The 6ES7223-1HF22-0XA8 (EM223 CN) is a digital input/output combination expansion module of the Siemens SIMATIC S7-200 CN family, integrating 8 DC 24V digital inputs and 8 relay outputs to extend both the input and output capacity of the CPU at once. One module covers applications where both I and O are short, and it is widely used for I/O expansion in machine tools, packaging machinery, building control, water treatment and other small and medium-sized automation systems.
  • 6ES7223-1HF22-0XA8

  • Siemens

Availability:
Quantity:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
sharethis sharing button

The EM223 CN connects directly to the S7-200 CN CPU or the previous expansion module via the backplane bus. It is automatically recognized with I/O addresses assigned, requires no separate configuration, and simply snaps onto a standard DIN rail. The 8 inputs are DC 24V type with optical isolation, suitable for standard switching signals such as pushbuttons, proximity switches and sensor outputs; the 8 relay outputs handle up to 2 A per point and can directly drive AC contactors, solenoid valves, indicator lamps and other AC or DC loads.

The outputs are arranged in 2 groups of 4 points, each group with its own common terminal, making it easy to isolate different voltage levels or power circuits. Status LEDs on all input and output channels make commissioning and troubleshooting quick and intuitive. Compact and mounted side by side with the CPU, it is one of the most cost-effective I/O expansion options for an S7-200 CN system.

  • Mixed I/O design: one module expands 8 inputs + 8 outputs simultaneously, saving expansion slots and cost.

  • Versatile relay outputs: up to 2 A per point, directly switching AC or DC loads (contactors, solenoid valves, lamps, etc.).

  • Optical isolation: inputs isolated from internal circuits for strong noise immunity and higher reliability.

  • Grouped outputs: 8 outputs in 2 groups × 4 points with separate commons, convenient for isolating different power circuits.

  • Plug and play: connects directly to the CPU via the backplane bus; I/O addresses assigned automatically, no configuration needed.

  • LED status indication: LEDs on all I/O channels make debugging and maintenance clear at a glance.

Part Number

6ES7223-1HF22-0XA8 (EM223 CN, 8 DI / 8 DO relay)

Module Type

S7-200 CN digital input/output combination expansion module

Inputs

8 digital inputs (DC 24V)

Outputs

8 relay outputs, max. 2 A per point (resistive load)

Input / Output Groups

Inputs: 8 points, one common; outputs: 2 groups × 4 points, each with its own common

Electrical Isolation

Optical isolation (inputs and outputs isolated from internal circuits)

Power Supply

Supplied by the CPU via the backplane bus (5V DC)

Dimensions

Approx. 46 mm × 80 mm × 62 mm

Mounting

Standard DIN rail

Protection / Operating Temperature

IP20; 0–55 °C (horizontal mounting)

Status Indication

LED indicators on input / output channels

Compatible CPUs

S7-200 CN series: CPU 221 / 222 / 224 / 224 XP / 226

Q1: Are the EM223 outputs relay or transistor type? Can they switch AC loads?

A: This model (suffix HF22) has relay outputs rated 2 A per point and can directly switch AC loads (e.g. AC 220V contactors) as well as DC loads. For transistor outputs (DC 24V, fast response, no contact wear), choose the transistor-type EM223 module.

Q2: What type are the inputs? Can they accept 220V signals directly?

A: The inputs on this module are DC 24V type and cannot accept 220V AC signals directly. If only 220V switching signals are available on site, convert them via interposing relays, or choose an AC-input expansion module.

Q3: Which CPUs can it be used with, and how many modules can be connected?

A: It works with all S7-200 CN CPUs (CPU 221 / 222 / 224 / 224 XP / 226). Each CPU supports up to 7 expansion modules; the total I/O must stay within the CPU limits, and the 5V DC backplane power budget must be verified.

Q4: Does the module need configuration? How are I/O addresses assigned?

A: No. The system detects the module automatically once connected via the expansion cable; input and output addresses are assigned in the order of connection and can be referenced directly in STEP 7-Micro/WIN.

Q5: How long do the relay outputs last? What should I watch out for?

A: Relays are mechanical contacts suited to low-to-medium switching frequencies. When driving inductive loads such as solenoid valves and contactors, add surge suppression (RC network or flyback diode) across the loads, and avoid exceeding the 2 A per-point rating and the group total current to extend contact life.