6ES7132-6HD01-0BB1
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The 6ES7132-6HD01-0BB1 is a relay output module from the SIMATIC ET 200SP distributed I/O system, specifically the RQ (Relay Output) series. It provides 4 normally open (NO) relay contacts for switching resistive, inductive, and lamp loads.
Key electrical data: supply voltage 24V DC (19.2-28.8V); load voltage range 120V DC to 230V AC; maximum switching current 5A per channel; maximum switching frequency 2 Hz for resistive load, 0.5 Hz for inductive load (DC13). The relay contacts are isolated from each other and from the backplane bus, with isolation tested at 2500V DC.
The module fits BaseUnit types B0 (3-wire connection) and B1 (2-wire connection), and supports redundancy capability. I&M data (I&M0 to I&M3) is supported for identification and maintenance.
Critical Safety Notes:
- NO integrated short-circuit protection. External miniature fuse required (max. 6.3A, fast-acting, breaking capacity ≥1500A for mains).
- For inductive DC loads with switching frequency >0.1 Hz, an external freewheeling diode must be installed.
- Do not mix SELV/PELV and dangerous live voltages between channels simultaneously.
Mechanical data: net weight approximately 51g; country of origin Germany. Engineering via TIA Portal V14 or STEP 7 V5.5 SP3 or higher.
Product Lifecycle: PM300 (Active Product). Every unit is 100% tested before shipping.• 4 Relay Outputs: Normally open (NO) contacts, electrically isolated.
• Wide Load Voltage: 120V DC to 230V AC — one module for mixed AC/DC loads.
• 5A Switching Current: Directly drives contactors, solenoids, and lamps.
• True Dry Contacts: No leakage current, suitable for critical loads.
• ET 200SP Platform: Fits BU type B0 (3-wire) or B1 (2-wire).
• Redundancy Capable: Supports redundant configurations.
• I&M Data Support: I&M0 to I&M3 for identification and maintenance.
• External Fusing Required: No integrated short-circuit protection.
• Active Product: PM300 lifecycle — not a discontinued spare part.
• 100% Tested: Every module undergoes rigorous functional testing before dispatch.General Information:
• Product Type: RQ 4x120VDC...230VAC/5A NO ST
• Product Family: SIMATIC ET 200SP
• Product Lifecycle: PM300 (Active Product)
• Country of Origin: Germany
• Net Weight: Approx. 51 g
Supply:
• Supply Voltage (DC): 24 V (19.2 V to 28.8 V)
• Input Current (no load, rated): 55 mA
• Power Loss (typical): 1.5 W
• Reverse Polarity Protection: Yes
Outputs:
• Type: Relay, normally open (NO)
• Number of Outputs: 4
• Load Voltage Range: 120V DC to 230V AC
• Max. Switching Current: 5 A per channel
• Short-Circuit Protection: No (external fuse required)
• Switching Frequency (Resistive): Max. 2 Hz
• Switching Frequency (Inductive, DC13): Max. 0.5 Hz
• Parallel Switching for Logic: Yes
• Parallel Switching for Power Increase: No
• Parallel Switching for Redundant Load: Yes
Isolation:
• Channel-to-Channel: Yes
• Channel-to-Backplane Bus: Yes
• Isolation Tested With: 2500V DC
• Permissible Potential Difference (Channels to Backplane): AC 240 V
BaseUnit Compatibility:
• BU Type B0: 3-wire connection
• BU Type B1: 2-wire connection
• Color Code: CC40
• Mechanical Coding Element: Type C
Engineering:
• TIA Portal: V14 or higher
• STEP 7: V5.5 SP3 or higher
• PCS 7: V8.1 SP1 or higher
Environmental:
• Operating Temperature (Horizontal): -30°C to +60°C
• Operating Temperature (Vertical): -30°C to +50°C
• Protection Class: IP20Q: Does this module have built-in short-circuit protection?
A: No. The relay channels have NO integrated short-circuit protection. You must provide external fusing, typically a 6.3A fast-acting miniature fuse. For mains voltages, the breaking capacity should be at least 1500A.
Q: Can this module switch both AC and DC loads?
A: Yes. The relay contacts support load voltages from 120V DC to 230V AC, making it suitable for mixed applications.
Q: What BaseUnit do I need?
A: Use BU type B0 for 3-wire connection or BU type B1 for 2-wire connection. The module does not include a BaseUnit.
Q: What should I do for inductive DC loads?
A: For inductive DC loads with switching frequency above 0.1 Hz, install an external freewheeling diode to protect the relay contacts.
Q: Is this a Siemens or Beckhoff product?
A: This is a Siemens SIMATIC ET 200SP product, not Beckhoff.
Q: Is this product active or discontinued?
A: This is an active product (PM300 lifecycle). Contact us for current stock and shipping rates.