6ES7134-6FB00-0BA1
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The 6ES7134-6FB00-0BA1 is an analog input module from the SIMATIC ET 200SP distributed I/O system, specifically the AI 2xU Standard series. It is designed for voltage measurement in industrial automation applications.
Key electrical data: supply voltage 24V DC (19.2-28.8V); 2 analog input channels for voltage measurement; measurement ranges 0-10V (15-bit), 1-5V (15-bit), ±10V (16-bit including sign), and ±5V (16-bit including sign); input resistance 180 kΩ for all ranges; destruction limit 30V; cycle time (all channels) minimum 500 μs.
The module supports 1-wire and 2-wire connections via BU type A0 or A1. It does NOT provide 24V encoder supply or additional 24V encoder supply [citation:1]. Measurement principle is Sigma-Delta with parameterizable integration time. Interference frequency suppression: 16.6 / 50 / 60 Hz / off. Conversion time per channel: 50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6 Hz, 250 μs without filter [citation:6].
Diagnostics include module diagnostics and diagnostic alarms. Status is indicated via PWR LED, channel status LEDs, and DIAG LED.
Isolation: Channels are isolated from the backplane bus and electronics power supply, but NOT isolated from each other.
Mechanical data: dimensions 15 x 73 x 58 mm (W x H x D); net weight approximately 38 g [citation:4]. Fits BU type A0 or A1. Color code CC00. Engineering via TIA Portal V13 SP1 or STEP 7 V5.5 SP3 or higher [citation:1].
Product Lifecycle: PM300 (Active Product). Every unit is 100% tested before shipping.• 2 Voltage Inputs: 0-10V, 1-5V, ±10V, ±5V with 16-bit resolution (±10V/±5V).
• High Input Resistance: 180 kΩ for accurate voltage measurement.
• Sigma-Delta Measurement: Parameterizable integration time and interference suppression.
• Module Diagnostics: Diagnostic alarms and status LEDs for monitoring.
• ET 200SP Platform: Fits BU type A0 or A1 (BaseUnit not included).
• Compact Design: 15mm width, approx. 38g net weight.
• Active Product: PM300 lifecycle — not a discontinued spare part.
• 100% Tested: Every module undergoes rigorous functional testing before dispatch.General Information:
• Product Type: AI 2xU ST
• Product Family: SIMATIC ET 200SP
• Product Lifecycle: PM300 (Active Product)
• Hardware Functional Status: FS21 or higher
• Firmware Version: V1.0.1 (updatable)
• Usable BaseUnits: BU type A0, A1
• Color Code: CC00
• Net Weight: Approx. 38 g
• Country of Origin: Germany
Supply:
• Rated Supply Voltage (DC): 24 V
• Permissible Range: 19.2 V to 28.8 V DC
• Reverse Polarity Protection: Yes
• Current Consumption (max): 37 mA
• Power Loss (typical): 0.9 W
Analog Inputs:
• Number of Inputs: 2 (voltage)
• Measurement Ranges: 0-10V, 1-5V, ±10V, ±5V
• Resolution: 15 bit (0-10V/1-5V); 16 bit incl. sign (±10V/±5V)
• Input Resistance: 180 kΩ (all ranges)
• Destruction Limit: 30 V
• Cycle Time (all channels, min): 500 μs
Encoder Supply:
• 24V Encoder Supply: No
• Additional 24V Encoder Supply: No
Diagnostics:
• Module Diagnostics: Yes
• Diagnostic Alarm: Yes
• Limit Value Alarm: No
• LEDs: PWR, Channel Status, DIAG
Isolation:
• Channel-to-Channel: No
• Channel-to-Backplane Bus: Yes
• Channel-to-Electronics Power: Yes
• Permissible Potential Difference (UCM): 10 V
Measurement:
• Principle: Sigma-Delta
• Integration Time: Parameterizable
• Interference Suppression: 16.6 / 50 / 60 Hz / off
• Conversion Time: 50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6 Hz, 250 μs without filter
• Smoothing: 4 levels (None/Weak/Medium/High)
Mechanical Data:
• Dimensions (W x H x D): 15 x 73 x 58 mm
• Weight: Approx. 38 g
Environmental:
• Operating Temperature (Horizontal): -30°C to +60°C
• Protection Class: IP20
Engineering:
• TIA Portal: V13 SP1 or higher
• STEP 7: V5.5 SP3 or higherQ: Does this module provide 24V sensor supply?
A: No. The 6ES7134-6FB00-0BA1 does NOT provide 24V encoder supply or additional 24V encoder supply. If your sensor requires 24V power, please supply it externally or use a different module.
Q: Are the channels isolated from each other?
A: No. The channels are isolated from the backplane bus and electronics power supply, but NOT from each other. Permissible potential difference between inputs is 10 V.
Q: Can this module measure current (4-20mA)?
A: No. This is a voltage input module (AI 2xU). For current measurement, please use 6ES7134-6GB00-0BA1 (AI 2xI).
Q: What BaseUnit do I need?
A: Use BU type A0 or A1. The BaseUnit is not included and must be ordered separately.
Q: What is the resolution?
A: 15 bits for 0-10V and 1-5V ranges; 16 bits including sign for ±10V and ±5V.
Q: What is the product lifecycle status?
A: This is an active product (PM300 lifecycle). Contact us for current stock and shipping rates.