6GK7342-5DA03-0XE0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The CP 342-5 communication processor 6GK7342-5DA03-0XE0 mounts on the S7-300 rail and provides a single PROFIBUS DP interface via a 9-pin Sub-D socket (RS485). It enables the S7-300 CPU to communicate with PROFIBUS DP field devices, either as a DP master (up to 124 slaves) or as a DP slave. The module also supports open communication via SEND/RECEIVE blocks, S7 communication, and PG/OP functions. Configuration requires STEP 7 V5.1 SP2 or higher, or STEP 7 Professional V12 (TIA Portal) or higher. Hunan Dream Road Electrical Technology Co., Ltd. provides reliable spare parts for your maintenance needs.
Connects SIMATIC S7-300 to PROFIBUS DP networks
Supports DP master (up to 124 slaves) and DP slave operation
Transmission rate: 9.6 kbit/s to 12 Mbit/s
9-pin Sub-D socket (RS485) interface
S5-compatible, PG/OP and S7 communication
Up to 16 open communication connections via SEND/RECEIVE
Supports up to 4 CP modules per CPU
Parameter | Specification |
|---|---|
Article Number | 6GK7342-5DA03-0XE0 |
Product Series | SIMATIC NET / CP 342-5 |
Interface | 1x PROFIBUS DP, 9-pin Sub-D (RS485) |
Transmission Rate | 9.6 kbit/s to 12 Mbit/s |
Supply Voltage (external) | DC 24 V (±20% / -15%) |
Supply Voltage (backplane) | DC 5 V |
Current Consumption (backplane, typ.) | 0.15 A |
Current Consumption (external, typ.) | 0.25 A |
Power Loss (typ.) | 6.75 W |
DP Master Capability | Yes, up to 124 slaves |
DP Slave Capability | Yes |
Open Communication Connections | Max. 16 |
S7 Communication Connections | Max. 16 |
Modules per CPU | Max. 4 |
Operating Temperature | 0 °C to 60 °C |
Protection Class | IP20 |
Dimensions (W×H×D) | 40 × 125 × 120 mm |
Net Weight | Approx. 0.3 kg |
Q1: What is the function of the CP 342-5 module?
A1: The CP 342-5 is a communication processor that connects SIMATIC S7-300 PLC systems to PROFIBUS DP networks. It handles DP master/slave communication, S7 communication, and PG/OP functions.
Q2: What configuration software is required?
A2: STEP 7 V5.1 SP2 or higher, or STEP 7 Professional V12 (TIA Portal) or higher is required for configuration.
Q3: Can this module operate as both master and slave?
A3: Yes. The module supports DPV0 as both DP master (up to 124 slaves) and DP slave.
Q4: How to contact the supplier for a quotation?
A4: Please contact Hunan Dream Road Electrical Technology Co., Ltd. at Tel: 17620734453 or Email: 1772989321@qq.com.