6ES7307-1EA80-0AA0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The module has a single-phase AC input with a voltage selector switch on the housing for 120 V or 230 V. The actual input range covers 93–132 V and 187–264 V at 47–63 Hz, tolerating the weak and fluctuating grids often found at remote sites. Input current is approximately 2.1 A at 120 V and 1.2 A at 230 V. Inrush current is limited to a maximum of 45 A (at 25 °C, limiting duration 3 ms, I²t approx. 1.8 A²s), preventing upstream breakers from tripping when several devices power up together. An internal T 3.15 A/250 V fuse (not accessible from outside) protects the input; an upstream miniature circuit breaker of 10 A characteristic C or 6 A characteristic D is recommended.
The output is a controlled, isolated 24 V DC rated 5 A with ±3% tolerance and a residual ripple of max. 150 mV (typically 40 mV). A soft-start design prevents overshoot at power-up (response delay max. 3 s, rise time approx. 100 ms), providing clean power for the PLC and sensitive analog loops. Protection is comprehensive: output current limiting at 5.5–6.5 A, electronic shutdown with automatic recovery after a short circuit, short-term overload capability of approx. 20 A (180 ms at start-up, 80 ms in operation), and an additional control loop that shuts the output down at approx. 30 V in case of overvoltage, restarting automatically. Efficiency is approx. 84% with typical power loss of 23 W, keeping heat build-up low inside sealed outdoor cabinets.
Input and output are safely isolated, and the output meets SELV requirements (EN 60950-1 / EN 50178, creepage and clearance > 5 mm). The unit is protection class I and must be connected to a reliable protective conductor; leakage current is max. 3.5 mA (typically 0.3 mA), degree of protection IP20. A green "24 V OK" LED on the front panel indicates a healthy output. Connection is via screw terminals (L, N, PE and L+, M; 0.5–2.5 mm²). Cooling is natural convection without a fan; leave 50 mm clearance above and below, while the left and right sides may be mounted flush.
Far wider than the standard 0 to +60 °C; climate class 3K5 with transient condensation permitted.
Approx. 120 W capacity, ±3% accuracy, ripple ≤150 mV, soft start without overshoot.
120/230 V AC selected by switch, effective range 93–264 V at 47–63 Hz for weak grids.
Current limiting 5.5–6.5 A, electronic short-circuit shutdown with auto-restart, ~30 V overvoltage trip.
Isolated input/output, SELV output, class I, IP20, leakage current ≤3.5 mA.
Powers sensors, transmitters and DI circuits as well as the backplane — no extra supply needed.
Product type | SIMATIC S7-300 regulated power supply PS307, 5 A, outdoor version |
|---|---|
Input voltage | 1-phase AC 120 V / 230 V (selector switch on the device) |
Input range | AC 93–132 V (120 V setting) / AC 187–264 V (230 V setting) |
Line frequency | 50/60 Hz (range 47–63 Hz) |
Input current | Approx. 2.1 A at 120 V; approx. 1.2 A at 230 V |
Inrush current | Max. 45 A at 25 °C, limiting duration 3 ms, I²t approx. 1.8 A²s |
Input protection | Internal T 3.15 A/250 V fuse (not accessible); upstream MCB ≥10 A char. C or ≥6 A char. D recommended |
Output voltage | DC 24 V ±3% (fixed, no potentiometer) |
Output current / power | 5 A (0–5 A), rated output power approx. 120 W; parallel operation not permitted |
Residual ripple | Max. 150 mV (typically 40 mV) |
Overload & short circuit | Current limiting 5.5–6.5 A; electronic shutdown with automatic restart; short-term approx. 20 A (180 ms start-up / 80 ms operation) |
Overvoltage protection | Additional control loop, shutdown at approx. 30 V with automatic restart |
Efficiency / loss | Approx. 84% / typically 23 W |
Isolation | Galvanic isolation input–output; SELV output (EN 60950-1 / EN 50178), creepage > 5 mm |
Protection rating | Class I (protective conductor required); leakage current ≤3.5 mA (typ. 0.3 mA); IP20 |
Status indication | Green LED: lit when 24 V output is OK |
Connection & mounting | Screw terminals L, N, PE and L+, M (0.5–2.5 mm²); slot 1 on S7-300 rail (far left); 50 mm clearance top and bottom |
Ambient conditions | Operation −25 to +70 °C; storage/transport −40 to +85 °C; humidity class 3K5 (EN 60721, transient condensation permitted) |
Dimensions / weight | W 80 × H 125 × D 120 mm; net weight approx. 0.57 kg |
Approvals | CE; UL (UL 508, File E143289); CSA (CSA C22.2 No. 142) |
Lifecycle | Phased out since 2023-10-01 (PM400); supplied mainly as stock / spare part |
Q1: What is the difference between 1EA80 (outdoor) and 1EA01 (standard)?
Both are 5 A PS307 supplies with identical electrical ratings, output, mounting and wiring. The difference is environmental capability: the 1EA80 is the outdoor wide-temperature version rated −25 to +70 °C, climate class 3K5 with transient condensation permitted, while the standard 1EA01 is rated 0 to +60 °C. Choose 1EA80 for outdoor cabinets, sheltered enclosures, pump stations or workshops with temperature extremes; the 1EA01 is sufficient for ordinary indoor control cabinets.
Q2: PS307 comes in 2 A / 5 A / 10 A — how do I choose?
Add up the current drawn by all modules in the rack plus external 24 V loads and allow 20–30% margin: the 2 A version suits small configurations (CPU plus a few SM modules); this 5 A version (approx. 120 W) suits medium configurations and can also supply some sensors; choose the 10 A version for larger loads or when many DI circuits must be fed. The supply capacity must match the total backplane current demand.
Q3: Can the 24 V output power external sensors or indicator lamps?
Yes. The PS307 can be used as a load power supply for sensors, transmitters and digital input circuits. Note, however, that the 5 A is shared with the backplane load — use only about 60–70% of the rating and verify protection coordination. For heavy external loads or where independent disconnection is required, use a separate 24 V supply.
Q4: Can two units be paralleled for more current or redundancy?
No. This model explicitly does not support parallel output connection (stated in the data sheet); paralleling causes load-sharing imbalance and may trigger protection. Choose the 10 A version for more current, and a redundancy-capable supply module or dedicated redundancy module for redundant 24 V architectures.
Q5: Is the output voltage adjustable? What if the site needs 26 V?
The output is fixed at 24 V ±3% with no adjustment potentiometer. If voltage drop over long cables is a problem, increase the conductor cross-section, shorten the cable run or use a supply with adjustable output; do not insert regulating devices in the output circuit.
Q6: Can it be used with S7-1200 / S7-1500?
No. The PS307 is dedicated to S7-300 and feeds the rack through the S7-300 rail and backplane bus bars, which are not compatible with the S7-1200/1500 backplane. Use the PM1207 for S7-1200 and the PM1507 family for S7-1500.
Q7: Must the power supply be configured in STEP 7 hardware configuration?
No. The power supply does not communicate on the backplane bus and occupies no module address, so it does not need a slot in the STEP 7 hardware configuration (some versions allow it as a placeholder). Simply mount and wire it — replacing the supply therefore does not affect the existing program or configuration.
Q8: The model is phased out — can I still buy it, and what replaces it?
Yes. We supply stock units and tested refurbished spare parts and support exchange/repair services; for batch projects please confirm stock and lead time in advance. Alternatives: for indoor applications with moderate temperatures, the standard 1EA01 can be evaluated (also in phase-out, stock to be confirmed); for new projects we recommend migrating to the S7-1200 (PM1207) or S7-1500 (PM1507) platform — we can assist with rack retrofit assessment and program porting.