6ES7407-0DA02-0AA0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The UC-type input accepts 120 V or 230 V AC (47–63 Hz) as well as 120/230 V DC directly — no jumpers or manual switching required — making the module plug-and-play across global voltage standards. Inrush current is limited to 8.25 A (5 ms half-value width) and the low leakage current of 3.5 mA ensures safe installation. The 5 V output delivers up to 4 A for the backplane bus and runs stably at no load — no base load required; the 24 V output (max. 0.5 A, idling-proof) supplies interface modules requiring 24 V. Both outputs are short-circuit protected. Typical active power input is 52 W with only 20 W power loss, offering good efficiency. An optional 3.6 V lithium AA battery (2.2 Ah) backs up CPU data during power failure, and four LEDs (MAINS, DC5V, DC24V, INTF) indicate supply and fault status in real time. Primary/secondary potential separation, 2 rack slots and industrial 0 to +60 °C operation complete the profile.
Fully compatible with 120/230 V AC and DC — automatically adapts to global voltage standards, no jumpers needed.
5 V DC/4 A backplane supply with no base load required — perfect for lightly configured racks.
5 V DC/4 A + 24 V DC/0.5 A, both short-circuit protected and safe under no-load conditions.
20 ms stored-energy time per NAMUR recommendation, riding through momentary grid dips.
Optional 1 × 3.6 V lithium battery (2.2 Ah) backs up CPU data during power failure.
Primary/secondary separation, 4 status LEDs, industrial EMC compliance.
Product type | SIMATIC S7-400 power supply PS407, 4 A, UC wide range |
|---|---|
Supply voltage | 120 V AC / 230 V AC; 120 V DC / 230 V DC (universal UC) |
Line frequency | 50/60 Hz (range 47–63 Hz) |
Input current | 0.42 A at 120 V AC; 0.22 A at 230 V AC; 0.35 A at 120 V DC; 0.19 A at 230 V DC |
Inrush current | Max. 8.25 A (half-value width 5 ms); leakage current max. 3.5 mA |
Mains buffering | Stored-energy time 20 ms, per NAMUR recommendation |
Output voltage/current | Backplane bus 5 V DC max. 4 A (no base load required); 24 V DC max. 0.5 A (idling-proof) |
Protection | Output short-circuit protection; primary/secondary potential separation |
Power | Typ. active power input 52 W; typ. power loss 20 W |
Backup battery | Optional 1 × lithium AA, 3.6 V / 2.2 Ah (ordered separately) |
Status indication | LEDs: MAINS, DC5V, DC24V, INTF (internal fault) |
Mounting | S7-400 rack power slot, occupies 2 slots |
Ambient conditions | Operating temperature 0 to +60 °C (S7-400 rack environment) |
Dimensions / weight | Standard 2-slot form factor; net weight approx. 0.76 kg |
Q1: What is the difference between PS407 and PS405?
Both are S7-400 system power supplies; the difference is the input type. PS407 accepts 120/230 V AC or DC (universal UC), suited to mains networks; PS405 accepts 24/48/60 V DC for DC control networks. Choose according to the available power network on site.
Q2: How do I choose between the 4 A, 10 A and 20 A versions?
Total the 5 V backplane current of all rack modules and add 20–30% margin. This 4 A version (0DA02) suits small configurations with a CPU and a few modules; the 10 A version is 0KA02 and the 20 A version is 0RA02. Always verify the current rating when ordering to avoid mix-ups.
Q3: What do the 5 V and 24 V outputs power?
The 5 V DC/4 A output powers all rack modules via the backplane bus; the 24 V DC/0.5 A output can supply interface modules that require 24 V. External loads (solenoids, lamps, etc.) should use a separate supply to avoid tripping the 24 V output protection.
Q4: Is a base load required for no-load operation?
No. Both the 5 V and 24 V outputs run stably at no load (idling-proof); no load resistors are needed during commissioning or light-load operation.
Q5: What does a flashing 24 V LED mean?
A flashing green 24 V LED indicates overload or short circuit on the 24 V output: verify that the total 24 V load does not exceed 0.5 A and disconnect loads one by one to locate the fault. Persistent overload can damage the module and should be corrected promptly.
Q6: What does the backup battery do?
The optional 3.6 V lithium battery preserves CPU memory data and the real-time clock during power failure. Batteries are ordered separately; the panel LED indicates status, and periodic replacement per the manual is recommended.
Q7: Can it be used in a redundant power configuration?
Yes. The S7-400 rack can host two power supplies for power redundancy; for redundant configurations, the dedicated redundant version (e.g. PS407 10 A redundant, 0KR02) or a dual-supply setup per the project manual is recommended.
Q8: Does the input need manual switching between 120 V and 230 V?
No. The universal UC input automatically handles 120/230 V AC and 120/230 V DC, covering the main voltage standards worldwide — especially convenient for exported equipment and multi-country projects, with no jumpers or settings required.