1772989321@qq.com    +86-17620734453
English

Product Detail

Home » Products » 6ES7214-2AS23-0XB8

Product Category

Contact Us

6ES7214-2AS23-0XB8

The 6ES7214-2AS23-0XB8 is the CPU 224XP CN main controller of the Siemens SIMATIC S7-200 CN family (AC powered, AC inputs, relay outputs). It integrates 14 AC digital inputs and 10 relay outputs onboard, plus 2 analog inputs and 1 analog output. The AC inputs accept 220V field signals such as pushbuttons, limit switches and selector switches directly — no additional 24V supply is needed, which simplifies wiring. It is widely used in machine tools, textile machinery, building services, water treatment and other small to medium-sized automation equipment.
  • 6ES7214-2AS23-0XB8

  • Siemens

Availability:
Quantity:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
sharethis sharing button

The CPU 224XP CN is the enhanced CPU of the S7-200 CN family. Building on the CPU 224 CN, it adds onboard analog channels, so 0–10V analog signals can be acquired and control signals output without any expansion module. This model uses AC 120/230V inputs that accept AC switching signals directly, giving strong noise immunity — ideally suited to equipment with predominantly 220V control circuits and electrically demanding environments.

The relay outputs handle up to 2 A per point and can directly drive AC contactors, solenoid valves and indicator lamps, whether AC or DC loads, offering excellent versatility. The module provides 2 RS485 ports for PPI communication with a programming PC and is programmed with STEP 7-Micro/WIN in LAD, FBD or STL. The CPU supports up to 7 expansion modules for flexible extension of digital I/O, analog functions and communication, and includes 2 analog potentiometers and a real-time clock onboard.

  • AC inputs, simple wiring: 14 × AC 120/230V inputs accept 220V pushbuttons and limit switches directly — no 24V auxiliary supply needed.

  • Relay outputs, highly versatile: 10 relay outputs rated 2 A per point, able to drive both AC and DC loads.

  • Onboard analog: 2 analog inputs (0–10V) + 1 analog output integrated, handling analog signals without expansion modules.

  • Scalable: connects up to 7 S7-200 CN expansion modules for flexible I/O and function extension.

  • Dual communication ports: 2 × RS485 ports for simultaneous connection to a programming device and an HMI/host system.

  • Easy programming: STEP 7-Micro/WIN software with LAD / FBD / STL and a rich instruction set.

Part Number

6ES7214-2AS23-0XB8 (CPU 224XP CN, AC/AC/Relay)

Power Supply

AC 120/230 V (permissible range 85–264 V AC)

Digital Inputs

14 AC inputs (AC 120/230V)

Digital Outputs

10 relay outputs, max. 2 A per point

Onboard Analog

2 analog inputs (0–10V) + 1 analog output (0–10V)

Program Memory

16 KB

High-Speed Functions

AC input + relay output type: high-speed counters (HSC) and pulse outputs (PTO/PWM) not supported

Communication Ports

2 × RS485 ports (PPI / freeport communication)

Expansion

Up to 7 expansion modules

Miscellaneous

2 analog potentiometers, real-time clock, DIN rail / panel mounting, IP20 protection

Programming Software

STEP 7-Micro/WIN

A: This model (suffix AS23) is AC powered with AC inputs and relay outputs — the "AC type" CPU: the 14 inputs accept AC 120/230V signals directly, and the 10 outputs are relay contacts that can switch both AC and DC loads.

Q2: How does it differ from the 6ES7214-2BD23-0XB0?

A: Both have the same I/O count (14 DI / 10 DO). The difference is the electrical type: the 2BD23 is DC 24V powered with DC inputs and transistor outputs, supporting high-speed counting and pulse outputs for motion control; this 2AS23 is AC powered with AC inputs and relay outputs — simpler wiring and more versatile, but without high-speed pulse outputs.

Q3: Can the AC inputs be connected directly to 220V pushbuttons and limit switches?

A: Yes. AC 120/230V inputs accept 220V control-circuit signals (pushbuttons, limit switches, proximity switches, etc.) directly with no separate 24V DC supply. Make sure the wiring of the input common (1M) and the signal voltage level are consistent.

Q4: What load can a relay output handle? Can it drive an AC contactor?

A: Each relay output is rated 2 A and can directly drive small AC contactors, solenoid valves and indicator lamps. For larger contactors or frequent switching, use an interposing relay and add surge suppression across inductive loads to extend contact life.

Q5: What signals can the onboard analog inputs accept?

A: The CPU has 2 onboard analog inputs for 0–10V voltage signals and can connect potentiometers, transmitters and other voltage sources. For 4–20mA current signals, use a precision sampling resistor or an analog expansion module.

Q6: How many expansion modules are supported, and which software is used?

A: Up to 7 S7-200 CN expansion modules, subject to the CPU's maximum I/O limits and the 5V DC expansion bus power budget. Programming uses STEP 7-Micro/WIN (V4.0 or later); connect via a USB/PPI cable or RS485 to the PPI port.

Previous: 
Next: 

PRODUCTS

PRODUCTS

QUICK LINKS

CONTACT

+86-176-2073-4453
No. 858 Dujuan Road, Wangyue Subdistrict, Hunan Xiangjiang New Area,China
© 2026 Hunan Dream Road Electrical Technology Co., Ltd. All Rights Reserved. 
Privacy Policy            Sitemap