6ES7322-1HH01-0AA0

The 6ES7322-1HH01-0AA0 is a SIMATIC S7-300 SM 322 relay output module featuring 16 digital outputs. Each output is a relay contact rated for 120V DC or 230V AC at 2A, providing true dry-contact switching for both AC and DC loads.

With channels isolated in groups of 8, this module is ideal for applications requiring dense, flexible switching of solenoid valves, contactors, small motors, and signal lamps. The relay outputs require no additional interposing relays for most standard loads, simplifying panel design.

Note: This model is currently listed as a spare part by Siemens. Every unit is 100% tested before dispatch.
  • 6ES7322-1HH01-0AA0

  • Siemens

Availability:
Quantity:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
sharethis sharing button
The 6ES7322-1HH01-0AA0 is a relay output module from the SIMATIC S7-300 family, providing 16 digital outputs for flexible switching of AC and DC loads. Each relay contact is rated at 2A, with load voltage up to 120V DC or 230V AC.

The outputs are isolated in groups of 8, with galvanic isolation between channels and the backplane bus via optocoupler. This module does not include built-in short-circuit protection, so external fusing is recommended for load protection.

The module requires a 20-pin front connector and is compatible with standard S7-300 mounting rails. It is well-suited for driving solenoid valves, contactors, small-power motors, lamps, and motor starters.

Important Note: This model is now listed as a spare part by Siemens. We guarantee 100% functional testing before shipping to ensure reliable operation in your existing S7-300 system.
 16 Relay Outputs: High-density dry-contact switching for AC and DC loads.
• Wide Voltage Range: 120V DC and 230V AC rated load voltage.
• 2A per Point: Handles solenoids, contactors, small motors, and lamps directly.
• Group Isolation: Channels isolated in groups of 8 for flexible wiring.
• Relay Technology: True dry contacts with no leakage current.
• 100% Tested: Every module undergoes rigorous testing before dispatch.
• Ready to Ship: Stock available for fast global delivery.
General Information:
• Product Type: SM 322, DO 16 x Relay
• Number of Outputs: 16 (relay contacts)
• Isolation: Channels isolated in groups of 8; channels to backplane bus via optocoupler

Load Voltage:
• L+ (DC) Rated: 120V DC
• L1 (AC) Rated: 230V AC

Output Current:
• Rated (signal "1"): 2A per point
• Minimum Load Current: 10 mA
• Total Current per Group (horizontal, up to 60°C): Max. 8A
• Total Current per Group (vertical, up to 40°C): Max. 8A

Switching Capacity:
• Lamp Load (230V AC): Max. 50 W
• Switching Frequency (Resistive): Max. 1 Hz
• Switching Frequency (Inductive): Max. 0.5 Hz
• Mechanical Switching Frequency: Max. 10 Hz

Relay Data:
• Relay Coil Voltage L+ (DC): 24V
• Contact Connection (internal): No (dry contact)
• Operating Cycles: 100,000 (general); 50,000 (24V DC, 2A); 700,000 (120V AC, 2A); 100,000 (230V AC, 2A)

Power & Current Consumption:
• Input Current from L+ (max): 250 mA
• Input Current from Backplane Bus 5V DC (max): 100 mA
• Power Loss (typ.): 4.5 W

Mechanical Data:
• Dimensions (W x H x D): 40 x 125 x 120 mm
• Weight (approx.): 250 g
• Required Front Connector: 20-pin

Environmental:
• Operating Temperature (horizontal): 0°C to 60°C
• Protection Class: IP20
• Isolation Tested With: 1500V AC
Q: Can this module switch both AC and DC loads?
A: Yes. The relay outputs support up to 120V DC and 230V AC, making it suitable for mixed load types.

Q: What is the difference between this module and the 8-output relay module (1HF10)?
A: This module provides 16 outputs at 2A per point, while the 1HF10 provides 8 outputs at 5A per point. Choose based on your required output count and current rating.

Q: Is short-circuit protection built in?
A: No. External fusing is recommended. The relay contacts do not provide electronic short-circuit protection.

Q: What front connector is required?
A: This module requires a 20-pin front connector.

Q: Is this product new and tested?
A: Yes. We supply tested units that are 100% functionally verified before dispatch. Contact us for current stock and shipping rates.
Previous: 
Next: 

PRODUCTS

PRODUCTS

QUICK LINKS

CONTACT

+86-176-2073-4453
No. 858 Dujuan Road, Wangyue Subdistrict, Hunan Xiangjiang New Area,China
© 2026 Hunan Dream Road Electrical Technology Co., Ltd. All Rights Reserved. 
Privacy Policy            Sitemap