The 6ES7405-0KA02-0AA0 is a SIMATIC S7-400 PS 405 power supply module with a wide-range DC input of 24V, 48V, or 60V. It provides a 5V DC / 10A output for the backplane bus and a 24V DC / 1A output for peripherals.

The module occupies 2 slots in the S7-400 rack and features short-circuit protection, mains buffering of 20 ms (NAMUR compliant), and an optional backup battery (2x AA lithium) for data retention during power failure.

Note: This is the standard (non-redundant) version. For redundant operation, the 6ES7405-0KR02-0AA0 (PS 405 10A R) is required.

Every unit is 100% tested before dispatch.
  • 6ES7405-0KA02-0AA0

  • Siemens

Availability:
Quantity:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
sharethis sharing button
The 6ES7405-0KA02-0AA0 is a PS 405 power supply module from the SIMATIC S7-400 family. It converts a wide-range DC input (24V, 48V, or 60V) into the voltages required by the S7-400 backplane bus and peripherals.

Key electrical data: input current 4A at 24V DC, 2A at 48V DC, 1.6A at 60V DC; output 5V DC / 10A (backplane bus, no base load required) and 24V DC / 1A (short-circuit proof); power loss typically 20W; mains buffering 20 ms per NAMUR recommendation.

The module occupies 2 slots in the S7-400 rack. An optional backup battery (2x lithium AA, 3.6V) can be installed for data retention during power failures.

Important: This is the standard version (0KA02). It is NOT the redundant type. For redundant power supply configurations in H-systems, the 6ES7405-0KR02-0AA0 (PS 405 10A R) must be used instead.

Mechanical data: dimensions 50 x 290 x 217 mm (W x H x D); weight approximately 1.2 kg; protection class I with protective conductor.

Every unit is 100% tested before shipping.
• Wide-Range DC Input: Accepts 24V, 48V, or 60V DC — flexible for different power systems.
• Dual Output: 5V DC / 10A for backplane bus + 24V DC / 1A for peripherals.
• Short-Circuit Protection: Built-in safety for connected equipment.
• Mains Buffering: 20 ms hold-up time, NAMUR compliant.
• Optional Backup Battery: 2x AA lithium for data retention during power failure.
• Standard Version (0KA02): For redundant configurations, use 6ES7405-0KR02-0AA0.
• Compact 2-Slot Design: Fits standard S7-400 racks.
• 100% Tested: Every module undergoes rigorous functional testing before dispatch.
General Information:
• Product Type: PS 405 Power Supply Module
• Product Family: SIMATIC S7-400
• Required Slots: 2
• Protection Class: I (with protective conductor)

Input:
• Rated Input Voltage: 24V DC / 48V DC / 60V DC
• Input Current at 24V DC: 4 A
• Input Current at 48V DC: 2 A
• Input Current at 60V DC: 1.6 A
• Inrush Current (max): 18 A (half-width 20 ms)
• Mains Buffering: 20 ms (NAMUR compliant)

Output:
• Output Voltage: 5V DC and 24V DC
• Output Current (5V DC, backplane bus): 10 A max (no base load required)
• Output Current (24V DC, peripheral): 1 A max (short-circuit proof)
• Short-Circuit Protection: Yes

Power:
• Active Power Input (typ.): 95 W
• Power Loss (typ.): 20 W

Backup Battery:
• Optional: 2x lithium AA, 3.6V / 2.2 Ah

Mechanical Data:
• Dimensions (W x H x D): 50 x 290 x 217 mm
• Weight: Approx. 1.2 kg

Environmental:
• Operating Temperature: 0°C to 60°C
• Storage Temperature: -40°C to +85°C

Approvals:
• FM, CCC, BIS, UL, ATEX, IECEx, Marine (ABS/BV/DNV/LR/NK/PRS/RINA/RMRS/CCS)
Q: What is the difference between 6ES7405-0KA02-0AA0 and 6ES7405-0KR02-0AA0?
A: The 0KA02 is the standard PS 405 power supply. The 0KR02 is the redundant version (PS 405 10A R), designed for redundant configurations where two power supplies feed the same rack. For H-systems or redundant power requirements, the 0KR02 must be used.

Q: What input voltages does this module accept?
A: It accepts 24V DC, 48V DC, or 60V DC input (wide-range).

Q: What are the output specifications?
A: 5V DC / 10A for the backplane bus and 24V DC / 1A for peripherals.

Q: Does this module include a backup battery?
A: No. The backup battery is optional. Two lithium AA cells (3.6V) can be installed separately for data retention during power failure.

Q: How many slots does this module occupy?
A: 2 slots in the S7-400 rack.

Q: Is this product tested?
A: Yes. We supply tested units that are 100% functionally verified before dispatch. Contact us for current stock and shipping rates.
Previous: 
Next: 

PRODUCTS

PRODUCTS

QUICK LINKS

CONTACT

+86-176-2073-4453
No. 858 Dujuan Road, Wangyue Subdistrict, Hunan Xiangjiang New Area,China
© 2026 Hunan Dream Road Electrical Technology Co., Ltd. All Rights Reserved. 
Privacy Policy            Sitemap