● Switching cycle counter: counts actuations of solenoid valves and similar actuators for wear prediction and predictive maintenance
● Safety-oriented shutdown: load group shutdown up to SIL2 (EN IEC 62061) / Cat. 3, PL d (EN ISO 13849-1)
● Substitute values: configurable per channel to output a predefined safe state on CPU failure
● Isochronous mode: minimum TCO 70 µs, Shared Output (MSO) support for deterministic control
● Space-saving design: only 35 mm wide, common to S7-1500 rails and ET 200MP stations, hardware-compatible with the ST version (6ES7522-1BH00-0AB0)
Item | Specification |
Order number | 6ES7522-1BH01-0AB0 |
Product type | DQ 16x24VDC/0.5A HF digital output module |
Number of outputs | 16 channels, 8 per group, 2 groups |
Output type | Transistor, sourcing (PNP), IEC 61131 type 0.5 |
Rated output voltage / current | 24 V DC / 0.5 A per channel |
Load supply voltage | 24 V DC (permissible range 19.2–28.8 V DC), reverse-polarity protected |
Max. current per group / module | 4 A / 8 A |
Output delay (resistive load) | "0"→"1" max. 100 µs; "1"→"0" max. 500 µs |
Switching frequency | resistive 100 Hz; inductive (DC-13) 0.5 Hz; lamp load 10 Hz |
Short-circuit protection | electronic (typ. response threshold 1 A), inductive shutdown limited to L+ (−53 V) |
Diagnostics | per channel: wire break / short circuit / missing load voltage / group fault; configurable substitute values |
Safety-oriented shutdown | up to SIL2 (EN IEC 62061) / Cat. 3, PL d (EN ISO 13849-1) |
Isochronous mode | supported, TCO min. 70 µs, bus cycle TDP min. 250 µs |
Backplane power / power loss | 1.1 W / typ. 2 W |
Cable length | shielded max. 1,000 m; unshielded max. 600 m |
Ambient temperature | 0…+60 °C (horizontal / vertical mounting) |
Dimensions (W×H×D) | 35 × 147 × 129 mm |
Net weight | approx. 230 g |
Front connector | ordered separately (screw or push-in type) |
Engineering | TIA Portal V13 SP1 or higher; firmware V1.1.0, update-capable |
Q1: What is the difference between the HF and ST versions?
The HF (High Feature) version adds single-channel diagnostics, the actuator switching cycle counter, and safety-oriented shutdown up to SIL2/PL d on top of the ST version (6ES7522-1BH00-0AB0). Both are hardware-compatible with identical pin assignment — choose HF where diagnostics and safety matter most.
Q2: Can the module be used on ET 200MP?
Yes. It works in both the SIMATIC S7-1500 local rack and ET 200MP distributed I/O stations, and can also be used as standard slave I/O in systems such as S7-300/400 via PROFIBUS/PROFINET GSD files.
Q3: Is the front connector included?
No. The front connector must be ordered separately and is available in screw-terminal or push-in versions, common to all S7-1500 I/O modules.
Q4: What is the switching cycle counter and what is it used for?
The module counts switching operations of connected actuators (e.g., solenoid valves) and raises a maintenance alarm when a configured threshold is reached, prompting preventive actuator replacement and shifting maintenance from reactive to predictive.
Q5: Which faults can the diagnostics detect?
Each channel detects wire break, short circuit to ground, and missing load voltage (L+), with group fault alarms and per-channel status LEDs. All diagnostics can be configured and read per channel in TIA Portal.