EL3154
Beckhoff
| Availability: | |
|---|---|
| Quantity: | |
The EL3154 is an analog input terminal from the Beckhoff EtherCAT Terminal system, specifically the EL Ed3xxx series. It processes signals in the 4…20 mA range and digitizes them with 16-bit resolution (including sign), then transmits them electrically isolated to the higher-level automation device.
The module provides 4 single-ended inputs with an internal resistance of typically 85 Ω + diode voltage. Input filter limit frequency is 5 kHz, and conversion time is approximately 100 μs. Measurement error is less than ±0.3% relative to full scale value.
A key feature of the EL3154 is its support for Distributed Clocks, enabling precise time synchronization across the EtherCAT network. The 24V power contact is fed to the terminal, allowing direct connection of 2-wire sensors without an external power supply. The input electronics are independent of the power contact supply voltage.
The module supports activatable FIR/IIR filters and limit value monitoring. Signal state and error conditions (overload, broken wire) are indicated via LEDs. Configuration requires no address or settings; the terminal is configured via TwinCAT System Manager.
Mechanical data: 12 mm width, 12 x 100 x 68 mm (W x H x D), approximately 60 g, IP20 protection.
Product status: Regular delivery. Every unit is 100% tested before shipping.• 4 Analog Inputs: 4…20 mA, single-ended.
• 16-Bit Resolution: High-precision current measurement.
• Distributed Clocks: Precise time synchronization across the EtherCAT network.
• 2-Wire Sensor Support: 24V power contact fed to terminal — no external supply needed.
• Fast Conversion: ~100 µs conversion time.
• Activatable FIR/IIR Filters: Flexible signal conditioning.
• Limit Value Monitoring: Built-in threshold checking.
• Error Diagnostics: LED indicators for overload and broken wire.
• No Configuration Needed: No address or settings required.
• Regular Delivery: Actively supplied product — not a discontinued spare part.
• 100% Tested: Every unit undergoes rigorous functional testing before dispatch.General Information:
• Product Type: EtherCAT Terminal, Analog Input
• Product Family: Beckhoff EL Ed3xxx
• Number of Inputs: 4 (single-ended)
• Signal Current: 4…20 mA
• Resolution: 16 bit (incl. sign)
• Product Status: Regular delivery
Electrical Data:
• Distributed Clocks: Yes
• Internal Resistance: Typ. 85 Ω + diode voltage
• Input Filter Limit Frequency: 5 kHz
• Dielectric Strength: Max. 30 V
• Conversion Time: ~100 µs
• Measurement Error/Uncertainty: < ±0.3% (relative to full scale)
• Electrical Isolation: 500 V (E-bus / signal voltage)
• E-bus Current Consumption: Typ. 130 mA
• Power Contacts Current Consumption: –
Process Image:
• Bit Width in Process Image: Inputs 16 byte
• Configuration: No address or configuration setting required
• Special Features: Standard and compact process image, activatable FIR/IIR filters, limit value monitoring
Mechanical Data:
• Dimensions (W x H x D): 12 mm x 100 mm x 68 mm
• Weight: Approx. 60 g
• Housing: EL-12-8pin compact terminal housing with signal LEDs
• Material: Polycarbonate
• Mounting: 35 mm DIN rail per EN 60715
Environmental:
• Operating Temperature: -25°C to +60°C
• Storage Temperature: -40°C to +85°C
• Relative Humidity: 95%, no condensation
• Protection Class: IP20
• Installation Position: Variable
Approvals/Markings:
• CE, CCC, UL, ATEX, IECEx, cFMusQ: What is the signal range of the EL3154?
A: The EL3154 measures 4…20 mA current signals with 16-bit resolution (including sign).
Q: Does this module support 2-wire sensors?
A: Yes. The 24V power contact is connected to the terminal, allowing direct connection of 2-wire sensors without an external power supply.
Q: What are Distributed Clocks and why are they important?
A: Distributed Clocks (DC) enable precise time synchronization across the EtherCAT network. This is important for applications requiring synchronized data acquisition across multiple channels or axes.
Q: What is the conversion time?
A: Approximately 100 µs.
Q: Is this a Beckhoff or Siemens product?
A: This is a Beckhoff Automation product from the EtherCAT Terminal series.
Q: Does this module need configuration?
A: No address or configuration settings are required. The terminal is configured via TwinCAT System Manager.
Q: Is this product tested?
A: Yes. We supply tested units that are 100% functionally verified before dispatch. Contact us for current stock and shipping rates.