6ES7322-1FL00-0AA0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The module uses solid-state AC outputs arranged in groups of 8 points (4 groups in total). Each group has its own fuse and a blown-fuse indicator (SF), so a fault can be pinpointed on site for fast maintenance and troubleshooting. The channels are optically isolated from the backplane bus, preventing power circuits from interfering with the CPU and providing strong noise immunity.
The module is double-width and requires 2 × 20-pin front connectors. Every channel has a green status LED, plus a red fault indicator. Because the outputs are AC type, they cannot drive DC loads; for inductive loads (contactor coils, solenoid valves) an RC snubber is recommended to suppress surges and extend module life. Note that this model is now listed as a spare part (Prod. Cancellation) — confirm availability and alternatives before selecting it for new projects.
32 AC outputs: 120/230V AC at 1 A per point, switching 220V AC loads directly without interposing relays.
Grouped protection, 8 points per group: 4 independent groups, each with a fuse and blown-fuse indicator for fast fault location.
Optical isolation: channels isolated from the backplane bus, separating power and control circuits with high noise immunity.
Wide load compatibility: directly drives AC contactors, AC solenoid valves, starters, small motors and indicator lamps.
Visible status: a green status LED per channel plus a red fault indicator for straightforward commissioning and troubleshooting.
Double-width design: high-density outputs — 32 AC channels within a compact rack footprint.
Part Number | 6ES7322-1FL00-0AA0 (SM 322, 32 DO, AC 120/230V, 1 A) |
|---|---|
System | SIMATIC S7-300 |
Number of Outputs | 32 digital outputs (solid-state AC outputs) |
Rated Load Voltage | AC 120 V / AC 230 V |
Output Current per Point | 1 A |
Grouping | 4 groups × 8 points, each with fuse and blown-fuse indicator (SF) |
Isolation | Optical isolation between channels and backplane bus; potential isolation between groups |
Status Indication | Green status LED per channel; red fault / group error indicator |
Suitable Loads | AC contactors, AC solenoid valves, starters, small motors, indicator lamps and other AC loads |
Diagnostics | None (fuse and status indication only; no wire-break / short-circuit diagnostics) |
Front Connectors | 2 × 20-pin front connectors (ordered separately) |
Dimensions | Double-width module (approx. 80 mm wide) |
Weight | Approx. 0.57 kg |
Protection / Operating Temperature | IP20; 0–60 °C (horizontal mounting) |
Product Status | Spare part (Prod. Cancellation); confirm alternatives for new projects |
Q1: Is this a relay output or transistor output module?
A: Neither. It is a solid-state AC output module (AC 120/230V, 1 A per point) for switching AC loads directly. Do not confuse it with the relay SM 322 variants (e.g. 1FH00) or the DC 24V transistor variants — some online listings incorrectly describe it as "32 relay outputs, 2 A", but the official Siemens data governs.
Q2: Can it drive DC 24V loads?
A: No. The outputs are AC only and drive AC 120/230V loads. For DC loads, use a DC 24V transistor SM 322 module.
Q3: Can 1 A per point drive an AC contactor directly?
A: It can drive small to medium AC contactor coils and AC solenoid valves, but consider the inrush current and power factor of the contactor. For large contactors or frequent switching, use an interposing relay and add an RC snubber across inductive loads.
Q4: What is the purpose of the blown-fuse indicator?
A: The outputs are divided into 4 groups of 8, each with its own fuse and a blown-fuse / group error indicator. If a short circuit or overload blows a fuse, the corresponding LED lights up, immediately identifying which group of 8 is affected.
Q5: How many front connectors are needed?
A: The module is double-width and requires 2 × 20-pin front connectors (with matching terminal blocks and cables). Front connectors are not included and must be ordered separately.
Q6: Is this model still available? Can it be used in new projects?
A: In Siemens' product lifecycle it is listed as a spare part (Prod. Cancellation), mainly for maintaining and replacing existing installations. For new projects, confirm the available replacement model with Siemens or your distributor first.