6ES7414-3XM05-0AB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The CPU occupies a single slot in a standard S7-400 UR rack (50 mm wide) and is powered via the backplane bus (typical 6 W). X1 is a MPI/DP combo interface at 12 Mbit/s supporting up to 32 stations in DP master/slave mode; X5 is an integrated PROFINET interface acting as IO controller for Ethernet HMIs, remote I/O and supervisory systems; the built-in second DP interface enables an independent DP network without IF964-DP, and the IF slot can add a further DP link. The CPU supports CiR (Configuration in RUN) for reconfiguration without downtime, isochronous operation, S7 communication, PG/OP communication and HMI services. Load memory expands to 64 MB via RAM/FEPROM memory cards, and the hardware real-time clock provides a unified time base for plant-wide synchronization and fault tracing. Engineering is performed with STEP 7 V5.4 SP5 or higher.
2.8 MB work memory; 45 ns bit/word/fixed-point and 135 ns floating-point execution for complex logic and process control.
MPI/DP + PROFINET + built-in second DP interface, plus an IF slot — rare single-CPU multi-network capability.
Up to 131,072 digital / 81,932 analog points, easily building large distributed systems with DP slaves.
Configuration changes without downtime and precise synchronized operation for high-availability lines.
512 KB onboard RAM, load memory expandable to 64 MB by card, 2048 timers and 2048 counters.
Diagnostic buffer and real-time clock on board, 0 to +60 °C operation, CE/UL/cULus/FM, IEC 61131-2 compliant.
Product type | SIMATIC S7-400 CPU 414-3 PN/DP central processing unit |
|---|---|
Work memory | 2.8 MB RAM (1.4 MB program + 1.4 MB data) |
Load memory | 512 KB onboard RAM; expandable to 64 MB via RAM/FEPROM memory card |
Execution speed | Bit 45 ns / word 45 ns / fixed-point 45 ns / floating-point 135 ns |
Interfaces | X1: MPI/DP combo (12 Mbit/s, DP master/slave, up to 32 stations); X5: PROFINET IO (integrated Ethernet); built-in second DP interface; 1 × IF slot (IF964-DP optional) |
I/O expansion | Max. 131,072 digital / 81,932 analog points |
Timers / counters | 2048 each (timer range 10 ms to 9990 s) |
System functions | CiR, isochronous mode, S7 communication, PG/OP communication, HMI services, diagnostic buffer, real-time clock |
Engineering | STEP 7 V5.4 SP5 or higher (firmware V5.3) |
Power supply | Via S7-400 backplane bus; 5 V DC typ. 1.2 A (max. 1.4 A), 24 V DC max. 300 mA; typ. 6 W |
Mounting | Single slot in S7-400 UR rack; IP20 (control cabinet installation only) |
Ambient conditions | Operating 0 to +60 °C; storage −40 to +85 °C; humidity 5–95% non-condensing; pollution degree 2 |
Dimensions / weight | 50 × 290 × 219 mm (W×H×D); approx. 1 kg |
Certifications | CE, UL/cULus, FM; compliant with IEC 61131-2 |
Q1: What applications is the CPU 414-3 PN/DP suitable for?
Medium and large complex automation systems: power plant auxiliary control, metallurgical rolling lines, chemical process control, pulp & paper and large packaging lines — wherever large program capacity, fast processing and parallel networks are required.
Q2: Which communication interfaces does it have and what do they do?
Three integrated interfaces plus one expansion slot: X1 is the MPI/DP combo port (DP master/slave, MPI networking, PG/OP connections); X5 is the PROFINET interface (IO controller, Ethernet HMI and supervisory systems); the built-in second DP interface joins another independent DP network; the IF slot accepts an IF964-DP for additional DP links.
Q3: How much I/O can it handle?
Up to 131,072 digital and 81,932 analog points; combined with ET 200 distributed slaves, it covers extremely large systems.
Q4: What is CiR (Configuration in RUN)?
CiR allows hardware configuration changes (e.g. adding/removing DP slaves, adjusting parameters) while the system keeps running, without a restart — essential for continuous production that cannot tolerate interruption.
Q5: What if program memory is not enough?
Beyond the 512 KB onboard load memory, RAM or FEPROM (flash) memory cards can be inserted to expand load memory up to 64 MB for very large programs and data logging.
Q6: Which software is used for engineering?
Classic STEP 7 (V5.4 SP5 or higher) with LAD/FBD/STL languages, compatible with S7-PLCSIM simulation and STEP 7 Professional engineering workflows.
Q7: What is the supply status of this model?
This model has entered the phase-out transition stage of the Siemens product lifecycle and is mainly supplied for maintenance and spare-part replacement of existing S7-400 systems. For new projects, consider migrating to S7-1500. Please contact us to confirm stock and lead time before ordering.
Q8: What are the installation and environmental requirements?
Mounted in a single slot of an S7-400 UR rack, IP20 rated and intended for control cabinet installation only; operating temperature 0 to +60 °C, powered via the rack backplane bus with no separate power wiring required.