6ES7305-1BA80-0AA0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The input is a wide-range DC design rated 24/48/72/96/110 V DC and accepting 16.8–138 V DC, with a short-time overvoltage capability of 154 V DC for 0.1 s. Corresponding input currents are approx. 2.7 A at 24 V, 1.3 A at 48 V, 0.9 A at 72 V, 0.65 A at 96 V and 0.6 A at 110 V, so the upstream supply and conductor cross-sections must be sized for the actual input voltage. Inrush current is limited to 20 A (at 25 °C, limiting duration 10 ms, I²t approx. 5 A²s). An internal T 6.3 A/250 V fuse (not accessible) protects the input; an upstream DC-rated miniature circuit breaker of 10 A characteristic C is recommended.
The output is a controlled, galvanically isolated 24 V DC, rated 2 A with ±3% tolerance and stable at no load. When the input voltage is above 24 V (24–138 V DC), the output capability rises to 3 A, leaving headroom for expansion. A soft-start design prevents overshoot at power-up (ramp-up time max. 3 s), and residual ripple is max. 150 mV (typically 30 mV), providing clean power for the PLC and analog loops. Protection is comprehensive: output current limiting at 3.3–3.9 A, electronic non-latching short-circuit shutdown with automatic recovery, short-term overload of approx. 9 A for about 270 ms, and output overvoltage shutdown at approx. 30 V with automatic restart.
Power-failure buffering exceeds 10 ms at rated input and rated load (minimum repeat interval 1 s), riding through short input dips without stopping the CPU or losing data. Efficiency is approx. 75% with a typical power loss of 16 W, and MTBF at 40 °C is approximately 964,500 hours. Input and output are safely isolated (rated 150 V AC, tested at 2800 V DC) and the output meets SELV requirements. The unit is protection class I and must be connected to a reliable protective conductor; leakage current is max. 3.5 mA (typically 0.7 mA), degree of protection IP20, EMC designed to EN 55011 Class A emissions and EN 61000-6-2 immunity. A green "24 V OK" LED indicates a healthy output. Connection is via screw terminals (L+1/M1 input, L+2/M2 output, 0.5–2.5 mm²). Cooling is natural convection without a fan; dimensions are 80 × 125 × 120 mm, weight approx. 0.74 kg, with 50 mm clearance required above and below.
Effective 16.8–138 V DC, covering 24/48/72/96/110 V nominal levels with no selector switch.
Approx. 48 W, ±3% accuracy, ripple ≤150 mV; up to 3 A when input is above 24 V.
Climate class 3K5 with transient condensation permitted — for outdoor cabinets, rail and marine use.
Current limiting 3.3–3.9 A, electronic shutdown with auto-restart, ~30 V overvoltage trip.
Maintains output through short input dips, preventing CPU stops; repeat interval min. 1 s.
2800 V DC dielectric test, class I, IP20, approx. 964,500 h MTBF at 40 °C.
Product type | SIMATIC S7-300 regulated power supply PS305, 2 A, DC input, outdoor version |
|---|---|
Input voltage (rated) | DC 24 / 48 / 72 / 96 / 110 V (wide-range input, no selector switch) |
Input voltage range | DC 16.8–138 V; short-time overvoltage 154 V DC for 0.1 s |
Input current | Approx. 2.7 A @24 V; 1.3 A @48 V; 0.9 A @72 V; 0.65 A @96 V; 0.6 A @110 V |
Inrush current | Max. 20 A at 25 °C, limiting duration 10 ms, I²t approx. 5 A²s |
Input protection | Internal T 6.3 A/250 V fuse (not accessible); upstream DC-rated 10 A char. C MCB recommended |
Output voltage | DC 24 V ±3% (stable at no load, fixed output) |
Output current / power | Rated 2 A (0–2 A), approx. 48 W; 3 A permissible when input is >24 V (24–138 V DC) |
Residual ripple | Max. 150 mV (typically 30 mV) |
Regulation | 0.2% for slow input change; 0.4% for slow load change; load-step recovery typ. 2.5 ms (max. 5 ms) |
Overload & short circuit | Current limiting 3.3–3.9 A; electronic non-latching shutdown with auto-restart; approx. 9 A short-time (about 270 ms) |
Overvoltage protection | Shutdown at approx. 30 V with automatic restart |
Power-failure buffering | >10 ms at rated input and load; repeat interval min. 1 s |
Efficiency / loss | Approx. 75% / typically 16 W (power input approx. 64 W) |
Isolation | Input–output isolation, rated 150 V AC, tested at 2800 V DC; SELV output |
Protection rating | Class I (protective conductor required); leakage current ≤3.5 mA (typ. 0.7 mA); IP20 |
Status indication | Green LED: lit when 24 V output is OK |
Connection & mounting | Screw terminals L+1/M1 (input) and L+2/M2 (output), 0.5–2.5 mm²; slot 1 on S7-300 rail; 50 mm clearance top and bottom |
Ambient conditions | Operation −25 to +70 °C; storage/transport −40 to +85 °C; climate class 3K5 (IEC 60721, transient condensation permitted) |
Dimensions / weight | W 80 × H 125 × D 120 mm; approx. 0.74 kg |
MTBF | Approx. 964,500 h at 40 °C |
EMC | Emissions EN 55011 Class A; immunity EN 61000-6-2 |
Lifecycle | Phased out since 2023-10-01 (PM400); supplied mainly as stock / spare part |
Q1: PS305 or PS307 — which one do I need?
The decisive difference is the input supply type: the PS305 has a DC input (24–110 V DC wide range) and delivers 24 V DC/2 A (48 W); the PS307 has a single-phase AC input (120/230 V AC) and delivers 5 A or 10 A. Choose PS307 when only AC mains is available in the cabinet; choose PS305 when the cabinet is already fed from a DC bus (24/48/110 V DC) or when the S7-300 rack supply must be generated inside a DC system.
Q2: What is the difference between 1BA80 (outdoor) and 1BA10 (standard)?
Electrical ratings are identical; the difference is environmental capability. The 1BA80 is the outdoor wide-temperature version rated −25 to +70 °C, climate class 3K5 with transient condensation permitted; the standard 1BA10 is rated 0 to +60 °C for indoor use. Select 1BA80 for outdoor cabinets, rolling stock, marine or sheltered outdoor enclosures.
Q3: Is 2 A enough? When can I draw 3 A?
2 A suits a small-to-medium rack (CPU plus a few signal modules) and can supply some sensors. Note that when the input voltage is above 24 V (24–138 V DC), the output capability increases to 3 A; with a 24 V DC input, plan on 2 A, and remember the input current is then approx. 2.7 A, so the upstream 24 V supply and cabling need that margin. If the rack demand approaches or exceeds 2 A, move to a higher-capacity supply concept.
Q4: Can it power external sensors and transmitters?
Yes, the PS305 can be used as a load power supply. However, the 2 A is shared with the backplane load — limit external loads to roughly 50–60% of the rating and verify protection coordination. For heavier external loads or where independent disconnection is required, use a separate 24 V supply.
Q5: Can units be paralleled for more power or redundancy?
Up to 2 identical units may be paralleled to increase output power, but this is not a redundant configuration — a single failure still interrupts the output. For true redundancy, use decoupling diode modules or a dedicated redundant power supply solution.
Q6: Is additional fusing required on the DC input?
The module contains a T 6.3 A/250 V fuse that is not accessible from outside. In practice, install a DC-rated 10 A characteristic C miniature circuit breaker on the incoming line for disconnection and cable protection. Observe DC polarity (L+ / M) and the protective conductor, and always use a breaker approved for DC — an AC breaker is not a substitute.
Q7: What are the mounting and clearance requirements?
Mount the module in slot 1 at the far left of the S7-300 rail; it feeds the following modules via the backplane bus bars. Leave 50 mm clearance above and below; the left and right sides may be mounted flush. For installation on a standard 35 mm DIN rail, the mounting adapter 6ES7390-6BA00-0AA0 is required. Cooling is natural convection without a fan — check the internal temperature rise when mounted in a sealed enclosure.
Q8: The model is phased out — can I still buy it, and what replaces it?
Yes. We supply stock units and tested refurbished spare parts and support exchange/repair services; for batch projects please confirm stock and lead time in advance. Alternatives: for indoor applications the standard 1BA10 can be evaluated (also in phase-out, stock to be confirmed); for system upgrades migrate to S7-1200 / S7-1500; and if the task is simply converting a DC bus into a 24 V control supply, a SITOP DC-input supply / DC-DC converter is a viable route — we can help match power rating and mounting space.