6ES7431-1KF10-0AB0
Siemens
| Availability: | |
|---|---|
| Quantity: | |
he 6ES7431-1KF10-0AB0 is an analog input module from the SIMATIC S7-400 family, specifically the SM 431 series. It provides 8 analog input channels with 14-bit resolution and is isolated from the CPU.
Supported input types include voltage (±80mV, ±250mV, ±500mV, ±1V, ±2.5V, ±5V, 1-5V, ±10V), current (0-20mA, 4-20mA, ±20mA), resistance (48Ω, 150Ω, 300Ω, 600Ω, 6000Ω), thermocouples (B, E, J, K, L, N, R, S, T, U), and RTD (Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000).
Important Channel Limitation: All 8 channels are available for voltage and current measurement. However, for resistance and temperature measurement, only 4 channels can be used (channels 0, 2, 4, or 6). The adjacent channel (n+1) must be deactivated because its terminals are used for current supply to the resistor connected at channel n.
Configuration Note: Measuring range modules on the side must match the sensor type and STEP 7 settings. For voltage ±1V and resistance/thermocouple/Pt100, use position A. For voltage 1-5V/±10V, use position B. For 4-wire current, use position C. For 2-wire current, use position D.
For 2-wire transmitters, an external 24V DC supply must be connected to the L+ terminals. The module can supply up to 50mA to the transmitters.
Mechanical data: dimensions 25 x 290 x 210 mm (W x H x D); weight approximately 500g.
Every unit is 100% tested before shipping.• 8 Analog Inputs: 14-bit resolution, isolated from CPU.
• Universal Input Types: Voltage, current, resistance, thermocouple, and RTD.
• Thermocouple Support: Types B, E, J, K, L, N, R, S, T, U.
• RTD Support: Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000.
• 2-Wire Transmitter Supply: L+ terminals provide power (external 24V DC required, max 50mA).
• Measuring Range Modules: A/B/C/D positions for sensor matching.
• Channel Limitation: Resistance/temperature measurement limited to 4 channels.
• 100% Tested: Every module undergoes rigorous functional testing before dispatch.General Information:
• Product Type: SM 431, AI 8 x 14 Bit
• Product Family: SIMATIC S7-400
• Number of Analog Inputs: 8
• Resolution: 14 bits
• Isolation: Analog section isolated from CPU
Input Ranges (Voltage):
• ±80mV, ±250mV, ±500mV, ±1V, ±2.5V, ±5V, 1-5V, ±10V
• Input Resistance: 1 MΩ (all voltage ranges)
Input Ranges (Current):
• 0-20mA, 4-20mA, ±20mA
• Input Resistance: 50 Ω
Input Ranges (Resistance):
• 0-48Ω, 0-150Ω, 0-300Ω, 0-600Ω, 0-6000Ω (usable up to 5000Ω)
• Constant Measuring Current: Typ. 1.67 mA
Input Ranges (Thermocouple):
• Types: B, E, J, K, L, N, R, S, T, U
Input Ranges (RTD):
• Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000
Channel Limitation:
• Voltage/Current: All 8 channels
• Resistance/Temperature: 4 channels only (0, 2, 4, 6)
Power Supply:
• Load Voltage L+ (rated): 24V DC (only for 2-wire transmitters)
• Current from L+ (max): 200 mA (8 transmitters)
• Current from Backplane Bus 5V DC (max): 600 mA
• Power Loss (typ.): 3.5 W
Mechanical Data:
• Dimensions (W x H x D): 25 x 290 x 210 mm
• Weight: Approx. 500 gQ: Can all 8 channels be used for RTD/thermocouple measurement?
A: No. Only 4 channels (0, 2, 4, 6) can be used for resistance or temperature measurement. The adjacent channel (1, 3, 5, 7) must be deactivated because its terminals are used for current supply to the resistor.
Q: How do I configure the measuring range modules?
A: Position A: Voltage ±1V, resistance, thermocouple, Pt100. Position B: Voltage 1-5V/±10V. Position C: 4-wire current. Position D: 2-wire current. Settings must match STEP 7 hardware configuration.
Q: Can this module supply power to 2-wire transmitters?
A: Yes, but an external 24V DC supply must be connected to the L+ terminals. The module can supply up to 50mA to the transmitters.
Q: What front connector is required?
A: This module requires a 48-pin front connector (not included). Please order separately.
Q: Is this product tested?