6ES7307-1KA02-0AA0
| Availability: | |
|---|---|
| Quantity: | |
The PS307 power supply module mounts directly in slot 1 of the S7-300 rail. It supplies operating voltage to the CPU and downstream modules via the backplane bus, while also providing DC 24 V at the front terminals for external loads. The input accepts 120/230 V AC with automatic range switching. The output is electronically short-circuit protected and features overvoltage shutdown at < 28.8 V with automatic restart. Hunan Dream Road Electrical Technology Co., Ltd. provides reliable spare parts for your maintenance needs.
Automatic 120/230 V AC input selection, no manual switching required
10 A output current at DC 24 V, 240 W typical output power
Electronic short-circuit protection with automatic restart
Overvoltage shutdown at < 28.8 V, automatic recovery
Green LED for 24 V output status indication
Safety-isolated SELV output according to EN 60950-1
Parallel operation supported
Parameter | Specification |
|---|---|
Article Number | 6ES7307-1KA02-0AA0 |
Product Series | SIMATIC S7-300 / PS307 |
Input Voltage | 120/230 V AC (auto-selected) |
Input Range | 85–132 V AC / 170–264 V AC |
Line Frequency | 47–63 Hz |
Rated Input Current | 1.9 A (230 V) / 4.2 A (120 V) |
Output Voltage | DC 24 V (regulated, no-load stable) |
Output Current | 10 A (7 A above 60 °C) |
Output Power (typ.) | 240 W |
Efficiency (typ.) | 90% |
Short-Circuit Protection | Electronic, auto-restart |
Overvoltage Protection | Shutdown at < 28.8 V, auto-restart |
Status Indicator | Green LED (24 V OK) |
Parallel Operation | Supported |
Degree of Protection | IP20 |
Dimensions (W×H×D) | 80 × 125 × 120 mm |
Weight | Approx. 800 g |
Q1: Does this power supply need to be configured in the engineering software?
A1: No. The PS307 operates once inserted into slot 1 of the S7-300 rail. It does not need to be added to the hardware configuration.
Q2: What input-side protection device is recommended?
A2: A miniature circuit breaker rated 10 A with C-type trip characteristic (e.g., Siemens 5SN1 series) is recommended on the 230 V AC input line.
Q3: Can multiple units be connected in parallel?
A3: Yes. The module supports parallel operation. Output voltages must be matched and Siemens wiring guidelines for parallel current sharing must be followed.
Q4: How does the output recover after a short circuit?
A4: The module features automatic restart. Once the short circuit is removed, the output voltage recovers automatically without manual reset.
Q5: How to contact the supplier for a quotation?
A5: Please contact Hunan Dream Road Electrical Technology Co., Ltd. at Tel: 17620734453 or Email: 1772989321@qq.com.