6ES7322-1BL00-0AA0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The SM 322 digital output module 6ES7322-1BL00-0AA0 mounts on the S7-300 rail and connects to the backplane bus. It provides 32 source-type transistor outputs, arranged in 4 groups of 8 channels. Each group requires an external DC 24 V load voltage supply via the front 40-pin connector. The outputs are electrically isolated from the backplane bus and protected against short circuits. This module is widely used for high-density output control in S7-300 systems, including solenoid valve banks, relay coils, and pilot lamps. Hunan Dream Road Electrical Technology Co., Ltd. provides reliable spare parts for your maintenance needs.
32 digital outputs, DC 24 V / 0.5 A per channel
Source-type (PNP) transistor outputs, short-circuit protected
Optically isolated between channels and backplane bus
Organized in 4 groups of 8 outputs, each group independently powered
Status LED per channel for output indication
Suitable for solenoid valves, contactors, and indicator lights
40-pin front connector required (not included)
Parameter | Specification |
|---|---|
Article Number | 6ES7322-1BL00-0AA0 |
Product Series | SIMATIC S7-300 / SM 322 |
Number of Outputs | 32 |
Output Type | DC 24 V transistor (source) |
Rated Load Voltage (L+) | DC 24 V |
Permissible Load Voltage Range | 20.4–28.8 V DC |
Output Current per Channel (rated) | 0.5 A |
Output Current Range (signal “1”) | 5 mA to 0.6 A |
Short-Circuit Protection | Electronic, threshold typ. 1 A |
Output Groups | 4 groups of 8 outputs |
Total Current per Group (horizontal, ≤40 °C) | Max. 4 A |
Total Current per Group (horizontal, ≤60 °C) | Max. 3 A |
Isolation (channels to backplane) | 500 V DC |
Cable Length (unshielded) | Max. 600 m |
Cable Length (shielded) | Max. 1,000 m |
Power Loss (typ.) | 6.6 W |
Front Connector | 40-pin (not included) |
Dimensions (W×H×D) | 40 × 125 × 120 mm |
Q1: Does this module require a front connector?
A1: Yes. A 40-pin front connector (e.g., 6ES7392-1AM00-0AA0) is required for wiring. It is not included with the module.
Q2: How is the load voltage supplied to the outputs?
A2: The module has 4 output groups, each requiring an external DC 24 V load voltage (L+) and 0 V reference (M) connected via the front connector. Each group must be powered independently.
Q3: What type of output does this module use?
A3: It uses source-type (PNP) transistor outputs. The output provides +24 V when the signal is “1”. Do not connect outputs in parallel to increase current capacity.
Q4: How to contact the supplier for a quotation?
A4: Please contact Hunan Dream Road Electrical Technology Co., Ltd. at Tel: 17620734453 or Email: 1772989321@qq.com.