1756-L84ES
AB
| Availability: | |
|---|---|
| Quantity: | |
The front panel offers one 10/100/1000 Mbps Gigabit Ethernet port and one USB 2.0 programming/diagnostic port, plus a 4-character alphanumeric display that shows IP address, firmware revision and fault codes — basic diagnostics are possible on site without a laptop. Backplane demand is only 1.2 A @ 5.1 V DC (plus 5 mA @ 1.2 V DC), with 6.2 W typical power dissipation and 21.2 BTU/hr heat load, keeping chassis power requirements low. Program retention uses an embedded energy-storage module (no battery required) with an optional 2 GB SD card (1784-SD2) for long-term nonvolatile storage, so a replacement controller can be restored simply by inserting the card. The controller supports up to 31 standard tasks plus 1 safety task, up to 1,000 programs per task, a maximum of 128,000 digital and 4,000 analog I/O points, 256 motion axes and 250 EtherNet/IP devices, and allows Removal and Insertion Under Power (RIUP) for maintenance without shutting down the system. The safety and standard sections are strictly isolated in memory and execution; the safety task accepts Ladder Diagram (LD) only and is protected by safety signature and safety lock mechanisms against unauthorized modification.
One controller, one slot for both standard and safety control — no separate safety PLC or extensive hardwiring.
Complies with IEC 61508/61511 SIL 3 and ISO 13849-1 PL e Cat. 4 for high-risk machine safety circuits.
20 MB standard user memory for large programs; 6 MB dedicated safety memory for safety logic.
Safety signals travel over EtherNet/IP with up to 248 safety inputs / 248 safety outputs, greatly simplifying wiring.
One Gb Ethernet port, up to 250 EtherNet/IP devices and 256 integrated motion axes.
Embedded energy-storage module needs no battery; optional 2 GB SD card; RIUP supported.
Product type | Allen-Bradley GuardLogix 5580 safety controller (ControlLogix 5580 platform) |
|---|---|
Catalog No. / UPC | 1756-L84ES / 889508112312 |
User memory | 20 MB standard memory + 6 MB dedicated safety memory |
Safety rating | SIL 3 (IEC 61508 / IEC 61511); PL e, Cat. 4 (ISO 13849-1) |
Safety communication | CIP Safety over EtherNet/IP; up to 248 safety inputs / 248 safety outputs |
Embedded ports | 1 × 10/100/1000 Mbps Ethernet; 1 × USB 2.0 (programming and diagnostics) |
Network capacity | Up to 250 EtherNet/IP devices |
Tasks and programs | 31 standard tasks + 1 safety task; up to 1,000 programs per task |
Max. I/O capacity | 128,000 digital and 4,000 analog points; 256 motion axes |
Nonvolatile storage | Embedded energy-storage module (battery-free); optional 2 GB SD card (1784-SD2) |
Backplane power | 1.2 A @ 5.1 V DC; 5 mA @ 1.2 V DC |
Power dissipation / heat | 6.2 W typical / 21.2 BTU·hr⁻¹ |
Isolation | 50 V continuous isolation between USB, Ethernet and backplane (basic insulation, 1000 V AC for 1 min) |
Installation | Single slot in any 1756-A4/A7/A10/A13/A17 ControlLogix chassis; RIUP supported |
Programming software | Studio 5000 Logix Designer v28 or later (safety functions require the appropriate license) |
Dimensions / weight | 50.8 × 177.8 × 233.68 mm (W × H × D); approx. 0.57 kg |
Operating temperature | 0 to +60 °C (32 to 140 °F) |
Certifications | CE, UKCA, CCC, ATEX, IECEx, RCM, EAC, ABS (marine), ODVA, and others |
Lifecycle status | Active (repairable / replaceable) |
Q1: What is the difference between the 1756-L84ES and the 1756-L84E?
Both share the same hardware platform (ControlLogix 5580, 20 MB user memory, one Gigabit Ethernet port, 256 axes). The difference is that the L84ES adds 6 MB of dedicated safety memory and safety functionality for SIL 3 / PL e safety logic, while the L84E is a standard-only controller. Choose the L84ES whenever the project involves emergency stops, safety doors, light curtains or similar safety circuits.
Q2: Do I still need a separate safety partner module as with the older GuardLogix 5570?
No. GuardLogix 5580 integrates safety into a single controller, so no additional 1756-L7SP safety partner is required. This saves a chassis slot and simplifies spare-parts management — one of the main benefits of migrating from 5570 to 5580.
Q3: Must the safety I/O be Rockwell-specific modules?
Safety signals are transmitted via CIP Safety over EtherNet/IP, so Rockwell Guard I/O distributed safety modules (such as 1732ES and 1791ES) as well as third-party CIP Safety devices can be used. Safety devices must establish a trusted connection with the controller through the Safety Network Number (SNN).
Q4: How many safety and standard I/O points can it handle?
Up to 248 safety inputs / 248 safety outputs on the safety side; up to 128,000 digital and 4,000 analog points on the standard side, plus 256 motion axes and 250 EtherNet/IP devices. Actual capacity also depends on network load and scan time — verify with Studio 5000 and the Integrated Architecture tools.
Q5: Which chassis can it be used in? Is a new chassis required?
It fits any standard 1756-A4/A7/A10/A13/A17 ControlLogix chassis and occupies one slot — no special chassis or mechanical modification is needed. When upgrading from ControlLogix 5570, the existing chassis and most I/O modules can usually be reused, but firmware and Studio 5000 version compatibility should be verified.
Q6: How is the program stored? Is it lost on power failure?
The controller includes an embedded energy-storage module and requires no battery, so the program is retained through power loss. For long-term archiving or fast controller replacement, add a 2 GB SD card (1784-SD2) and store the program and firmware on it — insert the card in the replacement controller to restore.
Q7: Which languages can be used for safety programming, and what are the modification restrictions?
The safety task supports Ladder Diagram (LD) only, while standard tasks support LD, FBD, ST, SFC and more. Safety logic is protected by the Safety Signature and Safety Lock: any modification generates a new signature and requires re-validation, ensuring compliance with functional safety audits.
Q8: Can it be used in a redundant or hot-standby configuration?
This model is positioned as a standalone safety controller. Where extremely high availability is required, redundancy can be applied at the standard control layer of the ControlLogix 5580 platform, and availability improved with DLR ring topologies and dual-port safety I/O. Because combining safety with redundancy has architectural constraints, please confirm the specific solution with us during the selection phase.