6ES7134-6GB00-0BA1
Siemens
| Availability: | |
|---|---|
| Quantity: | |
The 6ES7134-6GB00-0BA1 is an analog input module from the SIMATIC ET 200SP distributed I/O system, specifically the AI 2xI 2/4-wire ST (Standard) series. It is designed for current measurement in industrial automation applications.
Key electrical data: supply voltage 24V DC (19.2-28.8V); 2 analog input channels; measurement ranges 0-20 mA (15-bit), 4-20 mA (15-bit), and ±20 mA (16-bit including sign); input resistance 130 Ω (90 Ω for 2-wire); destruction limit 50 mA; cycle time (all channels) minimum 500 μs.
The module supports both 2-wire and 4-wire current transmitters. For 2-wire transmitters, the module provides 24V sensor supply with a total current of max. 50 mA for both channels (short-circuit protected). For 4-wire transmitters, the additional encoder supply provides max. 200 mA (module-level short-circuit protected).
Diagnostics include: module diagnostics, diagnostic alarms, wire break detection (with 4-20 mA only), short-circuit in sensor supply, overflow/underflow, and supply voltage monitoring. Status is indicated via PWR LED (green), channel status LEDs (green), and DIAG LED (green/red).
Isolation: Channels are isolated from the backplane bus and from the electronics power supply, but NOT isolated from each other. Permissible potential difference between inputs (UCM) is 10 Vpp.
Measurement principle is Sigma-Delta with parameterizable integration time. Interference frequency suppression: 16.6 / 50 / 60 Hz / off. Conversion time per channel: 50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6 Hz, 500 μs without filter. Smoothing is parameterizable in 4 levels.
Mechanical data: dimensions 15 x 73 x 58 mm (W x H x D); weight approximately 32 g. Fits BU type A0 or A1. Color code CC05. Engineering via TIA Portal V13 SP1 or STEP 7 V5.5 SP3 or higher.
Product Lifecycle: PM300 (Active Product). Every unit is 100% tested before shipping.• 2 Current Inputs: 0-20 mA, 4-20 mA, ±20 mA with 16-bit resolution (±20 mA).
• 2-Wire & 4-Wire Support: Direct connection of both transmitter types.
• Sensor Supply: 24V DC, max. 50 mA (2-wire) / 200 mA (4-wire), short-circuit protected.
• Module Diagnostics: Wire break (4-20 mA), overflow/underflow, supply monitoring.
• Sigma-Delta Measurement: Parameterizable integration time and interference suppression.
• ET 200SP Platform: Fits BU type A0 or A1 (BaseUnit not included).
• Hot-Swap Capable: Supports module replacement during operation.
• Active Product: PM300 lifecycle — not a discontinued spare part.
• 100% Tested: Every module undergoes rigorous functional testing before dispatch.General Information:
• Product Type: AI 2xI 2-/4-wire ST
• Product Family: SIMATIC ET 200SP
• Product Lifecycle: PM300 (Active Product)
• Hardware Functional Status: FS22 or higher
• Firmware Version: V2.0.0 (updatable)
• Usable BaseUnits: BU type A0, A1
• Color Code: CC05
• Net Weight: Approx. 32 g
Supply:
• Rated Supply Voltage (DC): 24 V
• Permissible Range: 19.2 V to 28.8 V DC
• Reverse Polarity Protection: Yes
• Current Consumption (rated): 37.5 mA
• Current Consumption (max): 245 mA (including sensor supply)
• Power Loss (typical): 0.9 W (rated voltage, 50% active channels)
Analog Inputs:
• Number of Inputs: 2
• Measurement Ranges: 0-20 mA, 4-20 mA, ±20 mA
• Resolution: 15 bit (0-20/4-20 mA); 16 bit incl. sign (±20 mA)
• Input Resistance: 130 Ω (90 Ω for 2-wire)
• Destruction Limit: 50 mA
• Cycle Time (all channels, min): 500 μs
Sensor Supply:
• 24V Sensor Supply (2-wire): Yes, max. 50 mA total (short-circuit protected)
• Additional 24V Encoder Supply (4-wire): Yes, max. 200 mA total (module-level short-circuit protected)
Diagnostics:
• Module Diagnostics: Yes
• Diagnostic Alarm: Yes
• Wire Break: Yes (with 4-20 mA)
• Short-Circuit (Sensor Supply): Yes
• Overflow/Underflow: Yes
• Supply Voltage Monitoring: Yes
• LEDs: PWR (green), Channel Status (green), DIAG (green/red)
Isolation:
• Channel-to-Channel: No
• Channel-to-Backplane Bus: Yes
• Channel-to-Electronics Power: Yes
• Isolation Tested With: 707 V DC (Type Test)
• Permissible Potential Difference (UCM): 10 Vpp
Measurement:
• Principle: Sigma-Delta
• Integration Time: Parameterizable
• Interference Suppression: 16.6 / 50 / 60 Hz / off
• Conversion Time: 50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6 Hz, 500 μs without filter
• Smoothing: 4 levels, parameterizable
Mechanical Data:
• Dimensions (W x H x D): 15 x 73 x 58 mm
• Weight: Approx. 32 g
Environmental:
• Operating Temperature (Horizontal): -30°C to +60°C
• Protection Class: IP20
Engineering:
• TIA Portal: V13 SP1 or higher
• STEP 7: V5.5 SP3 or higherQ: Are the channels isolated from each other?
A: No. The channels are isolated from the backplane bus and the electronics power supply, but NOT from each other. Permissible potential difference between inputs (UCM) is 10 Vpp. If you need channel-to-channel isolation, please select a different module.
Q: Can this module connect to 2-wire transmitters?
A: Yes. The module provides a 24V sensor supply with a total current of max. 50 mA for both channels (short-circuit protected). For 4-wire transmitters, an additional encoder supply provides max. 200 mA.
Q: What is the resolution?
A: 15 bits for 0-20 mA and 4-20 mA ranges; 16 bits including sign for ±20 mA.
Q: Does this module support wire break detection?
A: Yes, but only with the 4-20 mA range.
Q: What BaseUnit do I need?
A: Use BU type A0 or A1. The BaseUnit is not included and must be ordered separately.
Q: What is the product lifecycle status?
A: This is an active product (PM300 lifecycle). Contact us for current stock and shipping rates.