1756-EN2T
AB
| Availability: | |
|---|---|
| Quantity: | |
The module occupies one slot and can be placed in any position in the ControlLogix chassis, exchanging data with the controller over the backplane. Front-panel LEDs indicate network status, module status and activity, making link and connection health easy to assess. Communication capacity: 128 TCP connections, 256 CIP connections (explicit and implicit I/O connections in any combination), 128 + 128 CIP unconnected messages (backplane + Ethernet) and up to 32 produced/consumed tags. Packet handling reaches approximately 10,000 I/O packets per second and 3,200 HMI/MSG packets per second — enough for real-time I/O and HMI traffic in a mid-size chassis. The module also supports integrated motion over EtherNet/IP (up to 8 axes; the actual number depends on controller and firmware). Power is drawn from the backplane: 1 A at 5.1 V DC and 3 mA at 24 V DC, with 5.1 W power dissipation and 17.4 BTU/hr heat load, placing little demand on the chassis supply. Isolation between the Ethernet port, USB port and backplane is 30 V continuous basic insulation (type tested at 980 V AC for 60 s). Operating temperature is 0–60 °C, radiated emissions meet CISPR 11 Class A, vibration resistance is 2 G (10–500 Hz) and shock resistance 30 G; the open-style housing must be mounted inside a control cabinet. Electronic Keying with the "Compatible Module" setting allows the module to replace an older 1756-ENBT without program changes.
Twice the connection capacity of the 1756-ENBT — more I/O devices, HMIs and host systems at once.
One auto-sensing 10/100 Mbps RJ45 port on standard twisted-pair cabling, compatible with existing infrastructure.
One slot, installable in any ControlLogix chassis position for easy wiring zones and expansion.
One network carries real-time I/O, HMI/SCADA messaging and program downloads — no second network needed.
Routes messages between EtherNet/IP subnets for cross-subnet device access.
Electronic Keying and a USB port allow direct replacement of a 1756-ENBT, protecting existing investment.
Product type | ControlLogix EtherNet/IP communication (bridge) module, single copper port |
|---|---|
Catalog No. / UPC | 1756-EN2T / 612598329106 |
Communication rate | 10 / 100 Mbps auto-sensing |
Ethernet port | 1 × RJ45 (Category 5 shielded or unshielded twisted pair, 802.3 compliant) |
USB port | 1 × USB (full speed 12 Mbps, programming/temporary configuration only) |
TCP connections | 128 max. |
CIP connections | 256 max. (any combination of explicit or implicit I/O connections) |
CIP unconnected messages | 128 + 128 (backplane + Ethernet) |
Produced/consumed tags | Up to 32 |
Packet rate | Approx. 10,000 I/O packets/s; approx. 3,200 HMI/MSG packets/s |
Integrated motion | Integrated motion over EtherNet/IP (up to 8 axes, depending on controller and firmware) |
Backplane current | 1 A @ 5.1 V DC; 3 mA @ 24 V DC |
Power dissipation / heat | 5.1 W / 17.4 BTU·hr⁻¹ |
Isolation | 30 V continuous basic insulation (Ethernet/USB to backplane); type tested at 980 V AC for 60 s |
Mounting | Any ControlLogix chassis slot, 1 slot wide; open style (IP20, cabinet required) |
Dimensions / weight | Approx. 85 × 30 × 111 mm; approx. 0.26 kg |
Environment | Operating 0 to +60 °C; storage −40 to +85 °C; humidity 5%–95% non-condensing; vibration 2 G (10–500 Hz); shock 30 G |
EMC | CISPR 11 Class A emissions; ESD 6 kV contact / 8 kV air; EFT ±3 kV at 5 kHz on Ethernet ports; surge ±2 kV line-to-earth |
Certifications | CE, c-UL-us, ATEX (T4), IECEx, RCM, EAC, KC, marine class approvals, among others — see product label |
Lifecycle status | Active (repairable / replaceable) |
Q1: How do I choose between the 1756-EN2T, 1756-EN2TR and 1756-EN3TR?
They serve different needs: the EN2T is a single-port 100 Mbps module for conventional star/linear networks; the EN2TR has two 100 Mbps ports and supports Device Level Ring (DLR), acting as a ring node or ring supervisor with self-healing on a single break; the EN3TR offers two 1 Gbps ports for high data volumes, many nodes or bandwidth-sensitive applications. Choose EN2TR/EN3TR for ring redundancy, and the EN2T for ordinary connections at lower cost.
Q2: Can it directly replace an older 1756-ENBT?
Yes. With Electronic Keying set to Compatible Module (or Disabled), the 1756-EN2T drops into the original slot as a replacement for the 1756-ENBT. Reconfigure the IP address (or set it quickly with the DIP switches) and the program usually needs no changes. Record the original IP, subnet and connection plan before swapping.
Q3: What do the 128 TCP / 256 CIP connections mean? Will that be enough?
TCP connections are used mainly for explicit traffic such as HMIs, programming software and MSG instructions; CIP connections carry I/O and explicit/implicit data, with 256 available for flexible allocation between I/O and messaging. A mid-size chassis (10–20 remote I/O stations, several drives, 2–3 HMIs) typically uses a few dozen connections, leaving ample headroom; large systems can distribute load across multiple communication modules. Keep at least 20% spare capacity when planning.
Q4: Can a single-port module form a DLR ring?
No. DLR ring nodes require two Ethernet ports, and the 1756-EN2T has only one, so it cannot act as a ring node or ring supervisor. For ring redundancy, use the dual-port 1756-EN2TR or 1756-EN3TR.
Q5: Can it be used in a redundant (hot-standby) system?
No. ControlLogix redundancy requires redundancy-capable communication modules (1756-EN2TR / 1756-EN3TR) used in pairs together with a redundancy module such as the 1756-RM2. The 1756-EN2T is a single-port standard module intended for non-redundant systems.
Q6: Does it support motion control, and how are axes counted?
It can carry integrated motion traffic over EtherNet/IP, with up to 8 motion axes at module level. The usable axis count in a system depends on the controller model, firmware revision and licensing (for example, a ControlLogix 5580 controller supports far more than 8 axes overall, but communication module and network planning factor in). For multi-axis, high-dynamics applications, perform a network load assessment.
Q7: What is the USB port for? Can I run production traffic over USB?
The USB port is full-speed 12 Mbps and is intended for first-time configuration, temporary program upload/download and on-site commissioning (it connects even without knowing the IP address). It is not suitable for continuous production data traffic — use the Ethernet port for that and disconnect the USB cable after commissioning.
Q8: Does the module need separate power or configuration software?
No separate supply is needed; the module is powered from the chassis backplane (1 A @ 5.1 V DC). Configuration is done in Studio 5000 Logix Designer by adding the module to a chassis slot and setting its IP address, which can also be set quickly with the on-board DIP switches. Firmware can be updated with ControlFLASH or Studio 5000; keep it matched to the controller firmware revision.